background image

65

quence will be executed on the next heat cycle.

The IFC continues the pressure switch proving sequence
by energizing the inducer at the rpm determined for the
high pressure switch during cold calibration and waits for
both the high and low pressure switches to close. The IFC
shall wait for 60 seconds for the switches to close. If the
low and high pressure switches are not both closed within
10 seconds, the IFC will set and display the low-level fault

45

” and/or “

57

” at the SSD and continue trying to close

the switches (at the same RPM) for the balance of one
minute. A re-learn cycle will not be required provided the
switches are both closed within the minute. If the offending
pressure switch(es) does/do not close within the 60 sec-
ond period, the control will initiate the five minute
wait/lockout period. After the five minute wait period, the
control shall initiate a new calibration sequence provided a
call for gas heat still exists. 

If the mid pressure switch fails to close during the pres-
sure switch proving sequence, the fault code 

“67”

will be

set and displayed simultaneously with the 

“H”

or 

“h”

(as

appropriate) and the proving and pre-purge sequences will
continue as long as all other requirements are met. How-
ever, furnace operation will fix to 70% any heating rate
which is between 50% and 65% regardless of the demand
of the thermostat until a successful calibration of the mid
pressure switch is completed. Also, a new calibration se-
quence will be executed on the next heat cycle.

Pre-Purge

The gas valve 100% rate demand command is to be
transmitted to the valve during the pre-purge period and
before ignition. The command must be sent and verified in
a timely manner so as not to interfere with or lengthen the
pre-purge cycle.

The furnace control begins a 30 second pre-purge period
at the cold high pressure switch inducer speed. Pre-Purge
is the amount of time the inducer runs before an attempt
for ignition. 

If either or both the high and low pressure switch(es)
open(s) for longer than 2 seconds but less than 60 sec-
onds during pre-purge, the IFC will reset the 30 pre-purge
start time to 0 seconds after the high and low pressure
switch(es) has/have re-closed. If either the high and/or low
the pressure switch(es) is/are open for longer than 60 sec-
onds, the IFC de-energizes the inducer and will enter a 5-
minute lockout period. The fault will be set to level 1 until
the end of the lockout period. After the lockout period, the
control will return to calibration for the next heat attempt. 

Trial for Ignition:

I.F.C. energizes the gas valve output and spark output si-
multaneously and begins to look for flame immediately.
When flame is detected for more than 1 second, the I.F.C.
immediately de-energizes the spark output. The spark out-
put is energized for a maximum of seven seconds. 

Ignition Activation Period (IAP)

= 7 seconds (IAP = Pe-

riod of time between energizing the main gas valve and
deactivation of the ignition means during a trial for ignition

period (per ANSI Z21.47, definition section)).

Trial for Ignition Period (TFI)

= 8 seconds (TFI = The pe-

riod of time between energizing and de-energizing the gas
valve if the supervised flame is not established (per ANSI
Z21.47, definition section)).

After the spark output is de-energized due to the expira-
tion of the 7 second period and flame is not detected, the
I.F.C. continues to look for flame for an additional 1 sec-
ond. If flame is not detected by the I.F.C. within 8 seconds
of the gas valve and igniter becoming energized, the I.F.C.
will de-energize the gas valve and initiate ignition retry.

Directly after ignition, if a valid heat demand still exists, the
furnace will operate at the 100% heat rate for 2 minutes if
cold calibration preceded, otherwise for the period of heat
blower on delay.

Warm Calibration

If the heat call is canceled prior to start of warm calibra-
tion, the warm calibration cycle will always be completed
before shutting down the gas heat.

After the 2 minute warm-up period (or 2 minutes after igni-
tion), if the calibration cycle has taken place prior to pre-
purge, the furnace control will continue calibration by
attempting to determine the necessary inducer RPM’s cor-
responding to the open and closed points for the mid and
high pressures switches. Directly after ignition, the furnace
will operate for 2 minutes at the 100% heat rate provided.
The inducer RPM for this rate shall be that which was de-
termined during the cold calibration of the high pressure
switch. Next, the inducer RPM will be dropped steadily
and the furnace control waits for the high pressure switch
to open. This cycle repeats until the high pressure switch
opens. If the high pressure switch fails to open once the
inducer RPM has reached a pre-determined minimum, the
furnace will exit the heat sequence and set, display and
log a fault 

“55”

. A new calibration (both cold and hot) will

take place upon entry into the next heat sequence. 

