REVO S
3PH from 60A to 210A
User’s manual
23
LOAD TYPE
Delta
Open Delta
Star
Star + Neutral
T1
T2
T3
T1
T2
T3
T1
T2
T3
N
T1
L1 L3 L2
T2
T3
5.7 Connection Diagram for 3 phases (control on 3 phases) from 120 to 210A
Caution:
this procedure must be performed only by qualified persons.
Note:
*
1
A suitable device must ensure that the unit can be electrically isolated from the supply (electromagnetic
circuit breaker or by fuse isolator), this allows the qualified people to work in safety.
*
2
Only for the HB option
See par. “Heater break Alarm and SCR short circuit”.
*
3
The heat-sink must be connected to the earth.
*
4
Analog Input Connection
-
The analog input is not isolated from Aux Supply. A series connection between analog inputs of the units
is not possible
-
With AC Aux supply it’s not possible
connect the zero terminal “7 (-)” of Analog Input to the earth.
-
With DC Aux supply it’s not possible
to connect the zero of the power supply (terminal 1 and 2) with the
zero “terminal 7(-)” of analog input
-
Never connect
terminals “1” and “2” to earth
s
24Vac
24Vdc
AUX
1
2
3
- +
- +
- +
- +
+ -
M1
L1
L2
L3
T1
T2
T3
4
CAL Ext. 12-24Vdc
Down
Top
SSR Input Only
SSR Input Only [ SSR
Input [ SSR 0/10Vdc / 4-20mA
CT+HB option
HB Alarm
Relay Out.
Fan Supply
see Order Code
for characteristics
Fan Supply
see Order Code
for characteristics
TO L
O
AD
Analog Input
or SSR Input with HB
SSR Input: 4 ÷ 30Vdc 5mA Max (ON >4Vdc OFF <1Vdc)
Frequency 3Hz Max - On time min. 100 ms