INSTALLATION—CONTINUED
Field-Installation of Cooling Coil Cabinet and Downturn Plenum—Continued
(4) Locate coil blockoff plate and measure up 4 inches (102 mm) from bottom of blockoff plate . Drill second
7/8-inch hole at that location at center point of blockoff plate . Hole should be approximately even with first
hole drilled in downturn plenum leg .
(5) On cabinet leg on entering air side of cooling coil cabinet, measure up 10 inches (254 mm) from bottom
pan and then in 4inches (102 mm) from edge . Drill third 7/8-inch hole at that location .
b . On outside of furnace section where flanges were joined in step 4, locate three hole plugs and remove center
plug to expose 7/8-inch hole in cabinet leg (see
c . Run damper motor wires:
(1) Out through hole in discharge plenum leg into cooling coil cabinet .
(2) Through blockoff plate across coil cabinet .
(3) Out through hole in cooling coil cabinet leg .
(4) Into furnace section .
d . On bottom of electrical box in furnace section, remove hole plug below terminal blocks and route damper motor
wires up through hole and into electrical box .
e . Connect wires in accordance with
Figure 11. Discharge Damper Wiring Connections