Easy Start Guide

14. STO (Safe Torque Off) Connections

Page 14

This guide has been produced by The Inverter Drive Supermarket Ltd.
All content, including but not limited to graphics, text and procedures copyright

The Inverter

Drive Supermarket and must not be reproduced or altered without prior written permission.

©

Bosch Rexroth EFC 5610 Series Inverter

Safe Torque Off (STO) is an optional safety feature
included with some EFC5610 Inverters. If present,
the Inverter will include a yellow STO connector. No
parameter changes are required to enable this
feature.

STO provides a facility to disable the output of the
Inverter so that the motor it is controlling cannot be
operated ie. that no torque can be applied.
However, it does not provide any form of braking so
will not prevent the load from rotating the motor.

This section is an overview only.
You must also refer to the manual
provided by the manufacturer for
full details of STO functionality.

The STO function is only effective when wired to
suitable safety devices that detect an 'unsafe'
situation. A safety assessment of the machinery
is required by suitably qualified personnel to
identify what should be considered ‘unsafe’ and
what safety devices are appropriate for the
application.

It is not recommend to stop a motor using the
Inverter STO function. The motor should be
stopped before STO is activated or an

error

message will be displayed.

Sto-r

STO does not isolate the electrical supply.
Therefore, the Inverter must be isolated from the
supply before any maintenance is carried out.

There are 12 terminals on the STO plug which
are bridged for easy connection. Therefore,
either the top 6 or bottom 6 can be used.

The Inverter is supplied with links configured
so that the Inverter can be used with STO
disabled. The illustration on the right shows
this arrangement. The links simply connect
STO channels 1 and 2 to 24V and common.

When the Inverter is powered up, 24V must be
present on both STO channels or an
alarm will be displayed and the motor will not
operate.

Sto-A

If 24V is lost on one channel an

error

message will be displayed.

Sto-E

When enabled, the STO channels are
connected to the external safety devices. The
manufacturer recommends that a suitable
external 24V power supply is used instead of
the +24V and COM terminals on the Inverter.

14.2 STO Enabled

If STO is to be used, remove all links.

14.1 STO Links (STO disabled, as supplied)

+24V

STO2+

STO1+

COM

STO1-

STO2-

+

STO1 (external channel 1)

STO2 (external channel 2)

+

-

-

This display will flash StO-A and the motor will not

start if 24V is not present on both STO channels

STO Disabled

STO Enabled

Summary of Contents for EFC 5610 Series

Page 1: ...ermarket customers It should not be used as a replacement for the manual issued by the manufacturer Issue 1 20180705 This product is not a safety device All safety considerations including but not lim...

Page 2: ...tions Star and Delta How to enable Sensorless Vector control Parameters Overview How to set a Parameter value Power and Motor Connections Three Phase How to Operate the Inverter from the keypad STO Sa...

Page 3: ...y isolated from the power supply have been isolated for at least 5 minutes and that the motor is not turning Bosch Rexroth EFC 5610 Series Inverter Motor Power Earth Phase W Phase V Phase U Live L1 Ne...

Page 4: ...e screened or armoured cable between the I n v e r t e r a n d M o t o r To m i n i m i s e electromagnetic interference ensure the cable screen is grounded as shown The order of the three motor phase...

Page 5: ...o at one side Only two links are required for Star Double up the links if changing from Delta to allow the motor to be changed back in future The order of the three phases determines the direction the...

Page 6: ...eg 230 C1 07 Rated motor current A Set to match motor nameplate eg 3 34 C1 08 Rated motor frequency Hz Default is 50 00 Change to 60 00 for 60Hz motor only otherwise set at 50 00 C1 09 Rated motor spe...

Page 7: ...eg E0 Some parameter groups may be hidden when Advanced Parameters are not enabled Press Set to select E0 There are a total of 17 parameter groups when Advanced Parameters are enabled 6 3 Find a Para...

Page 8: ...ed by parameter E0 10 and the maximum reference by E0 09 7 2 Press the green Run button to start the motor Press the green button firmly to start the motor The motor will accelerate to the speed set i...

Page 9: ...that cannot be decoupled from the motor a stationary Autotune set C1 01 to 1 instead of 2 is possible but is not as accurate A rotating Autotune is therefore the preferred option Parameter Descriptio...

Page 10: ...nvenient location such as a cabinet door if the EFC 5610 is cabinet mounted or on the machine itself A Potentiometer of rating should be used 10kOhm The number of turns depends on the application but...

Page 11: ...ication a remote switch can be used instead The parameters described in Section 5 enable Run Stop operation via the red and green buttons on the Inverter This section explains how to enable 2 wire con...

Page 12: ...he Forward Reverse switch can be omitted A wiring diagram is shown in the illustration opposite The SC and COM terminals must be linked 11 2 Connecting the Switches When run is selected 24V to X1 and...

Page 13: ...is required for this example 35 E1 01 X2 input Default is for Reverse Run default is required for this example 36 E1 02 X3 input Default is 0 set to to select 3 wire control with reverse select 25 E1...

Page 14: ...ng diagram is shown in the illustration opposite Connect the brake resistor to the B and Terminals on the Inverter The order of the connections is unimportant The braking resistor may get hot during o...

Page 15: ...re appropriate for the application It is not recommend to stop a motor using the Inverter STO function The motor should be stopped before STO is activated or an error message will be displayed Sto r S...

Page 16: ...ows b0 do not press and hold the Func button 15 2 Select Parameter b0 10 Press the Set button to select the b0 Parameter group then use the up button to locate parameter b0 10 15 3 Change value of b0...

Reviews: