background image

1104UESAGBEN, page 4/31

2. UNIT HEATER     
    LOCATION

Use the minimum clearances in section 4 and the throw data in the technical data 
table addended when determining where to suspend the heater.
Recommended minimum height is 2.5mm.

WARNING

If touched, the vent pipe 
and internal heater sur-
faces that are accessible 
from outside the heater 
will cause  burns. Suspend 
the heater such that these 
components cannot be 
touched.

REMARK

Flue requirements may 
affect location.  Consult 
section 6 before making a 

fi

 nal determination.

For best results, the heater should be placed with certain rules in mind. Always 
ensure that minimum clearances are maintained.  Locating a unit heater above 
the maximum recommended height can result in signi

fi

 cant air strati

fi

 cation.  

When possible, heaters should be arranged to blow toward or along exposed 
wall surfaces.
Suspended heaters are most effective when located as close to the working zone 
as possible, but care should be exercised to avoid directing the discharged air 
directly on occupants. 
Partitions, columns, counters, or other obstructions should be taken into consid-
eration when locating the unit heater so that a minimum quantity of air

fl

 ow will be 

de

fl

 ected by such obstacles.

When units are located in the centre of the space to be heated, the air should 
be discharged toward the exposed walls. In large areas, units should be located 
to discharge air along exposed walls with extra units provided to discharge air 
in toward the centre of the area. For optimum results heaters are best used in 
conjunction with recirculating air fans suspended at high level.

At those points where in

fi

 ltration of cold air is excessive, such as at entrance 

doors and shipping doors, it is desirable to locate the unit so that it will dis-
charge directly toward the source of cold air, typically from a distance of 4.5 to 
6.0 meters or install a down

fl

 ow unit over the door opening.

CAUTION

Do not locate the heater 
where it may be exposed 
to water.

Hazards of Chlorine - applies to the location of the combustion air inlet

The presence of chlorine vapours in the combustion air of gas-

fi

 red  heating 

equipment presents a potential corrosion hazard. Chlorine, found usually in the 
form of freon or degreaser compounds when exposed to a 

fl

 ame will precipitate 

from the compound, and go into solution with any condensation that is present 
in the heat exchanger or associated parts. The result is hydrochloric acid which 
readily attacks all metals. Care should be taken to separate these vapours from 
the combustion process. This may be done by wise location of the unit 

fl

 ue and 

combustion air terminals with regard to exhausters or prevailing wind directions. 
Chlorine is heavier than air. Keep this fact in mind when determining installation 
location of the heater in relation to building extract systems. 

3. UNCRATING & 
    PREPARATION

This unit was test operated and inspected at the factory prior to crating and was 
in proper operating condition. If the heater has incurred damage in shipment, 
document the damage with the transport company and contact your supplier.
Check the rating plate for the gas and electrical speci

fi

 cations of the heater to be 

sure that they are compatible with the gas and electric supplies at the installation 
site. 
Read this booklet and become familiar with the installation requirements of your 
heater. If you do not have knowledge of local requirements, check with the gas 
supplier and any other local agencies who might have requirements concerning 
this installation. 
Before beginning, make preparations for necessary supplies, tools, and man-
power. 

If the installation includes optional vertical louvres or downturn nozzle etc.,  
install these options before the heater is suspended. Follow the instruc-
tions included in the option package. 

Summary of Contents for UESA

Page 1: ...ufacturer does not take any responsibility in the event of non observance of the regulations concerning the connection of the apparatus causing a harmful operation possibly resulting in damage to the...

Page 2: ...4 Gas conversion 6 2 Venting and combustion air 6 2 1 Flue requirements 6 2 2 Flue requirement for installations type B 6 2 3 Flue requirement for installations type C 7 Electrical connections 16 7 1...

Page 3: ...ldren should be supervised to ensure that they do not play with the appliance 1 GENERAL 1 2 General information Models UESA 035 through 102 are design certified to the CE EN1020 standard for use in in...

Page 4: ...e of cold air typically from a distance of 4 5 to 6 0 meters or install a downflow unit over the door opening CAUTION Do not locate the heater where it may be exposed to water Hazards of Chlorine appl...

Page 5: ...Suspend the heater so that the bottom is a minimum of 2 5m above the floor Figure 1a Table 1a Clearances Heaters can be base mounted on suitable non combustible supports Attention The minimum overall...

Page 6: ...SA 035 055 083 102 Flue outlet Air inlet diameter mm 100 100 130 130 Gas connection diameter 3 4 3 4 3 4 3 4 Rear view Side view Front view Top view Legend 1 Combustion air inlet 130 2 Flue connection...

