RFL VF-5XP
RFL Electronics Inc.
July 10, 2007
2
(973) 334-3100
SPECIFICATIONS
As of the date this Instruction Data Sheet was published, the following specifications apply to the RFL
VF-5XP module. Because all of RFL products undergo constant refinement and improvement, these
specifications are subject to change without notice.
Configuration:
Two independent voice channels per module.
Time Slots Required:
Channel One: Requires one user-selectable 64-Kbps time slot.
Channel Two: Requires two 64-Kbps time slots. (Must be after channel 1’s time slot)
Remote Interface:
All settings can be changed in remote mode using NMS, except E&M signaling type. Access to
status registers, including board and firmware revision levels, is also provided through NMS.
Signal Levels:
CH1: TLP transmit range: -23 dBm to +10 dBm nominal (+13 dBm peak)
TLP receive range: -31.5 dBm to +10 dBm nominal (+13 dBm peak)
Level control resolution: 0.5 dB
Absolute level accuracy: 0.5 dB
CH2: TLP transmit range: +10 dBm to -23 dBm nominal (+13 dBm peak)
TLP receive range: +10 dBm to -22 dBm nominal (+13 dBm peak)
Level control resolution: 0.5 dB
Absolute level accuracy: 0.5 dB
Input Impedance:
600
Ω
nominal
Output Impedance:
600
Ω
nominal
Frequency Response relative to 1004 Hz:
CH1: 300 to 3000 Hz,
±
0.3 dB (bidirectional)
CH2: 300 to 4000 Hz,
±
0.3 dB (bidirectional)
Idle Channel Noise:
Less than 23 dBrnc0
Impulse Noise:
Maximum counts per 30-minute interval. (Input level -13dbm0(-29dbm) @ 1004 Hz.
Level Adjustment set to -16dBm in, +7dBm out.
Threshold
Level
(dBrnc)
Counts/30
minutes
-61
0
Signaling Format (Digital interface):
T1 systems: RBS (Robbed-Bit Signaling) AT&T PUB 43801
E1 systems: CAS (Channel Associated Signaling)
Transmission
Only
E&M Signaling Types:
Jumper selectable, E&M Type I, II, III and V