background image

5

Installation and Operation
Blood Bank Refrigerators

6.2

Display Functions

Table 2. 

Control Panel Display Functions

6.3

Programming Functions

You can enter programming mode by pressing   and holding for 5 seconds. Pressing   repeatedly scrolls through the available setpoint 
functions: warm alarm and cold alarm. 

Table 3. 

Setpoint Programming Functions

6.4

Service Parameters

You can access service parameters by entering programming mode and pressing   for an additional 5 seconds. Pressing   repeatedly 
scrolls through the available service functions. While you are in service mode, the wrench icon is illuminated. For any displayed 
parameter you can use

  

and

 

 to adjust the value

CAUTION!

Resetting any of the following parameter values could adversely affect the performance of your blood bank 

refrigerator. These settings very rarely need to be changed for 4ºC operation. Be sure to call Revco Service before 
making any adjustments to service parameter values.

Table 4. 

Service Parameters

Function

Meaning

Sequence

Display

Normal operation

Default display while refrigerator 
is running

 —

Temperature display and thermometer show cabinet 
temperature.

Cold excursion

Show coldest cabinet temperature 
since last startup or reset 

Press 

Display shows cold excursion while button is pressed. 

Warm excursion

Show warmest cabinet temperature 
since last startup or reset 

Press 

Display shows warm excursion while button is pressed. 

Mute

Silence audible alarm

Press 

Display and thermometer show cabinet temperature, 
alarm icon continues to flash. 

Reset

Return to default display after 
excursion or alarm condition

Press 

 and 

 

simultaneously, hold 
for five seconds

Excursion values are reset; temperature display shows 
cabinet temperature.

Alarm test

Test by simulating warm alarm 
conditions

Press 

 and 

 

simultaneously, hold 
for five seconds

Display and thermometer show simulated cabinet 
temperature, alarms flash and sound as appropriate. 
Display blinks twice when test is completed.

Lower sensor

Display lower cabinet temperature

Press 

 and 

 

simultaneously and 
hold

Display shows lower cabinet temperature while buttons 
are held, returns to upper cabinet temperature when 
buttons are released.

Function

Programming Sequence

Adjust cold alarm setpoint

Enter programming mode by pressing 

 

and holding for 5 seconds. On release, the current cold alarm 

setpoint value flashes in the temperature display; use 

 and 

 to adjust it. The display automatically returns 

to normal operating mode 30 seconds after the last key entry or after scrolling through both available 
functions.

Adjust warm alarm setpoint

Enter programming mode and press 

 

repeatedly until the top of the thermometer is illuminated. The current 

warm alarm setpoint value then flashes in the temperature display; use 

 and 

 to adjust it. The display 

automatically returns to normal operating mode 30 seconds after the last key entry or after scrolling through 
both available functions. 

Parameter

Notes

Parameter

Notes

1. Offset

Center air temperature calibration. Default value is 0.

6. Defrost Duration

Range 5 to 30 minutes; default value is 15.

2. Line voltage

Display only.

7. Defrost Termination

Temperature at evaporator at which defrost 
cycle terminates; default value is 4ºC.

3. Cut On

Cabinet temperature at which compressor starts to 
cool down to setpoint. Default value is 5ºC.

8. Short Cycle Delay

Range 0 to 15 minutes; default value is 0.

4. Differential

Offset – differential = temperature at which 
compressor stops after achieving cabinet temperature 
setpoint. Default value is 2.

9. Control Probe 

Temperature

Display only.

5. Defrost Interval

Range 1 to 12 hours; default value is 1.

10. Defrost Probe 

Temperature

Display only.

Summary of Contents for REB-1204

Page 1: ...ining this product please be sure to read this manual and product warning labels carefully Failure to follow these instructions may cause this product to malfunction which could result in injury or damage Below are important safety precautions that apply to this product Use this product only in the way described in the product literature and in this manual Before using it verify that this product ...

Page 2: ...ed power lines Always connect the equipment to a dedicated separate circuit Electrical codes require fuse or circuit breaker protection for branch circuit conductors Use time delay fuses for 12 AWG circuits For all blood bank models the wiring diagram is attached to the back of the cabinet 4 3 Leveling The unit must be level Rotate the leveling screws located under the front corners of the unit un...

Page 3: ...g tabs from the slots on the slides Note The drawers fit snugly between the slides Push the back of the drawer from underneath to remove the drawer 3 Raise the back of the drawer almost to a vertical position and disengage the front mounting clips from the slides To remove the drawers on Space Saver models depress the hooks located on both sides of the drawers about 1 3 of the way back and slide t...

Page 4: ...nts are 8ºC and 0ºC Then the number of bars illuminated indicates cabinet temperature as follows bulb only 0ºC cold alarm 6 bars 4 8 1 bar 0 8 7 bars 5 6 2 bars 1 6 8 bars 6 4 3 bars 2 4 9 bars 7 2 4 bars 3 2 10 bars 8 warm alarm 5 bars 4 setpoint When cabinet temperature exceeds the warm alarm setpoint the top bar of the thermometer flashes When temperature is lower than the cold alarm setpoint t...

Page 5: ...larm test Test by simulating warm alarm conditions Press and simultaneously hold for five seconds Display and thermometer show simulated cabinet temperature alarms flash and sound as appropriate Display blinks twice when test is completed Lower sensor Display lower cabinet temperature Press and simultaneously and hold Display shows lower cabinet temperature while buttons are held returns to upper ...

Page 6: ...r critical applications such as blood storage be sure that the alarm systems are working and active before you load any product 7 3 Automatic Defrost The defrosting process on all models is primarily accomplished by air circulated during off cycle periods All models are equipped with a built in on demand defrost feature which is preset at the factory The units defrost only under the most severe co...

Page 7: ...e purple and red white wires must be tied together in this application The wiring diagram is attached to the inside of the alarm back cover 9 4 Alarm Test Note It is important to test your alarm system after any maintenance operation or temperature control adjustment 9 4 1 Theory of Operation This test procedure applies to both factory installed built in alarms and optional field installed remote ...

Page 8: ... needs to be changed 10 3 Changing Chart Paper To change the chart paper complete the following steps 1 Locate the pressure sensitive buttons at the front upper left of the recorder panel 2 Press and hold the change chart button for one second The pen will move off the scale 3 Unscrew the center nut remove the old chart paper and install new chart paper Carefully align the day and time with the re...

Page 9: ...Condensers should be cleaned at least every six months In heavy traffic areas condensers load with dirt more quickly Failure to keep the condenser clean can result in equipment warm up or erratic temperatures CAUTION Never clean near condensers with your fingers Some surfaces are sharp Periodically check the condenser to make sure that it is clean In all models the condenser is located in the top ...

Page 10: ...mperature continues to fluctuate call an authorized Revco service representative Unit warms up Door is open Make sure the door is completely closed Door seal Check the door seal following instructions in Section 4 5 on page 3 Warm product recently loaded in unit Allow ample time to recover from loading warm product Power supply Check for proper voltage to the unit If there is no voltage to the uni...

Page 11: ...Can dial up to four telephone numbers to advise of alarm condition across any telephone system which accepts pulse dialing One system can monitor up to four individual cabinets In addition the system can monitor up to three groups of cabinets Contact Revco for detailed specifications Customer installed 6224 Description Catalog No Temperature recorder 6 in circular chart seven day drive free standi...

Page 12: ...months from the date of shipment by Revco If any part is found to contain a manufacturing defect in material or workmanship Revco assumes no responsibility for any labor expenses for service removal or reinstallation required to replace part or for incidental repairs and such costs are the responsibility of the Owner unless a service labor agreement exists between the Owner and his Dealer The warr...

Page 13: ...plate attached to the equipment If available please provide the date purchased the source of purchase Revco or specific agent rep organization and purchase order number If You Need Assistance REVCO SALES DIVISION Phone 828 658 2711 800 252 7100 FAX 828 645 3368 LABORATORY PARTS and SERVICE Phone 800 438 4851 FAX 828 658 2576 TECHNICAL SUPPORT Phone 800 438 4851 275 Aiken Road Asheville NC 28804 U ...

Reviews: