●
B1 in accordance with IEC 60364-5-52, e.g. stranded wires routed
in cable duct
●
B2 in accordance with IEC 60364-5-52, e.g. multi-core line routed
in cable duct
●
E in accordance with EN 60204-1, e.g. multi-core line routed on
open cable tray
●
In accordance with NFPA 79 (external wiring), UL508A (internal
wiring), NEC, NFPA 70:
–
1 cable with 3 conductors, 1 neutral conductor and 1 equip‐
ment grounding conductor
–
Routed in pipe on the wall
Internal wiring: Routing inside of control cabinet or inside of devi‐
ces
External wiring: Routing outside of control cabinet
Field wiring: Data of cross sections of terminal connectors wired by
the user (in the field)
5. Recommendation for design of the fuses:
●
International except for USA/Canada:
–
Fuse-link in accordance with IEC 60269-1, characteristic gG
(fuses)
–
Circuit breakers in accordance with IEC 60898-1/2, type B or
C
–
Circuit breakers in accordance with IEC 60947-2/6-2
●
USA / Canada:
–
Class J; 600 V
Correction factors
For deviating dimensioning variables, the corresponding stand‐
ards specify correction factors.
Below you can find the correction factors for ambient temperature
and numbers of routed lines and circuits. If necessary, multiply
the determined current in the supply feeder with these factors.
Correction Factor Ambient Temperature
Ambient temperature T
A
/ °C
30
35
40
45
50
55
60
Correction factor according to
EN 60204‑1:2006, table D.1
0,87 0,93 1,00
1,1
1,22 1,41 1,73
Correction factor according to
NFPA 79:2007, table 12.5.5(a)
0,88 0,94 1,00
1,1
1.18 1.32 1,52
Tab.15-6:
Correction Factor Ambient Temperature in Accordance with EN
60204-1:2006 and NFPA 79:2007
DOK-INDRV*-SYSTEM*****-PR06-EN-P
Rexroth IndraDrive Drive Systems with HMV01/02 HMS01/02, HMD01, HCS02/03
Bosch Rexroth AG
271/309
Calculations