3.20 Remarks of the above Tables
1) 2) 3)
: See
chapter 3.21 "Distances" on page 33
4)
: DC bus L+, L-; mains input L1, L2, (L3)
5)
: Depending on switching frequency
6) 7) 8)
: Housing dimension; see also related dimensional drawing
9)
: Use listed AC input line fuses (class J; 600 VAC) at the mains supply
10)
: Copper wire; XLPE or EPR-insulation (conductor temperature 90 °C)
installation mode B1 (EFC 3600: B1, B2, E)
11)
: Copper wire; PVC-insulation (conductor temperature 75 °C)
Ta ≤ 40 °C (EFC 3600: Ta ≤ 50 °C; EFC x610: Ta ≤ 45 °C)
12)13)14)
: Cable installation modes B1, B2, E, see
chapter 3.22 "Cable Installation
Modes" on page 34
15)
:
●
ND: Normal Duty, ONLY available with EFC 3610
●
HD: Heavy Duty, available with both EFC 3610 and EFC 5610
3.21 Distances
A
Air intake
B
Air outlet
C
Mounting surface in control cabinet
d
top
Distance top
d
bot
Distance bottom
d
hor
Distance horizontal
Fig. 3-1: Air intake and air outlet at device
Bosch Rexroth AG
Ratings and Dimensions
DOK-RCON01-REX*F*UL***-IN10-EN-P
33/69