background image

8/25 

 

3.3.1 Flues for power vented installations 
(Type B appliances) 

 

If the air heater is to be installed as a type B 
appliance, air for combustion will be taken from 
within the space where the heater is installed. 
Ensure that an adequate air supply for combustion 
and ventilation is provided within the building in 
accordance with the regulations & rules in force. 
 
Table 5 shows flue pipe sizes and maximum pipe 
lengths. The minimum flue length is 0.5 metres. 

 

Table 5 Flue pipe diameters & maximum lengths 

12

35->145

Heater socket & 
pipe dia

Equivalent length 

m

of 45° elbow

1.5

80

9

20, 30

100

130

LCSA-4

mm

m

Equivalent length
of 90° elbow 

Maximum straight 
length

m

0.75

 

 
Single wall flue pipes are required. All joints must 
be sealed to prevent products of combustion from 
leaking into the building. An approved flue terminal 
is required. 
 
If the flue passes through a combustible element of 
the building it must be enclosed by a sleeve of non-
combustible material and separated from the sleeve 
by at least a 25 mm air break. The temperature of 
any combustible material near to the flue must not 
exceed 65°C when the heater is in operation. The 
flue must be at least 50 mm away from any 
combustible material. 
 
Single wall flue pipe exposed to cold air or run 
through unheated areas must be insulated. Where 
condensation is unavoidable, provision must be 
made for the condensation to flow freely to a point 
to which it can be released, i.e. a drain or gully. The 
condensation drain from the flue must be 
constructed from non-corrodible material not less 
than 20 mm diameter. Copper or copper based 
alloys must not be used for condensation drains. 

 
 

3.3.2 Combustion air inlet pipe & flue pipe for 
balanced flue installation (Type C appliances) 

 

Balanced flue air heaters are designed to be fitted 
with a combustion air inlet pipe that obtains outdoor 
air and a flue pipe that exhausts flue products to 
outdoors. 
 
Air heaters if fitted with a power venter permitting 
either a vertical or horizontal combustion air 
inlet/flue pipe system. 

The heaters must be 

installed with a concentric vertical or horizontal 
flue/combustion air inlet. The heaters are only 
approved for use when installed with the 
appropriate approved concentric vent terminal. 

See table 6. 

Both the flue and combustion air pipes must be sealed. 
Use gasket sealed seamless aluminium pipe or 
equivalent. 
 
The flue pipe must include a re-sealable test port to 
allow good average sampling of the flue gas mixture 
for testing, the port must be at least 450 mm away 
from the air heater flue connection socket. 
 
Follow any flue pipe manufacturers’ installation 
instructions for making joints, including connections to 
the air heater, for passing through a building element 
and for support requirements. If more than one air 
heater is being installed in the same place each heater 
must have a separate flue system. 
Where condensation is unavoidable, provision must 
be made for the condensation to flow freely to a 
point to which it can be released, i.e. a drain or 
gully. The condensation drain from the flue must be 
constructed from non-corrodible material not less 
than 20 mm diameter. Copper or copper based 
alloys must not be used for condensation drains. 

 

Figure 2b :  
Combustion air and flue pipe sockets, 

Type C 

Legend : 

1  Flue products flue outlet socket for flue pipe 
2  Combustion air inlet opening  

 

 

 

Table 6  
Combustion air inlet & flue pipe requirements  

LCSA-4

12

35 -> 145

Flue pipe

80

130

Inlet pipe

80

130

Flue pipe

Inlet pipe

Flue pipe

Inlet pipe

Flue pipe

Inlet pipe

Max. straight
length

m

20, 30

100
100

9

9

Heater socket
& pipe dia

mm

Concentric vertical vent or wall terminal : Mugro/Burfix dia 130
Concentric horizontal vent or roof terminal : Mugro/Burfix dia 130

Equivalent length
of 45° elbow

Equivalent length
of 90° elbow

m

m

1,5

1,5

0,75

0,75

Summary of Contents for 100

Page 1: ...ca Spain Sweden Turkey Ukraine WARNING Improper installation adjustment alteration service or maintenance can cause property damage injury or death All work must be carried out by appropriately qualified persons The manufacturer does not take any responsibility in the event of non observance of the regulations concerning the connection of the apparatus causing a dangerous operation of the apparatu...

Page 2: ...tallation 4 4 Gas Connection 4 5 Electrical Connections 4 6 Room Thermostat Siting 5 0 AIR DISTRIBUTION 6 0 COMMISSIONING AND TESTING 6 1 Electrical Check 6 2 Gas Connection 6 3 Suspension and Support 6 4 Lighting the Heater 6 4 1 To Turn the Heater ON 6 4 2 To Turn the Heater OFF for Short Periods 6 4 3 To Turn the Heater OFF for Long Periods 6 5 Heater pipe work 6 6 Adjustments 6 7 Air Distribut...