Page 7: ...d into the cabinet WARNING WARNING Unit must be level for proper Unit must be level for proper operation Do not place or operation Do not place or add additional weight to the add additional weight to...

Page 8: ...ervice NEVER TEST FOR LEAKS WITH AN OPEN FLAME Failure to comply could result in personal injury property damage or death Figure 3 Gas connection WARNING This appliance is equipped for a maxi mum gas...

Page 9: ...as valve Affix new data plate and gas type label Upon completition of conversion re commission the air heater in accordance with sec tion 9 of this document Changes to carry out Natural gas set pressu...

Page 10: ...ich will condense out within the flue No condensate leakage is permitted Horizontal flue runs must rise by 1 17mm per meter from the appliance to ensure that the condense returns to the flue drain Gas...

Page 11: ...both produced in the heater and collected from the vent ing system Therefore the installaton requires a condensate drain from the secondary heat exchanger and a condensate drain from the flue exhaust...

Page 12: ...es to be certain that this is permitted condensate from the heater has about the acidity of soda pop and is not harmful to a sanitary drain UESA heaters will produce condensate depending on size and g...

Page 13: ...ue pipe seamless aluminium pipes are required All joints must be sealed to prevent products of combustion from leaking into the building As condensation is unavoidable provision must be made for the c...

Page 14: ...l times Reliance on doors and windows is not permitted Always ensure that adequate combustion air is provided to suit the total instal lation of all combustion equipment in accordance with BS6230 or B...

Page 15: ...page 15 31 Figure 10 Approved appliances type C For illustrative purposes only For actual pipe con nections see figure 11 Figure 11 Type C appliances combustion air and flue pipe sockets C12 C52 C12b...

Page 16: ...o ensure correct operation of the unit An external burner reset switch with red indicator light is fitted on the heater To add a remote reset button make connections to the terminals in the electric b...

Page 17: ...1104UESAGBEN page 17 31 7 2 Wiring connection connection Smartcom...

Page 18: ...the prime safety shutoff All gas supply lines must be free of dirt or scale before connecting to the unit to ensure correct sealing 8 3 Safety controls 8 3 1 Combustion air pressure switch The combus...

Page 19: ...needs replacing use only the factory authorized re placement part for the size of heater For limit locations see figure 16a 8 3 2 Limit controls WARNING Never bypass the limit controls hazardous condi...

Page 20: ...down and the moment the combustion fan venter is de energized Start pre purge Energisation of venter motor If the differential pressure switch is in normally closed position start position Power to ga...

Page 21: ...Set thermostat to lowest setting 2 Turn off all electrical power to the heater 3 Shut the manual service valve at the inlet of the unit 4 Wait five 5 minutes for any gas to evacuate the heater Then s...

Page 22: ...nt in the air more frequent maintenance is recommended When any service is completed be careful to reassemble correctly to ensure that no unsafe conditions are created When starting the heater always...

Page 23: ...there is an accumulation of dirt dust and or lint clean the compartment and follow the instructions below to remove and clean the burner Caution use of eye protection is recommended Instructions for...

Page 24: ...paces between the burner ribbons Holding the burner assembly so that any foreign material will fall away from the burner use a stiff bristle brush to loosen and remove any foreign material s If the bu...

Page 25: ...mportant When reassembling the wire must remain attached to the ignitor Inspect the internal portion of the heat exchanger with burner assembly re moved At the burner flame entrance of each tube shine...

Page 26: ...1 If the heater is installed turn off the gas and dis connect the electric power 2 Open the access door and disconnect the fan motor wires 3 Remove the fan assembly fan guard motor and fan blade 4 Di...

Page 27: ...6 Follow the wiring diagram to properly connect the wires 7 Restore power to the heater and turn on the gas Light following the instructions on the lighting instruction plate Check for proper operati...

Page 28: ...or with emery cloth or steel wool Is the sensor located in flame Reposition flame sensor Is the heater grounded earthed Replace flame sensor Connect ground wire earth to unit chassis YES NO NO YES NO...

Page 29: ...mic spark electrode is cracked or grounded e Burner relay not grounded e Check burner relay ground wire f Unit not properly grounded f Make certain unit is properly field grounded earthed and properly...

Page 30: ...102 30 60618 450 Relay all 30 61748 Burner on indication lamp all 60 61996 reset switch all 60 61988 Gas valve nat gas 1st all 03 25136 Gas valve nat gas 2st all 03 25136 02 Gas valve prop 1st all 03...

Page 31: ...0 5 m s The air throw will be influ enced by the height of the building mounting height of the unit ambient temperature adjustment of the louvres 6 Sound pressure level in dB A in free field conditio...

Reviews: