User’s manual
27
8.1 Input calibration procedure
Warning:
this procedure can be done just by specialized personnel
This procedure is needed only if you change the input type
ON
2sec.
S.C
H.B.
ON
S.C
H.B.
ON
S.C
H.B.
ON
S.C
H.B.
ON
S.C
H.B.
0% Signal
100% Signal
Auxiliary power supply
OFF
Start TUNE
Mantain Key CAL pushed
and give the power supply
Release key
when red and yellow
led are ON
Yellow and Red leds
are flashing
Wait for more than 10 sec.
from start flashing
yellow and red leds
Within 10 sec. from start
flashing yellow and red leds
push again momentary
CAL Key
The leds will
stop flashing
SSR
ANALOG
INPUT TYPE
SSR Input
is tuned
Yellow led only is
flashing, apply
0 input Signal
I.E.: 0V for 0-10V
4mA for 4-20mA
Now press CAL Key again
Red led only is
flashing, apply
10V for 0-10V input
or
20mA for 4-20mA input
Now press CAL Key again
End
TUNE
Analog input
is tuned