Once the high pressure switch opens, the inducer RPM is
then increased steadily and the IFC waits for the high
pressure switch to close. The cycle repeats until the high
pressure switch closes. The speed at which the inducer is
operating when the high pressure switch closes shall be
added to a pre-determined value. The resultant sum is to
be used as the target RPM for the 70% to 100% hot gas
heating rates (two minutes or longer after ignition). This
value is only to be used during steady-state heat and after
the ignition, blower on delay and two minute warm-up pe-
riod. 

If the high pressure switch fails to close after reaching a
pre-determined maximum value, the calibration and heat
sequence will be cancelled and the furnace will exit the
heat sequence normally (with post-purge and blower off
delay) and set, display and log a fault 

“57”

at level 2. A

new calibration will take place upon entry into the next
heat sequence.

Once the high pressure switch has re-closed, the gas
valve output is reduced to 65% for the hot mid pressure

START-UP AND SEQUENCE OF OPERATIONS

Int

eg

rat

ed

 Fu

rn

ace

 Co

ntr

ol

Summary of Contents for 97MDV060 Series

Page 1: ...M BLOWER 97V SERIES U L and or C S A recognized fuel gas and CO carbon monoxide detectors are rec ommended in all applications and their installation should be in accordance with the manufacturer s re...

Page 2: ...s for Alt Horizontal and Variant of Alt Horizontal Direct Vent Terminations Options 4 and 5 37 Option 6 7 Vertical and Horizontal Concentric Vent Termination RXGY E02A and RXGY E03A 38 Options 8 9 Sid...

Page 3: ...om the distributor and are correct for the installation If not return the unit without open ing the carton If the model number is correct open the carton and verify that the furnace rating label speci...

Page 4: ...acturer products meet current Federal OSHA Guidelines for safety California Proposition 65 warnings are required for certain products which are not covered by the OSHA standards California s Propositi...

Page 5: ...ows ______ Exhaust Vent Temperature record temperature TERMINATIONS DIRECT VENT VERTICAL ______ Intake 12 305mm min above roof snow level record height above anticipated snow level or in Canada intake...

Page 6: ...INSTRUC TIONS WARNING COMBUSTION AND VENTILATION AIR MUST BE PRO VIDED TO THE FURNACE AS REQUIRED BY THE NA TIONAL FUEL GAS CODE U S AND CSA B149 1 CANADA AND THE COMBUSTION AND VENTILATION AIR SECTIO...

Page 7: ...MBUSTION RETURN AIR TEMPERATURE MAINTAINED BE TWEEN 55 F 13 C AND 80 F 27 C AND CLEAN FURNACE DUCT WORK AND COMPO NENTS UPON SUBSTANTIAL COMPLETION OF THE CONSTRUCTION PROCESS AND VERIFY THAT THE FURN...

Page 8: ...height of eight 8 feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than...

Page 9: ...m freezing as required by local practices or codes A UL or CSA listed heat tape or UL or CSA approved heating cable with a rating of 3 6 watts per foot is acceptable pro tection when installed and mai...

Page 10: ...tion clear ances GENERAL INFORMATION cont FIGURE 4 6 8 OPTION A 2 PIPE OPTION B 2 3 PIPE C ST A1194 86 00 CLEARANCE FLUE VENT TO WALL WARNING DO NOT LIFT THE UNIT BY THE HEAT EXCHANGER TUBES DOING SO...

Page 11: ...T AIR INLET CONDENSATE DRAIN UPFLOW ELECTRICAL CONNECTION LINE VOLTAGE ELECTRICAL CONNECTION LOW VOLTAGE 22 96 23 80 8 00 11 00 17 44 29 05 26 17 32 88 23 00 14 00 28 06 1 12 29 62 62 19 83 OPTIONAL L...

Page 12: ...EQUIRES A ROTATION A MINIMUM OF 10 FROM HORIZONTAL AS SHOWN HORIZONTAL INSTALLATIONS REQUIRE CONDENSATE TRAP TO BE MOUNTED EXTERNALLY BELOW THE UNIT USE CAUTION MOUNT THE TRAP AFTER THE UNIT IS AT THE...

