24
Installation
Installation in flexible and rigid wall, sealing with rigid rock wool boards with coating
The product was tested and approved in:
Range
Wall type
Sealing
Classification
200x200 mm ≤ CU2 ≤ 1200x800 mm Rigid wall
Aerated concrete ≥ 100 mm
Stone wool + coating ≥ 140 kg/m³ EI 90 (v
e
i
n
o) S - (300 Pa)
200x200 mm ≤ CU2 ≤ 1200x800 mm Flexible wall
Metal studs gypsum plasterboard Type A
(EN 520) ≥ 100 mm
Stone wool + coating ≥ 140 kg/m³ EI 60 (v
e
i
n
o) S - (500 Pa)
200x200 mm ≤ CU2 ≤ 1200x800 mm Flexible wall
Metal studs gypsum plasterboard Type F
(EN 520) ≥ 100 mm
Stone wool + coating ≥ 140 kg/m³ EI 90 (v
e
i
n
o) S - (300 Pa)
≥ 40 kg/m³
100 mm
F (EN520)
A (EN520)
≤ 300
≤ 300
50
2x12.5 / 1x25 mm
≤ Wn+600
≤ Hn+600
1. The opening around the damper is sealed with 2 layers of
50 mm-thick mineral wool panels with fire resistant coating on
one side (type PROMASTOP-CB 50 / PROMASTOP-CB/CC 50 /
HILTI CFS-CT B).
PROMASTOP-E / CC
HILTI CFS-S ACR
140 kg/m³
PROMASTOP-CB 50 (CC)
/ HILTI CFS-CT B
≤ 300
≤ 300
PROMASTOP-E / CC
HILTI CFS-S ACR
PROMASTOP-E / CC
HILTI CFS-S ACR
4. The joints on these 2 layers must be installed staggered and
covered all around the edge with coating (type PROMASTOP-E /
PROMASTOP-CC / HILTI CFS-S-ACR).
1
2
3
4