14
Installation
Installation into vertical shaft with built-in mounting frame: general instructions for all types of shafts (other than concrete)
e
≥ 125 mm
KAMOUFLAGE MP
EASY-KAP ME/MP
e
A = 2 x e + 20 mm
(W+
A
) x (H+
A
) mm
(W+
20) x (H+
20) mm
1. Make an opening with dimensions (W+A) x (H+A) mm.
A = 2 x thickness sleeve (e) + 20 mm.
Fit a sleeve of the same type of material and thickness of the
duct (thickness e) of minimum 125 mm deep in the opening.
Fasten and seal the mounting frame. See details per type of
shaft hereafter.
2. Two fixing lugs are provided at the bottom and at the top of
the mounting frame: fold these against the sleeve.
When fixed with screws, fasten the mounting frame to the
sleeve with chipboard screws (Ø 6 x e) mm. These screws can
be fixed in one of the openings provided for this purpose,
depending on the depth of the sleeve.
Take care not to misshape the frame during its installation. The
finished opening must have the same size as the mounting
frame (W+10) x (H+10) mm.
3. Put aside the screws that are affixed to one of the cross slats,
then unscrew the 4 cross slats of the mounting frame and fold
the 8 fastening plates in the frame.
When the EASY-KGC ME/MP mounting frame is used, unfold
the drop-guard grid (90°) in the shaft.
4. Rotate the four fastening plates on the damper 90° (to the
upright position).
1
2
3
4