Page 13: ...BULKHEAD COUPLING HOSE DOUBLE ELBOW TUBE C HOSE CLAMP INTAKE AIR DIFFUSER 8 X 1 2 SCREW X4 8 X 1 2 SCREW X10 5 8 DRAIN HOSE B CONDENSATE TRAP BRACKET DOWN FLOW 2 PVC VANE 1 4 HOLE PLUG 1 2 DRAIN HOSE...

Page 14: ...6 UPFLOW WITH LEFT SIDE VENT Pg 17 18 DOWNFLOW WITH RIGHT VENT NON ZERO CLEARANCE Pg 19 22 DOWNFLOW ZERO CLEARANCE Pg 23 27 HORIZONTAL RIGHT WITH RIGHT VENT Pg 28 30 HORIZONTAL RIGHT WITH VERTICAL VEN...

Page 15: ...T SIDE REMOVE PLUG DISCARD DRILL 2 1 8 HOLES FOR THE BULKHEAD COUPLING 2 3 OPTION DRAIN LEFT DRILL 1 8 7 8 PLUG DISCARD DRILL 1 8 7 8 PLUG DISCARD INSTALL BULKHEAD COUPLING USING 2 SCREWS INSTALL IN J...

Page 16: ...PARTS HAVE A SLOPE IN DIRECTION OF WATER FLOW __ BOTH WORM DRIVES ON THE HOSE CLAMPS OF THE IDB COUPLING MUST BE LOCATED ON THE TOP OF THE COUPLING SEE LOCATION DETAIL IN THE GENERAL CONVERSION INSTR...

Page 17: ...MOVAL 1b REMOVE 3 3 8 FLUSH MOUNT PLUG FROM JACKET DISCARD 1c RELOCATE 2 3 8 FLUSH MOUNT PLUG FROM JACKET TO TOP PLATE 2 2a INSTALL 2 5 8 FLUSH MOUNT PLUG IN TOP PLATE 2b INSTALL 2 PIPE GROMMET AS SHO...

Page 18: ...UPLINGS ARE TIGHTENED __ ALL DRAIN PORTS ARE PLUGGED __ UNIT HAS FORWARD PITCH __ HEAT TAPE INSTALLED IF REQUIRED 5a LEFT SIDE DRAIN OPTION ATTACH HOSE A PRE INSTALLED TO BULKHEAD COUPLING INSTALL HOS...

Page 19: ...ating into the living space 6 If a filter is installed near the furnace be sure to have adequate space for installation and removal of the unit filter 7 NOTE Where the maximum airflow is 1800 CFM or m...

Page 20: ...TIONS INCLUDING CARBON MONOXIDE POISON ING OR DEATH FOR BOTTOM RETURN A SOLID METAL BASE PAN MUST NOT BE INSTALLED FIGURE 7 1 REMOVE BLOWER DOOR AS SHOWN RETAINING TAB DETAIL INSTALLATION OF SOLID ME...

Page 21: ...LAT INSTALLER BENT UP ALTERNATE BENT DOWN NOTES THIS VIEW IS REPRESENTATIVE OF BOTH SUPPLY AND RETURN OPENINGS DUCT FLANGES MUST BE FIELD BENT ALONG PERFORATIONS EITHER INTO OR OUT OF THE FURNACE AS N...

Page 22: ...Water softening chemicals De icing salts or chemicals Carbon tetrachloride Halogen type refrigerants Printing inks paint removers varnishes etc Cleaning solvents such as perchloroethyl ene Hydrochlori...

Page 23: ...erature plastic pipe from another gas or fuel burning appliance unless the re quired minimum clearances to combustibles are main tained between the plastic pipe and other pipes For Canada PVC CPVC and...

Page 24: ...ction in pres sure drop throughout the system 1 Cut pipe end square Chamfer edge of pipe Clean fitting socket and pipe joint area of all dirt grease and moisture 2 After checking pipe and socket for p...

Page 25: ...the outside of the structure such as in areas with large accu mulations of snow in winter Table 2 shows the equivalent lengths of different types of elbows Table 3 specifies the equivalent maximum ve...

Page 26: ...r 3 inch pipe Combinations of long sweep 90s standard 90s or 45s may be used but the manufacturer recommends the use of long sweep 90s whenever possible because the use of the maximum number of standa...

Page 27: ...Lengths section Table 3 Application of these products is limited to the terminations listed in Ta bles 4 and 5 below These manufacturers have provisions for B vent liners and chimney liners which can...

