Form 465, Page 16
Pump Power
Installation
Connect Power to Remote Oil Pump
To connect the electrical power from the burner to the oil pump,
•
Use a 3 conductor, 14 gauge wire system - two 115 volt conductors
and a ground. Use BX if permitted, but make certain to follow local
codes for running conduit.
•
Refer to the wiring diagram for connecting terminals.
Electrical Supply Connections
DANGER: Make sure that the main circuit is OFF before making any wiring
connections. All wiring must be done in accordance with appropriate Codes!
Main Power
To install main power to the system (check the table
below and the rating plate on the boiler for current
requirements),
•
Sizes 140, 235 and 350
- Use #10 gauge
stranded copper wire to run a dedicated 115
volt, single phase, line from the power source
to a junction box mounted on the wall behind
the boiler or as required by appropriate codes.
Size 500
- Use #10 gauge stranded copper
wire to run a dedicated 230 volt, three
phase, line from the power source to a
junction box mounted on the wall behind
the boiler or as required by appropriate
codes.
•
Run the length of appropriate conduit from the
boiler to the junction box.
•
Connect the black wire to the hot lead.
•
Connect the white wire to the neutral lead.
•
Connect the green wire to the ground lead.
•
Install a fused manual reset, line voltage
switch (field supplied) in this main line
•
Electrical Ratings
Total
Minimum
Maximum
Current
Circuit
Fuse Size
Model
Amperes
Ampacity
(Supply)
RAB140
10
13
20
RAB235
11
14
20
RAB350
17
22
30
RAB500
8
11
20
NOTE:
Total amperes does not include water circu-
lation or other field-installed controls.
Heating Thermostat
A 24-volt thermostat is furnished as standard
equipment.
DO NOT
attempt to wire relays or other acces-
sories to the thermostat connections as these are
not load terminals.
DO NOT
install on or suspend the thermostat
from the heater
DO NOT
install thermostat on a cold outside
wall
To install the thermostat,
•
Locate the thermostat five feet above the
floor on an inside wall, not in the path of
warm or cold air currents nor in corners
where air may be pocketed
•
Remove the thermostat cover
•
Make sure the heat anticipator dial is set
at 0.2 amps
•
Connect the wires through the back of the
thermostat to the R & W terminals
•
Set the ON/OFF switch on the heater
electrical box to the “OFF” position and
connect the thermostat wires to the two
“T” terminals on the ignition controller.