Mounting 37/76
CytroPac, RE 51055-B/02.2021,
Bosch Rexroth AG
Make sure that in the “Basic" configuration the switch-off signals of oil
temperature, fill level and filter clogging cause the hydraulic power unit to shut
down, e.g. by removing the 24 VDC enable or disconnecting the electrical power
supply.
The CytroPac is equipped with the Rexroth EFC 5610 frequency converter that
can be connected via Mini USB cable to an external PC.
With the help of the software IndraWorks Ds you can access the frequency
converter and make settings. This software can be downloaded on the website of
Bosch Rexroth, see chapter 17.4 ”Accessories“ on page 68.
7.5.1 Pinout of the mating connector to connection 12X1:
Feed-in/voltage supply
▶
Assign the pins of the mating connector (optional accessory item, see chapter
17.4 “Accessories“ on page 68) for the power supply as shown in Fig. 18.
▶
Make sure that the supply connection complies with the below specified
requirements.
Fig. 18: Feed-in/voltage supply
▶
Feed-in/voltage supply including fuse and mains contactor are to be realized by
the customer.
12X1 power plug
(optionally available, see chapter 17.4 “Accessories“ on page
68)
11
2
PE
3
Pin
Function
1
L1
2
L2
3
L3
Fig. 19: Power plug (12X1)
-12X1 L1
L2
L3 PE
Voltage
3P 380 V … 480 VAC (-15 % / +10 %)
Frequency
50/60 Hz
Pin assignment
L1/L2/L3/PE
Rotary field
Rotary field right
Pre-fuse,
customer side
Power 1.5 kW → maximum 10 A
Power 2.2 kW → maximum 16 A
Power 3.0 kW → maximum 20 A
Power 4.0 kW → maximum 20 A