Page 28: ...be governed by the following guidelines 1 Avoid terminating under any kind of patio or deck How ever if necessary vent piping may be installed under a deck as long as the termination s is are not und...

Page 29: ...less than that specified in this table the space is defined as confined If the space is small enough to be designated as confined it must have openings into the space which are located in accor dance...

Page 30: ...t diameter for direct openings and vertical ducting only B Where communicating with the outdoors through horizontal ducts each opening shall have a minimum free area of 1 square inch for each 2 000 BT...

Page 31: ...he out doors and shall have a minimum of A 1 Square inch for each 3 000 BTUH of the total input rat ing of all equipment located in the enclosure and NON DIRECT VENT cont GENERAL VENTING REQUIREMENTS...

Page 32: ...RAL VENTING REQUIREMENTS AND GUIDELINES ST A1194 19 FIG B WARNING DO NOT USE VENT TERMINATIONS WHICH ARE NOT SPECIFIED IN THESE INSTRUCTIONS USING VENT TERMINATIONS OTHER THAN THOSE SPECI FIED HERE CA...

Page 33: ...LY WITH THE NATIONAL FUEL GAS CODE OR IN CANADA CSA B149 1 NATURAL GAS AND PROPANE INSTALLATION CODE AND LOCAL CODES TO PROVIDE ADEQUATE COMBUSTION AND VENTILATION AIR FOR THE FURNACE FAIL URE TO DO S...

Page 34: ...inimum only if no snow accumulation is anticipated Venting Terminations more than 24 above roof penetration re quire additional support 12 31cm U S CANADA TERMINATIONS MUST CONFORM TO CSA B149 1 10 SE...

Page 35: ...E ZONE AS THE EXHAUST TERMINATION 7 NO SCREENS MAY BE USED TO COVER COMBUSTION AIR OR EXHAUST 8 NO T S CAN BE INSTALLED AT THE TERMINATION 9 WALL PENETRATION AND VENT TERMINATIONS MUST BE WITH 2 PIPE...

Page 36: ...NAL TO THE STRUCTURE MUST BE INSULATED AS REQUIRED FOR LOCAL CLIMATE 10 WALL PENETRATION AND VENT TERMINATION MUST BE WITH 2 PIPE OPTION B ONLY NOTE 1 A TRAP IN THE COMBUSTION AIR PIPE IS NOT REQUIRED...

Page 37: ...ERMINATION ELBOWS MUST BE AT THE SAME ANGLE AND FACE THE SAME DIRECTION LEFT OR RIGHT 2 A WIND VANE MUST BE INSTALLED IN THE COM BUSTION AIR INLET PIPE AS SHOWN IN THE DIA GRAM 3 NUMBER AND DISTANCE B...

Page 38: ...hrough roofs or sidewalls One 5 inch diameter hole RXGY E03 RXGY E03A or 3 5 8 inch diameter hole RXGY E02 RXGY E02A is required for the installation See Figure 23 for the general layout Complete inst...

Page 39: ...sidewall termination kit NOTE Multiventing NO COMMON VENTING IS PER MITTED WITH THIS KIT NOTE With this option a trap on the inlet combustion air pipe is NOT required NOTE Install the vent and air in...

Page 40: ...0 000 Btuh 30kw 12 30cm 3 ft 9m 10 ft 3 05 m preferred 7 feet 2 1m 3 feet 9m within a height 15 feet 4 5m above the meter regulator assembly 3 feet 9m 6 inches 15cm for appliances 10 000Btuh 3kw 12 in...

Page 41: ...4 61cm ABOVE ROOF 6 1 8m MINIMUM 10 3m RECOMMENDED A A SEE SEE MINIMUM 12 31cm ABOVE GRADE IN U S 12 31cm U S CANADA TERMINATIONS MUST CONFORM TO CSA B149 1 10 SECT 8 14 48 MAX 122 cm 45 MAX 114 cm 36...

Page 42: ...it but the furnace will con tinue to run and heat will be provided If the installer uses this approach he must make sure that there is a mechanism for handling the possibility of water overflow onto...

