CONTROLS—CONTINUED
Optional Two-Stage Control (Makeup Air Application)—Continued
• Option AG3 or AG15:
Comparable to the two-stage heating units . Instead of control from a two-stage room
thermostat, the discharge air temperature is monitored and the two-stage gas valve is controlled by a two-stage
ductstat . When the discharge air temperature drops to the setpoint, low fire is energized . If low fire cannot satisfy the
ductstat setting, high fire is energized . Model HRPD includes two furnace sections, and each section is equipped
with a two-stage gas valve . Set the ductstat as indicated in
.
• Option AG4 or AG17 (model HRPD only):
Each furnace in the package is equipped with a single-stage gas
valve . The single-stage gas valves are staged by a two-stage ductstat . The furnaces are staged in sequence . This
concept will achieve two-stage control . Set the ductstat as indicated in
.
Table 17. Recommended Settings for Two-Stage Makeup Air Control
Option
Model
No. of
Furnaces
Ductstat Setting
Temperature Selector Setting
First
Second
Staging Sequence
Setpoint
Differential
Stage Adder
Offset
AG3
RP
1
70°F
—
66°F high stage
→
70°F low stage
→
74°F shutdown
—
—
—
HRPD
2
70°F
64°F
60°F high stage (both furnaces)
→
64°F low stage (furnace 2)
→
68°F shutdown (furnace 2)
→
70°F low stage (furnace 1)
→
74°F shutdown (furnace 1)
AG4
HRPD
2
70°F
—
66°F full rate (both furnaces)
→
70°F shutdown (furnace 1)
→
74°F shutdown (furnace 2)
AG15
*
RP
1
—
74°F
8°F
4°F
HRPD
**
2
—
74°F
14°F
10°F, 6°F, 4°F
AG17
*
HRPD
2
—
74°F
8°F
4°F
*
Adjust the setpoint and the differential of the temperature selector (Johnson #A350) . Adjust the offset potentiometer on each of the stage
adder modules (Johnson #S350) . The settings listed provide the same sequence of staging as shown for option AG3 (for option AG15) or
AG4 (for option AG17) . Follow the manufacturer’s instructions provided .
IMPORTANT:
Set the temperature selector and each stage adder
module to HEAT . Follow the wiring diagram to obtain proper sequencing .
Operation:
The differential setting and offset degrees allow the
controls to adapt to any adjustment in temperature selection (50–130°F) .
**
Model HRPD with option AG15 uses three stage adder modules .
Figure 14. Ductstat Options
•
Depending on the option selection, the factory-installed sensor is either field-connected by capillary tubing to the
, DETAIL A), which is factory-set at 70°F, or electrically-connected to a remote
field-installed electronic temperature selector (see
, DETAIL B) .
Ductstat Bulb
Typical Duct Furnace
Front (Discharge) View
DETAIL A: OPTIONS AG3 AND AG4
(A) Remote
Temperature Selector
(B) Stage-Adder
Module
(A)
(B)
DETAIL B: OPTIONS AG15 AND AG17