RGM 465, Mfg No. 175758, Page 29
Removing Fuel Line Assembly to Service Controls and
Spark Electrodes (Alternate method for servicing nozzle)
WARNING: Turn off the electric power before removing the fuel line assembly.
Escutcheon Plate
NOTE: In order to service the fuel line assembly controls and spark elec-
trodes, it is necessary to remove the fuel line assembly.
Removing the Fuel Line Assembly
1. Loosen the connection nut one or two turns.
2. Disconnect the fuel connection assembly by loosening the 5/16” inverted
flare fitting. Do not change the position of the escutcheon plate.
•
Pull the fuel connection assembly clear of the burner housing.
3. Loosen the two transformer hold-down screws.
•
Lift the hinged transformer to its open position.
4. There are eight wires in the fuel line assembly wire bundle.
•
Mark and disconnect the wires from their terminals in the burner
junction box.
5. Disconnect the nozzle air hose from the fitting at the air compressor.
•
Pull the hose through the opening “into” the burner housing.
6. The fuel line assembly may now be removed by either
•
Pulling the assembly up slightly and toward the rear of the burner
housing.
•
OR removing the burner and end cone and pulling straight out of
the blast tube. See page 28 for details.
Transformer in the
“open” position
Fuel Connection
Fuel Line
Assembly
Removed