26
REVO S
3PH from 60A to 210A
User’s manual
Input setting
The input type is already configured in line with customer requirements that are defined in the Order Code.
However, if you wish to change the input type (ex. from 0÷10V to 4÷20mA) set the jumpers as below represented
and then do the “Input calibration procedure”. Open the cover of the Master module (first on the left with
terminal block) and set the jumper as shown, don’t set the other jumpers with factory settings not shown.
Important: The analog input isn’t isolated from Aux Supply. The series connection between analog inputs
of the units is not possible. With AC Aux supply it’s not possible connect the zero terminal of Analog Input
to the earth. With DC Aux supply is not possible to connect the zero of the power supply with the zero of
analog input.
Warning:
Before operate, be sure that power and control cables are isolated from voltage
sources.
L1
T1
L2
T2
L3
T3
MASTER
8
There are two type of PCB board, for
SSR Only Version board the other
jumpers are not mounted on PCB.
A
B
C
SSR
JP2
A-B
JP3
B-C
JP6
A-B
JP2 JP3 JP6
JP8 JP7 JP9
A
B
C
JP2 JP3 JP6
SSR only
JP8 Close
JP9 Close
A
B
JP8 JP9
JP2
B-C
JP3
A-B
JP6
B-C
A
B
C
JP2 JP3 JP6
0-10 Vdc
JP2
B-C
JP3
B-C
JP6
B-C
A
B
C
JP2 JP3 JP6
4-20 mA