background image

18

Selection data

Selection data

AVANTAGE DP 1V60 - 1V120

Hn\Wn [mm] 350

400

450

500

550

600

650

700

385

ζ [-]

 2,522 

 2,079 

 1,768 

 1,540 

 1,365 

 1,227 

 1,114 

 1,021 

 

 

 

 

 

 

 

415

ζ [-]

 2,263 

 1,869 

 1,592 

 1,388 

 1,231 

 1,107 

 1,006 

 0,923 

 

 

 

 

 

 

 

445

ζ [-]

 2,053 

 1,698 

 1,448 

 1,264 

 1,122 

 1,009 

 0,918 

 0,842 

 

 

 

 

 

 

 

475

ζ [-]

 1,879 

 1,556 

 1,328 

 1,160 

 1,031 

 0,927 

 0,844 

 0,774 

 

 

 

 

 

 

 

505

ζ [-]

 1,732 

 1,437 

 1,227 

 1,073 

 0,953 

 0,858 

 0,781 

 0,717 

 

 

 

 

 

 

 

535

ζ [-]

 1,607 

 1,334 

 1,141 

 0,998 

 0,887 

 0,799 

 0,727 

 0,667 

 

 

 

 

 

 

 

565

ζ [-]

 1,500 

 1,246 

 1,066 

 0,933 

 0,829 

 0,747 

 0,680 

 0,625 

 

 

 

 

 

 

 

595

ζ [-]

 1,406 

 1,169 

 1,001 

 0,876 

 0,779 

 0,702 

 0,639 

 0,587 

 

 

 

 

 

 

 

625

ζ [-]

 1,323 

 1,101 

 0,943 

 0,826 

 0,735 

 0,662 

 0,603 

 0,554 

 

 

 

 

 

 

 

655

ζ [-]

 1,250 

 1,041 

 0,892 

 0,781 

 0,695 

 0,627 

 0,571 

 0,524 

 

 

 

 

 

 

 

685

ζ [-]

 1,185 

 0,987 

 0,846 

 0,741 

 0,660 

 0,595 

 0,542 

 0,498 

 

 

 

 

 

 

 

715

ζ [-]

 1,126 

 0,938 

 0,805 

 0,705 

 0,628 

 0,566 

 0,516 

 0,474 

 

 

 

 

 

 

 

745

ζ [-]

 1,073 

 0,895 

 0,767 

 0,673 

 0,599 

 0,540 

 0,492 

 0,452 

 

 

 

 

 

 

 

775

ζ [-]

 1,025 

 0,855 

 0,733 

 0,643 

 0,573 

 0,517 

 0,471 

 0,433 

 

 

 

 

 

 

 

805

ζ [-]

 0,981 

 0,818 

 0,703 

 0,616 

 0,549 

 0,495 

 0,451 

 0,415 

 

 

 

 

 

 

 

835

ζ [-]

 0,941 

 0,785 

 0,674 

 0,591 

 0,527 

 0,475 

 0,433 

 0,398 

 

 

 

 

 

 

 

865

ζ [-]

 0,904 

 0,755 

 0,648 

 0,568 

 0,507 

 0,457 

 0,417 

 0,383 

 

 

 

 

 

 

 

895

ζ [-]

 0,870 

 0,726 

 0,624 

 0,547 

 0,488 

 0,440 

 0,401 

 0,369 

 

 

 

 

 

 

 

925

ζ [-]

 0,838 

 0,700 

 0,602 

 0,528 

 0,470 

 0,425 

 0,387 

 0,356 

 

 

 

 

 

 

 

955

ζ [-]

 0,809 

 0,676 

 0,581 

 0,510 

 0,454 

 0,410 

 0,374 

 0,344 

 

 

 

 

 

 

 

985

ζ [-]

 0,782 

 0,653 

 0,562 

 0,493 

 0,439 

 0,397 

 0,362 

 0,332 

 

 

 

 

 

 

 

1015

ζ [-]

 0,757 

 0,632 

 0,544 

 0,477 

 0,425 

 0,384 

 0,350 

 0,322 

 

 

 

 

 

 

 

1045

ζ [-]

 0,733 

 0,613 

 0,527 

 0,462 

 0,412 

 0,372 

 0,339 

 0,312 

 

 

 

 

 

 

 

1075

ζ [-]

 0,711 

 0,594 

 0,511 

 0,448 

 0,400 

 0,361 

 0,329 

 0,303 

 

 

 

 

 

 

 

AVANTAGE DP 1V60 - 1V120  -  Free air passage (m²)

Hn\Wn [mm]

350

400

450

500

550

600

650

700

385

Sn [m²]

0,1090

0,1270

0,1450

0,1630

0,1810

0,1990

0,2170

0,2350

 

 

415

Sn [m²]

0,1190

0,1380

0,1580

0,1770

0,1960

0,2160

0,2350

0,2550

 

 

445

Sn [m²]

0,1280

0,1490

0,1700

0,1910

0,2120

0,2330

0,2540

0,2750

 

 

475

Sn [m²]

0,1380

0,1610

0,1830

0,2050

0,2280

0,2500

0,2730

0,2950

 

 

505

Sn [m²]

0,1480

0,1720

0,1960

0,2200

0,2440

0,2680

0,2920

0,3150

 

 

535

Sn [m²]

0,1580

0,1830

0,2080

0,2340

0,2590

0,2850

0,3100

0,3360

 

 

565

Sn [m²]

0,1670

0,1940

0,2210

0,2480

0,2750

0,3020

0,3290

0,3560

 

 

595

Sn [m²]

0,1770

0,2050

0,2340

0,2620

0,2910

0,3190

0,3480

0,3760

 

 

625

Sn [m²]

0,1870

0,2170

0,2470

0,2770

0,3070

0,3360

0,3660

0,3960

 

 

655

Sn [m²]

0,1960

0,2280

0,2590

0,2910

0,3220

0,3540

0,3850

0,4170

 

 

685

Sn [m²]

0,2060

0,2390

0,2720

0,3050

0,3380

0,3710

0,4040

0,4370

 

 

715

Sn [m²]

0,2160

0,2500

0,2850

0,3190

0,3540

0,3880

0,4230

0,4570

 

 

745

Sn [m²]

0,2260

0,2620

0,2980

0,3330

0,3690

0,4050

0,4410

0,4770

 

 

775

Sn [m²]

0,2350

0,2730

0,3100

0,3480

0,3850

0,4230

0,4600

0,4970

 

 

805

Sn [m²]

0,2450

0,2840

0,3230

0,3620

0,4010

0,4400

0,4790

0,5180

 

 

835

Sn [m²]

0,2550

0,2950

0,3360

0,3760

0,4170

0,4570

0,4970

0,5380

 

 

865

Sn [m²]

0,2640

0,3060

0,3480

0,3900

0,4320

0,4740

0,5160

0,5580

 

 

895

Sn [m²]

0,2740

0,3180

0,3610

0,4050

0,4480

0,4910

0,5350

0,5780

 

 

925

Sn [m²]

0,2840

0,3290

0,3740

0,4190

0,4640

0,5090

0,5540

0,5990

 

 

955

Sn [m²]

0,2940

0,3400

0,3870

0,4330

0,4790

0,5260

0,5720

0,6190

 

 

985

Sn [m²]

0,3030

0,3510

0,3990

0,4470

0,4950

0,5430

0,5910

0,6390

 

 

1015

Sn [m²]

0,3130

0,3630

0,4120

0,4610

0,5110

0,5600

0,6100

0,6590

 

 

1045

Sn [m²]

0,3230

0,3740

0,4250

0,4760

0,5270

0,5780

0,6290

0,6790

 

 

1075

Sn [m²]

0,3330

0,3850

0,4370

0,4900

0,5420

0,5950

0,6470

0,7000

 

 

Summary of Contents for AVANTAGE DP

Page 1: ...rft be en Rf Technologies nv Lange Ambachtstraat 40 9860 Oosterzele Belgium Tel 32 9 362 31 71 Fax 32 9 362 33 07 info rft be 1812 V17 EN E 03 2019 AVANTAGE DP Motorised dual purpose smoke control dam...

Page 2: ...19 Explanation of the abbreviations and pictograms Wn nominal width Hn nominal height Sn free air passage E integrity I thermal insulation S smoke leakage 60 120 fire resistance time Pa pascal o i me...

Page 3: ...F V500 35 mm Exthamat 25 mm Desenfire HD 25 mm HD Concrete 70 mm Avantage 120 Shaft Promatect L500 40 mm 1 EI 90 v ed i n o S 500 C10000 AA multi Geoflam 35 mm Tecniver 45 mm Exthamat 30 mm Desenfire...

Page 4: ...5 5 simple operating tests through remote opening and resetting 5 5 optimal free air passage and minimal pressure loss tested according to EN 1366 10 compliant with EN 12101 8 approved for installati...

Page 5: ...ASY KAP Mounting frame delivered separately GFV PB Technical front protection grill aluminium frame and perforated plate fastened with screws 4 8x19mm free air passage of 69 4 Options at the time of o...

Page 6: ...on when fitting the product should be handled with care and remain protected from any sealing products Caution before putting the installation into operation clean off all the dust and dirt Caution be...

Page 7: ...n and blue opening brown and blue closing It is recommended that only control systems conforming to standards ISO 21927 9 pr EN12101 9 and EN 12101 10 are used to operate the smoke control dampers 1 T...

Page 8: ...les through the opening Use the fixation clips 1 and the plastic cable clamp 2 to attach the cables to the frame Position in the shaft 105 105 105 1 Smoke control dampers should be fitted to the smoke...

Page 9: ...foam come standard with the shutter They can be affixed to the inner face of the door to prevent it from hitting the shaft wall when opening 2 Be sure to cut these blocks to the correct dimensions so...

Page 10: ...h screws and dowels 6 x minimum 60 mm steel or stainless steel For an opening with dimensions up to W 20 x H 20 mm Two sealing lugs are provided at the bottom and at the top of the mounting frame fold...

Page 11: ...the mounting frame If VM magnet remove the key from the lock to open the shutter Fasten the shutter onto the mounting frame with the 4 screws supplied with the mounting frame as shown in the drawing T...

Page 12: ...mm EI 90 ved i n o S 500 C10000 AA multi 1 Rotate the four fastening plates on the damper 90 to the upright position The fastening plates are not used for an installation without a mounting frame AVAN...

Page 13: ...120 ved i n o S 500 C10000 AA multi Avantage 120 350x385 mm Avantage 1V DP 700x1075 mm Shaft Geoflam Light 35 mm EI 120 ved i n o S 500 C10000 AA multi Avantage 120 350x385 mm Avantage 1V DP 700x1075...

Page 14: ...ge 120 350x385 mm Avantage 1V DP 700x1075 mm Shaft Promatect L500 50 mm EI 120 ved i n o S 500 C10000 AA multi Avantage 120 350x385 mm Avantage 1V DP 700x1075 mm Shaft Geoflam 45 mm EI 120 ved i n o S...

Page 15: ...HEVS are Fire Safety Installations and it is essential they are subject to the routine inspection and maintenance requirements of the country of installation of the SHEV system For example BS7346 part...

Page 16: ...gether with the installation guidelines remote unlocking remote by connection of 24 V DC Resetting manual resetting rearm magnetic latch with key delivered in the bag together with the installation gu...

Page 17: ...7 11 3 11 9 12 5 13 3 14 0 14 7 15 4 685 kg 10 9 11 5 12 1 12 8 13 6 14 3 15 1 15 8 715 kg 11 2 11 8 12 4 13 1 13 9 14 7 15 4 16 2 745 kg 11 4 12 1 12 7 13 4 14 2 15 0 15 8 16 6 775 kg 11 6 12 3 13 0...

Page 18: ...m 350 400 450 500 550 600 650 700 385 Sn m 0 1090 0 1270 0 1450 0 1630 0 1810 0 1990 0 2170 0 2350 415 Sn m 0 1190 0 1380 0 1580 0 1770 0 1960 0 2160 0 2350 0 2550 445 Sn m 0 1280 0 1490 0 1700 0 1910...

Page 19: ...and voltage Approvals and certificates All our products are submitted to a number of tests by official test institutes Reports of these tests form the basis for the approvals of the products 1812 Efe...

Reviews: