032 - Reset Log
Whenever this parameter is invoked, the three test logs (TESTS RUN, TESTS PASSED, and
TESTS FAILED) are reset in non-volatile RAM. This parameter can only be invoked at the
Master checkback module.
033 - Chassis Type
This parameter must be set according to the type of chassis housing the checkback module
being programmed. When housed in an RFL 9785 chassis, this parameter must be set to “85P.”
034 - Test One
035 - Test Two
036 - Test Three
037 - Test Four
038 - Test Five
039 - Test Six
040 - Test Seven
041 - Test Eight
These parameters control what happens during each of the eight checkback tests that can occur
during a test sequence. For each test, different values are stored; these values determine what
codes the checkback module will respond to, what code will be transmitted in response, and the
power level to be used during transmission. The values displayed will vary according to the
setting of Parameter #20 (Mode).
050 - Receive Block
This is a “print trigger” parameter; it can send a printout message to your terminal when a
block is received. To activate, set this parameter to “Y” for yes; to de-activate, set it to “N” for
no.
051 - Lose Block
This is a “print trigger” parameter; it can send a printout message to your terminal when a
block ceases to be received. To activate, set this parameter to “Y” for yes; to de-activate, set it
to “N” for no.
052 - Test Fail
This is a “print trigger” parameter; it can send a printout message to your terminal whenever a
checkback test fails. To activate, set this parameter to “Y” for yes; to de-activate, set it to “N”
for no.
This parameter can only be set at the Master checkback module.
053 - Transmit Fail
This is a “print trigger” parameter; it can send a printout message to your terminal whenever a
TRANSMIT FAIL alarm occurs. To activate, set this parameter to “Y” for yes; to de-activate,
set it to “N” for no.
This parameter can only be set at checkback modules housed in RFL 9785 chassis.
054 - Rem Alarm Enabled (Remote only)
When set to Yes, an alarm and test failure relay will happen if >24 hours occurs between
receiving a test request.
055 - Test OK Pulse (Master Only)
Test failure relay will remain in failure position except for a ten second pulse after a successful
test.