REVO S
2PH from 60A to 210A
User’s manual
25
7.2 HB Alarm contact
The Revo unit with HB option (if available), is supplied with Heater Break alarm contact
normally opened (NO):
• In normal conditions (without alarm) and with auxiliary power supply, the contact to
the terminals has opened (relay coil energized).
• In alarm condition or without auxiliary power supply the contact to the terminals is
closed (relay coil not energized).
If you wish to change the alarm contact open the cover of the Master module (first on
the left with terminal block) and set the jumper as shown in the next page,
don’t set the
other jumpers with factory settings.
Warning:
Before operate, be sure that power and control cables are
isolated from voltage sources.
L1
T1
L2
T2
MASTER
A
B
C
JP1
A
B
C
JP1 A - B =
NC
A
B
C
JP1 B - C =
NO