Easy Start Guide
Page 10
This guide has been produced by The Inverter Drive Supermarket Ltd.
All content, including but not limited to graphics, text and procedures copyright
The Inverter
Drive Supermarket and must not be reproduced or altered without prior written permission.
©
Bosch Rexroth EFC 5610 Series Inverter
10. How to connect and configure a Run Forward or
Run Reverse switch
Parameter
Description
How to set
b0.00
Access to additional parameters
Default is 0 for Basic Parameters. Set to
to enable Advanced Parameters.
2
E0.01
First run command source
When set to 1, the FWD lamp will go out.
Default is 0 for keypad. Set to
for terminal control on the Inverter.
1
E1.00
X1 input
Default is
for Forward Run; default is required for this example.
35
E1.01
X2 input
Default is
for Reverse Run; default is required for this example.
36
E1.15
2-wire / 3-wire control mode
Default is
for 2-wire forward / stop, reverse / stop; default is required for this example.
0
10.1 Relevant parameters for remote Run/Stop
If this is unsuitable for the application, a remote
switch can be used instead.
The parameters described in Section 5 enable
Run/Stop operation via the red and green
buttons on the Inverter.
This section explains how to enable 2-wire
control with Run Forward / Stop / Run Reverse
commands via a single selector switch.
Note that once this procedure is complete, the
Run/Stop buttons on the Inverter can no longer
be used.
10.2 Connecting the Switch
A wiring diagram is shown in the illustration
opposite. The SC and COM terminals must be
linked.
A suitable 3 position NO (Normally Open)
switch should be installed between terminals
24V, X1 and X2. The centre position should
remain open circuit.
When run forward is selected (24V to X1) the
motor will accelerate from 0 to the currently-
selected speed set point. Run and Fwd lamps
will illuminate. When run reverse is selected
(24V to X2) the behavior is the same but the
motor will run in reverse and the Rev lamp will
illuminate instead of Fwd.
When stop is selected (open circuit) the motor
will decelerate to zero and the Run and Fwd
lamps will go out. The display will revert to the
current setpoint.
2
1
F
R
3
Switch, 3 Position
Normally Open
“Run Forward / Stop / Run Reverse”
EFC 5610
I/O Terminal
Blocks
X2
X1
24V
1
3
2
SC
COM
Link cable