Form 465, Page 6
Additional
Parts
Shipped with each boiler is a re-
mote fuel pump, a draft inducer
and a carton of parts. The car-
ton contains parts required for
installation. Before beginning
actual installation, verify that
the remote fuel pump, the draft
inducer, and all the parts listed
on page 7 are at the installation
site.
Pump
Safety
Warnings
Continued
Venting
Air for
Combustion
Non-
Compliance
Failure to install or maintain this boiler properly will void the warranty.
WARNING: Failure to provide proper venting could
result in death, serious injury, and/or property damage.
Units must be installed with a flue connection, draft
regulator, draft inducer, and proper vent to the outside
of the building. Safe operation of any gravity-vented oil-
burning equipment requires a properly operating vent
system, correct provision for combustion air, and regular
maintenance and inspection.
WARNING: Care should be exercised to ensure that an
adequate supply of combustion air is available and free
to enter the air openings on all burners. Room openings
must equal one square inch per each 1,000 BTU heat
input.
Check the boiler for any damage that may have occurred in shipment!
If damage is found, file a claim with the transport company. Your unit was
inspected at the factory prior to crating and was in perfect condition at that
time. Open the boxes and verify receipt of all parts.
Unpacking and Inspection
Draft Inducer
P/N 174705, 115V for Sizes
140, 235, 350
175993, 230V for Size 500