EFC x610 main circuit terminals description
Terminal
Description
1P 200 VAC
L1, L2
Mains power supply inputs
U, V, W
Frequency converter outputs (to be connected to the motor)
B
Reserved terminal for external brake resistor
(+)
DC positive bus output
3P 200 / 400 VAC
L1, L2, L3
Mains power supply inputs
U, V, W
Frequency converter outputs (to be connected to the motor)
B
Reserved terminal for external brake resistor
(+)
DC positive bus output
(-)
DC negative bus terminal (only available with models of 5K50 and above)
Tab. 5-5: EFC x610 Main circuit terminals description
Fig. 5-22: Grounding and PE terminals
1: Grounding terminal for mains cables
2: Reserved for PE / shielding adapter (Order additionally)
3: Reserved for PE / shielding adapter (Order additionally)
4: Grounding terminal for motor cables
Fig. 5-23: Connection screw for internal EMC filter
Internal EMC filter must be disconnected in isolated neutral power system (e.g.,
IT-Net). Otherwise, the system will be grounded via the capacitor of the EMC fil-
ter, which may lead to danger or damage to the frequency converter. The con-
nection screw for the internal EMC filter as shown in the figure above is located
at the side of the frequency converter.
With the internal EMC filter disconnected, the specified EMC per-
formance of the frequency converter cannot be reached.
Bosch Rexroth AG
Instructions for Use
54/69
DOK-RCON01-REX*F*UL***-IN10-EN-P
Summary of Contents for EFC3600 Series
Page 17: ...Rexroth 60 15 Bosch Rexroth AG DOK RCON01 REX F UL IN10 EN P XV...
Page 18: ...Bosch Rexroth AG XVI DOK RCON01 REX F UL IN10 EN P...
Page 31: ...Fig 2 2 Type code Fv Bosch Rexroth AG Identification DOK RCON01 REX F UL IN10 EN P 11 69...
Page 32: ...Fig 2 3 Type code EFC 3600 Bosch Rexroth AG Identification 12 69 DOK RCON01 REX F UL IN10 EN P...
Page 33: ...Fig 2 4 Type code EFC x610 Bosch Rexroth AG Identification DOK RCON01 REX F UL IN10 EN P 13 69...
Page 89: ...Notes Bosch Rexroth AG...