Radio Frequency Systems
BD4200W Series Air Dryer User’s Guide
Page 22 of 114
100518835 - Rev. B
6.5.23
Connect a Common Alarm (as required):
6.5.23.1
Insert the included
Alarm Connector into
either of the two (2)
Alarm Ports.
6.5.23.2
Wire an external
alarm wire pair to the
Alarm Connector as
required:
Common
and
N.C.
for
OPEN ON ALARM
operation.
Common
and
N.O.
for CLOSE ON ALARM operation.
6.5.24
REGISTER YOUR DRYER. See section 7 for details.
6.6 Installation Checklist
No shipping damage was detected.
Dryer location meets the following requirements:
o
Well ventilated
o
Free from abrasive dust or chemicals
o
Ambient temperature is between 40° and 85° F (optimal)
Shipping block removed from Compressor Tray.
System Pressure is set to 50 PSI (345 KPa).
Static Pressure is set to 20 PSI (138 KPa).
No air leaks are present in the system.
No alarms are present on the Display Panel.