Configuration
Table 5-3. Placement of PLC-TT Module Adapters.
Chassis configuration
Required rear slot locations
Notes
One, 2-function module adapter
Slots 5 through 7.
Two, 2-function module adapters
One in slots 5 through 7.
The other in slots 11 through 13.
A cable is required from slot 8 of
the motherboard to JP3 of The
PLC-TT Module.
One, 4-function module adapter
Slots 5 through 10.
See Figure 5-2 for a view of this
configuration.
Two, 4-function module adapters
One in slots 5 through 10.
This is referred to as module
adapter “A”.
The other in slots 11 through 16.
This is referred to as module
adapter “B”.
A cable is required from slot 8 of
the motherboard to JP3 of The
PLC-TT Module. See Figure 5-3
for a view of this configuration.
RFL 9508D UCC
RFL Electronics Inc.
May 27, 2011
5-5
(973) 334-3100