Installation
Installation into vertical shaft (without a mounting frame): general instructions for all types of shafts (other than concrete)
The product was tested and approved in:
Product
Range
Wall type
Classification
Avantage 60
350x385 mm ≤ Avantage 1V DP ≤ 700x1075 mm
Shaft
Promatect L500 ≥ 30 mm
EI 60 (v
ed
i
n
o) S 500 C10000 AA multi
Avantage 60
350x385 mm ≤ Avantage 1V DP ≤ 700x1075 mm
Shaft
Geoflam ≥ 30 mm
EI 60 (v
ed
i
n
o) S 500 C10000 AA multi
Avantage 60
350x385 mm ≤ Avantage 1V DP ≤ 700x1075 mm
Shaft
Geotec ≥ 30 mm
EI 60 (v
ed
i
n
o) S 500 C10000 AA multi
Avantage 60
350x385 mm ≤ Avantage 1V DP ≤ 700x1075 mm
Shaft
Tecniver ≥ 35 mm
EI 60 (v
ed
i
n
o) S 500 C10000 AA multi
Avantage 60
350x385 mm ≤ Avantage 1V DP ≤ 700x1075 mm
Shaft
Glasroc F V500 ≥ 35 mm
EI 60 (v
ed
i
n
o) S 500 C10000 AA multi
Avantage 60
350x385 mm ≤ Avantage 1V DP ≤ 700x1075 mm
Shaft
Exthamat ≥ 25 mm
EI 60 (v
ed
i
n
o) S 500 C10000 AA multi
Avantage 60
350x385 mm ≤ Avantage 1V DP ≤ 700x1075 mm
Shaft
Desenfire HD ≥ 25 mm HD
EI 60 (v
ed
i
n
o) S 500 C10000 AA multi
Avantage 120
350x385 mm ≤ Avantage 1V DP ≤ 700x1075 mm
Shaft
Promatect L500 ≥ 40 mm
EI 90 (v
ed
i
n
o) S 500 C10000 AA multi
Avantage 120
350x385 mm ≤ Avantage 1V DP ≤ 700x1075 mm
Shaft
Geoflam ≥ 35 mm
EI 90 (v
ed
i
n
o) S 500 C10000 AA multi
Avantage 120
350x385 mm ≤ Avantage 1V DP ≤ 700x1075 mm
Shaft
Tecniver ≥ 45 mm
EI 90 (v
ed
i
n
o) S 500 C10000 AA multi
Avantage 120
350x385 mm ≤ Avantage 1V DP ≤ 700x1075 mm
Shaft
Exthamat ≥ 30 mm
EI 90 (v
ed
i
n
o) S 500 C10000 AA multi
Avantage 120
350x385 mm ≤ Avantage 1V DP ≤ 700x1075 mm
Shaft
Desenfire ≥ 25 mm THD
EI 90 (v
ed
i
n
o) S 500 C10000 AA multi
Avantage 120
350x385 mm ≤ Avantage 1V DP ≤ 700x1075 mm
Shaft
Promatect L500 ≥ 50 mm
EI 120 (v
ed
i
n
o) S 500 C10000 AA multi
Avantage 120
350x385 mm ≤ Avantage 1V DP ≤ 700x1075 mm
Shaft
Geoflam ≥ 45 mm
EI 120 (v
ed
i
n
o) S 500 C10000 AA multi
Avantage 120
350x385 mm ≤ Avantage 1V DP ≤ 700x1075 mm
Shaft
Geoflam Light ≥ 35 mm
EI 120 (v
ed
i
n
o) S 500 C10000 AA multi
Avantage 120
350x385 mm ≤ Avantage 1V DP ≤ 700x1075 mm
Shaft
Geotec ≥ 45 mm
EI 120 (v
ed
i
n
o) S 500 C10000 AA multi
Avantage 120
350x385 mm ≤ Avantage 1V DP ≤ 700x1075 mm
Shaft
Exthamat ≥ 35 mm
EI 120 (v
ed
i
n
o) S 500 C10000 AA multi
Avantage 120
350x385 mm ≤ Avantage 1V DP ≤ 700x1075 mm
Shaft
Tecniver ≥ 50 mm
EI 120 (v
ed
i
n
o) S 500 C10000 AA multi
Avantage 120
350x385 mm ≤ Avantage 1V DP ≤ 700x1075 mm
Shaft
Glasroc F V500 ≥ 50 mm
EI 120 (v
ed
i
n
o) S 500 C10000 AA multi
Avantage 120
350x385 mm ≤ Avantage 1V DP ≤ 700x1075 mm
Shaft
Desenfire HD ≥ 35 mm HD
EI 120 (v
ed
i
n
o) S 500 C10000 AA multi
Avantage 120
350x385 mm ≤ Avantage 1V DP ≤ 700x1075 mm
Shaft
Desenfire ≥ 45 mm
EI 120 (v
ed
i
n
o) S 500 C10000 AA multi
1. Rotate the four fastening plates on the damper 90° (to the
upright position).
The fastening plates are not used for an installation without a
mounting frame.
AVANTAGE DP
e
≥ 105 mm
e
A = 2 x e + 10 mm
(W+
A
) x (H+
A
) mm
(W+10) x (H+10) mm
2. Make an opening with dimensions (W+A) x (H+A) mm.
A = 2 x thickness sleeve (e) + 10 mm.
Fit a sleeve of the same type and thickness of the duct (thick-
ness e) of minimum 105 mm deep in the opening.
Fix the sleeve to the shaft wall.
With the opening prepared the shutter can be handled into po-
sition, from the room side. Ensure that the trailing lead cables
are not trapped at this stage and freely hang loose. Do not dis-
tort or twist the frames as this will affect the correct operation
and sealing of the shutter. Check for squareness by measuring
the frame diagonals (they must measure the same).
Fix the shutter in the opening using 4 screws and dowels Ø6 x 40 mm.
Caution: make sure that the screws don't exceed the sleeve's
thickness!
Connect the mechanism according to the wiring diagram.
Check the mobility of the shutter.
Caution: before putting the installation into operation, clean
off all the dust and dirt.