Page 3: ...ter than 1 8 meters measured to the underside of the appliance they may be used as a garage air heater This appliance must be installed in accordance with the rules in force Before installation check that the local distribution conditions nature of gas and pressure and adjustment of the appliance are compatible A permanent electricity supply of 230 volts 50 Hz single phase is required Heaters are ...

Page 4: ...on I2H or I3P Denmark II2H3 B P Serbia II2H3 England II2H3 Slovakia II2H3 Estonia II2H3 Slovenia II2H3 Finland II2H3 B P South Africa II2H3 Germany I2ELL Spain II2H3 Greece II2H3 Sweden II2H3 B P Hungary II2HS3P Turkey II2H3 Iceland II2H3 Ukraine I2H or I3P Latvia II2H3 Lithuania II2H3 2 LCSA 4 12 20 30 35 45 50 60 75 100 120 145 Gas category Comb Air Flue type B 1 Comb Air Flue type C 1 Connectio...

Page 5: ...bar no nat gas for Germany Model 12 20 30 35 45 50 60 75 100 120 145 Injector quantity 5 5 6 8 10 8 8 10 12 10 12 mm 1 50 2 10 2 10 2 20 2 20 2 40 2 70 2 70 2 90 3 40 3 40 marking 150 210 210 220 220 240 270 270 290 340 340 Burner pressure 1 mbar 8 10 8 00 7 25 7 10 6 90 9 20 8 50 8 30 7 50 9 20 9 00 Inlet pressure mbar Injector quantity 5 6 8 10 8 8 10 12 10 12 mm 1 15 1 15 1 15 1 15 1 40 1 45 1 ...

Page 6: ...123 611 406 3 4 G 45 965 845 652 130 74 531 117 605 138 824 331 420 82 175 508 720 134 211 123 611 406 3 4 G 50 1298 845 652 130 151 759 154 517 156 838 409 425 82 175 508 720 135 212 123 942 406 3 4 G 60 1298 845 652 130 151 759 154 517 139 824 409 425 82 175 508 720 135 212 123 942 406 3 4 G 75 1298 845 652 130 151 759 117 605 139 824 409 425 82 175 508 720 135 212 123 942 406 3 4 G 100 1298 954...

Page 7: ...ld be discharged toward outside walls In large areas they should be located to discharge air along outside walls with additional heaters provided to blow air into the centre of the area In places where infiltration of cold is excessive such as entrance doors it is desirable to locate a heater so that warm air is discharged directly toward the source of cold air from a distance of 4 5 6 0m Air heat...

Page 8: ...ustion air inlet pipe that obtains outdoor air and a flue pipe that exhausts flue products to outdoors Air heaters if fitted with a power venter permitting either a vertical or horizontal combustion air inlet flue pipe system The heaters must be installed with a concentric vertical or horizontal flue combustion air inlet The heaters are only approved for use when installed with the appropriate app...

Page 9: ... air throw pattern achieved In building having low heat loss where single heaters are required to cover a large floor area and in buildings with high ceiling heights air re circulation fans e g Maximizors may be fitted to ensure even heat distribution and minimize stratification Care should be taken to avoid impeding air flow with storage racking partitions etc 3 6 Electrical supply Wiring externa...

Page 10: ...o not place or add additional weight to the suspended air heater See hazard levels page 2 The heater must be installed in a level plane to ensure proper operation 4 3 Fitting the Combustion air inlet Flue system Flue pipe runs may be horizontal or vertical and terminate either through the wall or roof See table 5 for maximum pipe length for an appliance installed as type B or table 6 for maximum l...

Page 11: ...riately qualified persons observing the rules in force All electrical connections should be made in the heater control compartment refer to figure 9 Screw type terminals are provided Connections should be in accordance with the terminal markings and the wiring diagram affixed to the air heater or included with this document THIS APPLIANCE MUST BE EARTHED ATTENTION Failure in electrical wiring can ...

Page 12: ...with the appliance circuit diagram Ascertain that the correct fuse value and cable size has been provided Check to ensure that the appliance is earthed by conducting an earth continuity test Connect a test meter one lead to the appliance earth terminal and the other to the mains incoming earth point at the electrical isolator A resistance reading of 1 0 ohm or less must be indicated If a higher re...

