background image

15

Installation

3. Set aside the screws that are affixed to one of the cross slats, 
then unscrew the 4 cross slats of the mounting frame and fold 
the 8 plates in the frame.

4. Rotate the four fastening plates on the damper 90° (to the 
upright position).

5. With the opening prepared the shutter can be handled 
into position, from the room side. Ensure that the trailing lead 
cables are not trapped at this stage and freely hang loose. Do 
not distort or twist the frames as this will affect the correct 
operation and sealing of the shutter. Check for squareness by 
measuring the frame diagonals (they must measure the same). 
Fasten the shutter onto the mounting frame with the 4 screws sup-
plied with the mounting frame, as shown in the drawing. Tightening 
the screws pulls the shutter towards the wall until its final position. 
It also makes it possible to slightly correct the angle of the 
shutter with respect to the mounting frame.

 

†

Caution: make sure that the screws don’t exceed the sleeve’s 

thickness!

Connect the mechanism according to the wiring diagram. 
Check the mobility of the shutter. 

 

†

Caution: before putting the installation into operation, clean 

off all the dust and dirt.

Product maintenance

Smoke control dampers must form part of a professionally designed Smoke and Heat Exhaust Ventilation System (SHEVS) that will 
be specially suited to an individual buildings size, usage and structure. SHEVS are Fire Safety Installations and it is essential they are 
subject to the routine inspection and maintenance requirements of the country of installation of the SHEV system. For example, 
BS7346 part 8, NF S 61-933 and EN 13306. Avantage and Kamouflage DP dampers are virtually maintenance free, however, they will 
require occasional operation and maintenance as part of a system specific routine operational test and maintenance procedure. It 
is recommended that as part of the system testing and maintenance procedure that different individual dampers are operated at 
each system test such that each damper within a system is inspected, checked and tested at least once in any 6-month period. The 
following instructions are a general guide and our recommendations to the procedures required: a) Operate each ventilator at least 
once; checking that the unit opens and closes fully. b) Visually observe the control mechanisms ensuring the devices are in place and 
are not obviously damaged or obstructed. c) Inspect each ventilator in its open position to check that the intumescent fire seals and 
smoke seals between the vent frame and doors are not damaged and are securely attached. Wipe any dirt build up from the seals. 
Inspect the door leading and trailing edge seals and lightly lubricate with a machine oil and a silicone grease to the release latch.

Maintenance

 

No specific maintenance required.

 

Schedule at least two running checks each year.

 

Remove dust and all other particles before start-up.

 

Follow the local maintenance regulations (i.e. BS9999 Annex V; NF S 61-933) and EN13306.

3

4

5

Summary of Contents for AVANTAGE DP

Page 1: ...rft be en Rf Technologies nv Lange Ambachtstraat 40 9860 Oosterzele Belgium Tel 32 9 362 31 71 Fax 32 9 362 33 07 info rft be 1812 V17 EN E 03 2019 AVANTAGE DP Motorised dual purpose smoke control dam...

Page 2: ...19 Explanation of the abbreviations and pictograms Wn nominal width Hn nominal height Sn free air passage E integrity I thermal insulation S smoke leakage 60 120 fire resistance time Pa pascal o i me...

Page 3: ...F V500 35 mm Exthamat 25 mm Desenfire HD 25 mm HD Concrete 70 mm Avantage 120 Shaft Promatect L500 40 mm 1 EI 90 v ed i n o S 500 C10000 AA multi Geoflam 35 mm Tecniver 45 mm Exthamat 30 mm Desenfire...

Page 4: ...5 5 simple operating tests through remote opening and resetting 5 5 optimal free air passage and minimal pressure loss tested according to EN 1366 10 compliant with EN 12101 8 approved for installati...

Page 5: ...ASY KAP Mounting frame delivered separately GFV PB Technical front protection grill aluminium frame and perforated plate fastened with screws 4 8x19mm free air passage of 69 4 Options at the time of o...

Page 6: ...on when fitting the product should be handled with care and remain protected from any sealing products Caution before putting the installation into operation clean off all the dust and dirt Caution be...

Page 7: ...n and blue opening brown and blue closing It is recommended that only control systems conforming to standards ISO 21927 9 pr EN12101 9 and EN 12101 10 are used to operate the smoke control dampers 1 T...

Page 8: ...les through the opening Use the fixation clips 1 and the plastic cable clamp 2 to attach the cables to the frame Position in the shaft 105 105 105 1 Smoke control dampers should be fitted to the smoke...

Page 9: ...foam come standard with the shutter They can be affixed to the inner face of the door to prevent it from hitting the shaft wall when opening 2 Be sure to cut these blocks to the correct dimensions so...

Page 10: ...h screws and dowels 6 x minimum 60 mm steel or stainless steel For an opening with dimensions up to W 20 x H 20 mm Two sealing lugs are provided at the bottom and at the top of the mounting frame fold...

Page 11: ...the mounting frame If VM magnet remove the key from the lock to open the shutter Fasten the shutter onto the mounting frame with the 4 screws supplied with the mounting frame as shown in the drawing T...

Page 12: ...mm EI 90 ved i n o S 500 C10000 AA multi 1 Rotate the four fastening plates on the damper 90 to the upright position The fastening plates are not used for an installation without a mounting frame AVAN...

Page 13: ...120 ved i n o S 500 C10000 AA multi Avantage 120 350x385 mm Avantage 1V DP 700x1075 mm Shaft Geoflam Light 35 mm EI 120 ved i n o S 500 C10000 AA multi Avantage 120 350x385 mm Avantage 1V DP 700x1075...

Page 14: ...ge 120 350x385 mm Avantage 1V DP 700x1075 mm Shaft Promatect L500 50 mm EI 120 ved i n o S 500 C10000 AA multi Avantage 120 350x385 mm Avantage 1V DP 700x1075 mm Shaft Geoflam 45 mm EI 120 ved i n o S...

Page 15: ...HEVS are Fire Safety Installations and it is essential they are subject to the routine inspection and maintenance requirements of the country of installation of the SHEV system For example BS7346 part...

Page 16: ...gether with the installation guidelines remote unlocking remote by connection of 24 V DC Resetting manual resetting rearm magnetic latch with key delivered in the bag together with the installation gu...

Page 17: ...7 11 3 11 9 12 5 13 3 14 0 14 7 15 4 685 kg 10 9 11 5 12 1 12 8 13 6 14 3 15 1 15 8 715 kg 11 2 11 8 12 4 13 1 13 9 14 7 15 4 16 2 745 kg 11 4 12 1 12 7 13 4 14 2 15 0 15 8 16 6 775 kg 11 6 12 3 13 0...

Page 18: ...m 350 400 450 500 550 600 650 700 385 Sn m 0 1090 0 1270 0 1450 0 1630 0 1810 0 1990 0 2170 0 2350 415 Sn m 0 1190 0 1380 0 1580 0 1770 0 1960 0 2160 0 2350 0 2550 445 Sn m 0 1280 0 1490 0 1700 0 1910...

Page 19: ...and voltage Approvals and certificates All our products are submitted to a number of tests by official test institutes Reports of these tests form the basis for the approvals of the products 1812 Efe...

Reviews: