DIAX04 ELS-06VRS
Description of Diagnostic Letters F... and E...
4-29
DOK-DIAX04-ELS-06VRS**-WA01-EN-P
4.2
Error Diagnostic Messages E...
E219 Warning Drive temp. surveillance defective
Temperature monitoring checks to see if the measured drive controller
temperature is within reasonable bounds. If it determines that it is lower
than -10
°
C, then it is assumed the measuring unit is defective. Warning
E219 Warning Drive temp. surveillance defective
will appear for 30
seconds. Afterwards the drive will be brought to a standstill according to
the selected error response and message
F218 Amplifier overtemp.
shutdown
will be generated.
Cause:
Broken cable in the drive controller, or defective sensor.
Remedy:
Exchange or repair the drive controller.
E221 Warning Motor temp. surveillance defective
Temperature monitoring checks to see if the measured motor
temperature is within reasonable bounds. If it determines that it is lower
than -10
°
C, then it is assumed the measuring unit is defective. Warning
E221 Warning Motor temp. surveillance defective
will appear for 30
seconds. Afterwards the drive controller will be brought to a standstill
according to the selected error response and message
F221 Error Motor
temp. surveillance defective
will be generated.
Cause:
1.
Motor temperature sensor not connected.
2.
Broken cable.
3.
Defective sensor.
4.
Broken cable in drive controller.
Remedy:
For 1.
Connect the sensor to the drive controller and to the motor
(see project planning specifications for the motor).
For 2.
Exchange the wiring between the drive controller and the motor.
For 3.
Exchange the motor. Use second sensor in the motor if available.
For 4.
Exchange the drive controller.
See also the functional description: "Temperature monitoring".
E225 Motor overload
The maximum possible motor current is reduced in order to protect the
motor from being destroyed.
If a current flows in the that is greater than 2.2 times the motor current at
standstill S-0-0111, the maximum possible motor current
(S-0-0109,
Motor peak current)
is reduced. With 4-fold motor current at standstill,
the reduction starts after 400 ms. With 5-fold current it starts earlier, and
with 3-fold current later. The
E225 Motor overload
warning is issued
when the motor peak current is reduced by the limitation.
The reduction also has an effect on the
P-0-4046,
Active permanent
current
.
Summary of Contents for DIAX04
Page 4: ...About this Documentation DIAX04 ELS 06VRS DOK DIAX04 ELS 06VRS WA01 EN P Notes...
Page 14: ...1 4 Diagnostic Message Descriptions DIAX04 ELS 06VRS DOK DIAX04 ELS 06VRS WA01 EN P Notes...
Page 106: ...6 2 Index DIAX04 ELS 06VRS DOK DIAX04 ELS 06VRS WA01 EN P W Warning symbols 3 1...
Page 113: ......
Page 114: ...Printed in Germany 2 9 1 6 2 8...