12
Installation
Installation into vertical concrete shaft (without a mounting frame)
The product was tested and approved in:
Product
Range
Wall type
Classification
Avantage 60
350x385 mm ≤ Avantage 1V DP ≤ 700x1075 mm
Shaft
Concrete ≥ 70 mm
EI 60 (v
ed
i
n
o) S 500 C10000 AA multi
Avantage 120
350x385 mm ≤ Avantage 1V DP ≤ 700x1075 mm
Shaft
Concrete ≥ 70 mm
EI 90 (v
ed
i
n
o) S 500 C10000 AA multi
1. Rotate the four fastening plates on the damper 90° (to the
upright position).
The fastening plates are not used for an installation without a
mounting frame.
AVANTAGE DP
(W
n+
10
) x (H
n+
10
) mm
2. Make an opening with dimensions (W+10) x (H+10) mm.
Open and position the shutter in the opening. If VM magnet:
remove the key from the lock to open the shutter.
Fix the shutter in the opening using 4 screws and dowels Ø6 x
40 mm.
Connect the mechanism according to the wiring diagram.
Check the mobility of the shutter.
1
2