RGM 465, Mfg No. 175758, Page 15
Draft
Regulator
Draft Inducer
and Draft
Proving
Switch
• Support:
The vent system must be adequately supported using non-
combustible strapping or supports to carry the weight of the vent and
wind load. Do not use the boiler to provide support for the vent system.
• Barometric Draft Regulator (see below):
A barometric draft regula-
tor which is the same diameter as the vent pipe
must
be used, and it
should be located close to the heater.
Do not
install a manual damper
or any other device that will obstruct the free flow of the flue gases.
• Draft Inducer (see below):
A draft inducer is required; follow the
manufacturer’s instructions and wire according to the wiring diagram.
• Draft Proving Switch:
Mount the switch on any vertical surface
within 5 feet (1.5M) of the draft inducer. Do not mount it on the
inducer or on any other surface with a temperature in excess of 160
o
F.
Wire according to the wiring diagram.
• Terminal End:
The vent must terminate at least 3 feet (914mm) above
the highest point of exit and at least 2 feet (610mm) higher than any
portion of a building or obstruction within 10 feet (3M) of the chimney.
Install a vent cap on the terminal end of the vent. A Reznor (Option
CC1) or Type L Breidert Air-x-hauster
®
vent cap is recommended. A
different style of vent cap could cause nuisance problems. (Type L Air
X-hauster
®
is a trademark of the G. C. Breidert Company.)
A barometric draft regulator is shipped
with this boiler and MUST be installed
in the flue near the boiler flue connec-
tion.
Refer to the illustrations on pages 13
and 14 for recommended locations. To
install, follow the manufacturer’s
instructions packaged with the draft
regulator.
A draft inducer and a draft proving switch are shipped with this boiler and
MUST
be installed
. Refer to the illustrations on pages 13 and 14 for the
recommended location for the draft inducer. Follow the manufacturer’s in-
structions packaged with the draft inducer. Mount the switch vertically within
five feet (1.5M) of the draft inducer; do not mount on the draft inducer. To
connect the switch and wiring, refer to the wiring diagram on the boiler or
on pages 44-45 of this booklet.
Vent System
Requirements
(cont’d)