RFL Network Management Software
9. Input Type 1
Input Type 1 can be set to OR or AND. This is used when a second I/O module is installed to have
double input and output per teleprotection command.
10. Input Type 2
Input Type 2 can be set to OR or AND. This is used when a second I/O module is installed to have
double input and output per teleprotection command.
11. Input Type 3
Input Type 3 can be set to OR or AND. This is used when a second I/O module is installed to have
double input and output per teleprotection command.
12. Input Type 4
Input Type 4 can be set to OR or AND. This is used when a second I/O module is installed to have
double input and output per teleprotection command.
13. Func 1 pretrip timer (ms)
The Function 1 pretrip timer can be set from 0.00ms to 4.00ms in 0.25ms increments. Select the pretrip
timer value that you want from the pull down box. (0.25ms to 4.00ms are valid)
14. Func 2 pretrip timer (ms)
The Function 2 pretrip timer can be set from 0.00ms to 4.00ms in 0.25ms increments. Select the pretrip
timer value that you want from the pull down box. (0.25ms to 4.00ms are valid)
15. Func 3 pretrip timer (ms)
The Function 3 pretrip timer can be set from 0.00ms to 4.00ms in 0.25ms increments. Select the pretrip
timer value that you want from the pull down box. (0.25ms to 4.00ms are valid)
16. Func 4 pretrip timer (ms)
The Function 4 pretrip timer can be set from 0.00ms to 4.00ms in 0.25ms increments. Select the pretrip
timer value that you want from the pull down box. (0.25ms to 4.00ms are valid)
17. Func 1 unblock enable
The Function 1 unblock enable can be set to enable or disable. When set to enable, if you lose
communication for 20ms, the trip output will go active for 150ms.
18. Func 2 unblock enable
The Function 2 unblock enable can be set to enable or disable. When set to enable, if you lose
communication for 20ms, the trip output will go active for 150ms.
19. Func 3 unblock enable
The Function 3 unblock enable can be set to enable or disable. When set to enable, if you lose
communication for 20ms, the trip output will go active for 150ms.
20. Func 4 unblock enable
The Function 4 unblock enable can be set to enable or disable. When set to enable, if you lose
communication for 20ms, the trip output will go active for 150ms.
RFL 9508D UCC
RFL Electronics Inc.
September 7, 2012
4-25