11/25
Figure 4
Figure 5
4.4 Gas connection
Connection to a gas network may only be carried out
by appropriately qualified persons. The gas
installation must comply with the rules in force using
materials appropriate for gas installation.
To facilitate servicing, the air heater must be fitted
with an approved gas service tap and union fitting or
union tap adjacent to the appliance.
The inlet gas supply line must be installed so as to
permit the access door to be opened and to allow
removal of the slide out burner assembly.
Air heaters suspended by flexible suspension
materials or drop rods must be connected to the gas
supply using an approved flexible connector.
Sufficient slack must be provided in the connection
to allow for movement of the appliance. Use a
flexible connector of suitable size to reduce the
pressure drop and the possibility of gas flow noise.
Do not use the appliance gas supply to
balance or support any part of the
appliance
.
Figure 6
Legend :
1 Gas tube inlet sealing ring
2 Inlet gas pipe
3 Union fitting
4 Gas service tap
5 Gas pipe
4.5 Electrical connections
The electrical installation may only be carried out by
appropriately qualified persons observing the rules
in force.
All electrical connections should be made in the
heater control compartment (refer to figure 9).
Screw type terminals are provided. Connections
should be in accordance with the terminal markings
and the wiring diagram affixed to the air heater or
included with this document.
THIS APPLIANCE MUST BE EARTHED!
ATTENTION : Failure in electrical wiring can
bring real damage to components of this
appliance. Please follow very carefully the
wiring diagram supplied with this air heater.
The minimum external controls required for the air
heater are a room thermostat.
It is essential the
main input line and neutral to terminals L and N
remains live at all times even when the appliance
is switched off this is to ensure correct
operation of the unit.
An indicator light and burner reset button are fitted
inside the appliance. To add a remote reset button,
make connections to the terminals in the electric
box as indicated on the wiring diagram.
IMPORTANT:
If the reset button requires activating for any reason the
cause should be identified before resetting. After
resetting stay with the appliance for long enough to
ensure that lock-out does not reoccur (suggest 5
minutes).
Fix all electric cables and installer’s wiring to the control
panel and ensure they do not touch the combustion
collector box.
danger