Page 13: ...mostat to its lowest setting or OFF The fan will continue to run to cool the heater and then switch OFF automatically 6 4 3 To turn the air heater OFF for long periods Adjust the room thermostat to OFF or its lowest setting When the fan has stopped turn OFF the gas supply and then switch OFF the electricity supply to the air heater 6 5 Air heater gas pipe work The soundness of the air heater pipe ...

Page 14: ...ime delay relay will activate the thermal fan control which will energize the fan motor Continue to operate the air heater for several minutes to ensure correct operation Turn room thermostat to its lowest setting The main burners should extinguish while the fan continues to run to cool the air heater The fan delay relay will normally be de energized and stop the fan motor in approximately 45 seco...

Page 15: ...s from the burner with a wire brush Clean the ports with a degreaser or acetone A vacuum cleaner or compressed air may assist in this cleaning operation Wipe the inside of the burner tube clean cleaning thoroughly with a degreaser as recommended will retard future build up of dirt Inspect the burner for any damage or deterioration If the burner is damaged or corroded replace it 2 The heat exchange...

Page 16: ...ck manifold assembly upward and pull the assembly out of the air heater Instructions for re assembly 1 Reverse the procedure for removal making sure that all parts are installed correctly Check that all components are secure 2 When lighting always follow the lighting instructions on the air heater Remember After any service work has been carried out the air heater must be fully commissioned See se...

Page 17: ...ce back into service as outlined in section 6 0 The gas control operating valve is the prime safety shut off All gas supply lines must be free of dirt scale etc before connecting to the air heater thus ensuring positive closure of the control valve 8 5 Thermal overheat limit controls If it is determined that the thermal overheat control needs replacing use only authorized replacements that are des...

Page 18: ...ty Determinewhat causedthe limit totrip Placeintonormal operation Checkthemains Checkthetime tempeature control Is therecontinuitybetween 9 10 Isthere230Vbetween 11 12 Ispower ventingoperating Reset limit control Checkventer motor Replacepressureswitch Isthethermostat above roomtemperatureandif usedisthetime clock ON Set thermostat aboveroom temperature if usedmake certainthetimeclockisON Doesthep...

Page 19: ...e During 5 trial for ignition is a spark visible Check electronic ignition control Check spark gap and ceramic check spark wire connector Is a spark visible Check flame signal Is it greater than 1 0 micro Amps Check flame signal using micro amp meter Is signal greater than 1 0 micro Amps During 5 trial for ignition is a flame visible in ths view port Correct polarity Does the inlet gas pressure ag...

Page 20: ...bution device been placed on the heater Is there excessive static pressure in the ductwork Did the motor overload trip Does the fan control energize the fan motor in less than 75 Adjust thermostat temp setting above ambient to energize fan gas solenoid valve Replace the motor Consult fan fault finding Does the limit trip before the fan is energized Place system in normal operation Consult fan faul...

Page 21: ...1 Gas valve one stage 120 145 03 25144 Burner relay E 03 25324 Ignition electrode ER 03 400US 42 Ignition electrode ER 120 145 05 25186 Flame sensor electrode IS 03 401US 195292 ERP fan 12 01 27003 ERP fan 20 01 27006 ERP fan 30 01 27021 ERP fan 35 45 01 27010 01 ERP fan 50 01 27011 01 ERP fan 60 75 01 26063 ERP fan 100 01 27014 02 ERP fan 120 145 2x 01 26063 Settings GAS CONVERSION 11 1 LCSA 4 ai...

Page 22: ...stat calls for heat after about 30 sec 6 If the appliance does not light a check that the burner control does not require resetting An indicator light glows at the inside panel of the appliance and on a remote control if fitted Reset by pushing reset button inside the appliance or the remote control b check if thermal overheat control requires resetting 7 If the thermal overheat control requires r...

Page 23: ...fer reddening and itching of the skin Fiber entry into the eyes will cause foreign body irritation Inhalation will cause irritation to the respiratory tract Precautions Wear protective gloves when handling People with a history of skin complaints may be susceptible to irritation Dust levels are only likely when the material is abraded In general normal handling and use for this purpose will not pr...

Page 24: ...lies with the requirements of further directives namely GAD 2009 142 EC EMC 2004 108 EC LVD 2006 95 EC the following harmonized standards have been applied EN 1020 Non domestic gas fired forced convection air heaters for space heating not exceeding a net heat input of 300 kW incorporating a fan to assist transportation of combustion air and or combustion products The following notified body Techni...

Page 25: ...reznor eu Registered in England N 1390934 Registered office 10 Norwich Street London EC4A 18D Nortek Global HVAC is a registered trademark of the Nortek Global HVAC Limited Because of continuous product innovation Nortek Global HVAC reserves the right to change product specification without due notice ...

Reviews: