17
Installation
Installation into vertical shaft GEOFLAM (LIGHT) / GEOTEC with built-in mounting frame
The product was tested and approved in:
Product
Range
Wall type
Classification
Kamouflage 60 MP
350x385 mm ≤ Kamouflage 1V MP ≤ 700x1075 mm Shaft
Geoflam ≥ 30 mm
EI 60 (v
ed
i
n
o) S 1500 C10000 AA multi
Kamouflage 60 MP
350x385 mm ≤ Kamouflage 1V MP ≤ 700x1075 mm Shaft
Geotec ≥ 30 mm
EI 60 (v
ed
i
n
o) S 1500 C10000 AA multi
Kamouflage 120 MP
350x385 mm ≤ Kamouflage 1V MP ≤ 700x1075 mm Shaft
Geoflam ≥ 35 mm
EI 90 (v
ed
i
n
o) S 1500 C10000 AA multi
Kamouflage 120 MP
350x385 mm ≤ Kamouflage 1V MP ≤ 700x1075 mm Shaft
Geoflam ≥ 45 mm
EI 120 (v
ed
i
n
o) S 1500 C10000 AA multi
Kamouflage 120 MP
350x385 mm ≤ Kamouflage 1V MP ≤ 700x1075 mm Shaft
Geoflam Light ≥ 35 mm
EI 120 (v
ed
i
n
o) S 1500 C10000 AA multi
Kamouflage 120 MP
350x385 mm ≤ Kamouflage 1V MP ≤ 700x1075 mm Shaft
Geotec ≥ 45 mm
EI 120 (v
ed
i
n
o) S 1500 C10000 AA multi
e
≥ 125 mm
KAMOUFLAGE MP
EASY-KAP ME/MP
e
A = 2 x e + 20 mm
(W+
A
) x (H+
A
) mm
(W+
20) x (H+
20) mm
1. Coat the edges of the opening with adhesive plaster type
PLACOL (in case of Geoflam) or GEOCOL (S) (in case of Geotec).
In case of Geotec you can also assemble the sleeve with glue and
screws Ø 5 x (2 x e) mm and affix the assembled sleeve to the
shaft wall with glue and screws Ø 5 x (2 x e) mm every 100 mm.
Seal the joints between uprights and cross pieces and between
the lining and the wall with vegetable fibre caulking and
plaster or with GEOCOL (S) (in case of Geotec).
Two fixing lugs are provided at the bottom and at the top of
the mounting frame: fold these against the sleeve. Caulk the
mounting frame to the duct with vegetable fibre or (in case
of Geotec) you can also coat the opening with Geocol (S) and
fasten the mounting frame with screws of Ø 5 x e mm. Take
care not to misshape the frame. The finished opening must
have the same size as the mounting frame (W+10) x (H+10) mm.
Installation into vertical shaft GEOFLAM (LIGHT) / GEOTEC (without a mounting frame)
The product was tested and approved in:
Product
Range
Wall type
Classification
Kamouflage 60 MP
350x385 mm ≤ Kamouflage 1V MP ≤ 700x1075 mm Shaft
Geoflam ≥ 30 mm
EI 60 (v
ed
i
n
o) S 1500 C10000 AA multi
Kamouflage 60 MP
350x385 mm ≤ Kamouflage 1V MP ≤ 700x1075 mm Shaft
Geotec ≥ 30 mm
EI 60 (v
ed
i
n
o) S 1500 C10000 AA multi
Kamouflage 120 MP
350x385 mm ≤ Kamouflage 1V MP ≤ 700x1075 mm Shaft
Geoflam ≥ 35 mm
EI 90 (v
ed
i
n
o) S 1500 C10000 AA multi
Kamouflage 120 MP
350x385 mm ≤ Kamouflage 1V MP ≤ 700x1075 mm Shaft
Geoflam ≥ 45 mm
EI 120 (v
ed
i
n
o) S 1500 C10000 AA multi
Kamouflage 120 MP
350x385 mm ≤ Kamouflage 1V MP ≤ 700x1075 mm Shaft
Geoflam Light ≥ 35 mm
EI 120 (v
ed
i
n
o) S 1500 C10000 AA multi
Kamouflage 120 MP
350x385 mm ≤ Kamouflage 1V MP ≤ 700x1075 mm Shaft
Geotec ≥ 45 mm
EI 120 (v
ed
i
n
o) S 1500 C10000 AA multi
KAMOUFLAGE MP
e
≥ 125 mm
e
A = 2 x e + 10 mm
(W+
A
) x (H+
A
) mm
(W+10) x (H+10) mm
1. Coat the edges of the opening with adhesive plaster type
PLACOL (in case of Geoflam) or GEOCOL (S) (in case of Geotec).
Seal the joints between uprights and cross pieces and between
the lining and the wall with vegetable fibre caulking and
plaster or with GEOCOL (S) (in case of Geotec).
In case of Geotec you can also assemble the sleeve with glue and
screws Ø 5 x (2 x e) mm and affix the assembled sleeve to the
shaft wall with glue and screws Ø 5 x (2 x e) mm every 100 mm.
1
1