Radio Frequency Systems
BD4200W Series Air Dryer User’s Guide
Page 81 of 114
100518835 - Rev. B
9.15.5
After one (1) minute,
verify that a High Outlet
Pressure Alarm appears on
the display.
9.15.6
Press the
RESET Button
to clear the alarm.
9.15.7
Turn Outlet Pressure
Regulator knob counter-
clockwise until Outlet
Pressure (
OUTLET
) reading
lowers to the reading
recorded in step 9.15.1
9.15.8
Push knob in to lock.
9.15.9
Reinstall the Front Panel (section 8.10 ).
If you are unable to create a High Outlet Pressure Alarm as described, see
section 13.6 for troubleshooting information.