RFL 9785
RFL Electronics Inc.
April 25, 2005
14-5
(973) 334-3100
039 – Reserve Key
This indicates if Reserve Key is active or inactive. When active, the
power level has been reduced to one-tenth of the power level.
040 – Remote Initiate
This indicates if Remote Initiate is active or inactive. When active, it
causes the Checkback sequence to be activated.
041 – Start
This indicates if Start is active or inactive. When active, it causes the
unit to transmit a Block.
042 – Stop
This indicates if Stop is active or inactive. When active, it overrides the
Start input.
043 – Block Output
This indicates if Block Output is active or inactive. When active, the unit
is receiving a valid Block signal.
044 – IRIG-B Status
This indicates if IRIG-B Status is active or inactive. When active, the
unit is receiving a valid IRIG-B signal.
100 – RxCh1 Level
Indicates the Channel 1 receive level
(+/-10 dB from nominal). This is
the same number that is displayed on the RFL 9785 front panel digital
meter.
102 – TxCh1 PWR(50ohm)
Indicates the amount of power that would be transmitted into an ideal,
balanced 50
Ω
load, with zero reflection (with source and load matched),
for Channel 1. Typical range is 1W to 10W
104 – TxCh1 Actual PWR
Indicates the actual power being transmitted into the load for Channel 1.
Theoretical range is 0W to 10W.
106 – TxCh1 REFL PWR
Indicates the Channel 1, percent reflected power. Numerical range is 0%
to 40%. Over 40% reflected power will be displayed as >40%.
If there is an open or short, “OPEN” or “SHORT” will be displayed.