Page 43: ...SATE WATER SENSOR TO SHUT THE FURNACE DOWN WHEN THE DRAIN IS BLOCKED THIS OPTION WILL NOT SPILL WATER FROM THE DRAIN VENT BUT THE FURNACE WILL ALSO NOT CONTINUE TO RUN WITH A BLOCKED DRAIN CONDENSATE...

Page 44: ...N AIR AND TENDS TO COLLECT AT LOWER LEVELS MAKING IT MORE DIFFICULT TO SMELL AT NOSE LEVEL NATURAL GAS IS LIGHTER THAN AIR AND WILL RISE POSSIBLY ACCUMULATING IN HIGHER PORTIONS OF THE STRUCTURE IF A...

Page 45: ...o easily remove the gas valve assembly Local codes may dictate the location of the ground joint union In stall a manual shut off valve in the gas line outside of the furnace casing and upstream of the...

Page 46: ...ITYTABLE CU FT HR Capacity of gas pipe of different diameters and lengths in cu ft per hr with pressure drop of 0 3 in and specific gravity of 0 60 natural gas Nominal Length of Pipe Feet Iron Pipe Si...

Page 47: ...al wiring must comply with the latest NFPA 70 National Electrical Code and all state and local codes Be sure to check the fuel code of your furnace The fuel code is adjacent to the serial number See t...

Page 48: ...pins together inside the jumper well This can be confirmed by visual inspection and by verifying proper manifold pressure at high fire 100 after the jumper is installed Manifold pressure should always...

Page 49: ...ressure Switch See Figure 37 12 Reconnect the supply gas line to the furnace 13 Place the conversion label adjacent to the A G A rating plate 14 Turn on gas supply and electrical supply 15 Check unit...

Page 50: ...ng value of 1100 BTU s ft3 at elevations from 0 2 000 ft All other elevations and heating values will require changing orifices and possibly input rate A Gas requirements LP or Natural The furnace is...

Page 51: ...gas pressure measurements If the supply gas line pressure is above these ranges in stall an in line gas regulator to the furnace for natural gas units With LP gas have the LP supplier reduce the line...

Page 52: ...s valve remove the outlet manifold pressure tap plug in the gas valve See Figure 39 2 Install field supplied pressure tap to the outlet manifold tap in place of the plug Connect the positive pressure...

Page 53: ...sure tap plug in the gas valve See Figure 39 2 Install field supplied pressure tap to the outlet manifold tap in place of the plug Connect the positive pressure hose from a manometer to the pressure t...

Page 54: ...1 Altitude Adjusted Gas Heating Value 975 BTU ft3 given from gas supplier 2 Meter used is 1 revolution per ft3 3 Time per revolution at high fire 36 seconds this is measured by the installer 4 From T...

Page 55: ...the low end will affect a lin ear adjustment to the entire range of heating airflow ex cept at the 100 rate The adjustment to the range will be such that the 40 heating rate will be adjusted up or dow...

Page 56: ...he return air temperature from the supply air temperature The dif ference is the temperature rise 5 Compare the measured temperature rise to the ap proved temperature rise range listed on the furnace...

Page 57: ...EVICE ___AMPERES DISPOSITIF DE PROTECTION CONTRE UNE SURINTENSITE DE ___A AU MAXIMUM NOx EMISSION LIMIT NANOGRAMS JOULE ___ LIMITE D MISSION D OXYDES D AZOTE NOx EN NANORAMMES PAR JOULE ___ HOURLY INP...

Page 58: ...e re versed Make all electrical connections in accordance with the latest edition of the National Electrical Codes If the line voltage electrical needs to be moved to the op posite side of the furnace...

Page 59: ...straight against spade terminal This low insertion force flag terminal will deliver an audible click when en gaged Failure to engage will cause defective contact THERMOSTAT The room thermostat must b...

Page 60: ...Maximum current is 1 0 amps for the electronic air cleaner output HUMIDIFIER Humidifier output is a set of dry contacts The logic control ling these contacts and the necessary wire diagrams for in sta...

Page 61: ...CREWS TO THE REAR OF THE FURNCE AT THE LOCATIONS PROVIDED UPFLOW HORIZONTAL SIDE RETURN ST A1194 10 X0 ST A1194 11 X0 FIGURE 46 FILTER LOCATIONS ACCESSORIES FIELD INSTALLED OPTION ACCESSORIES cont RXG...

Page 62: ...e will op erate at 40 heat rate regardless of the heat demand to W1 W2 or V This is done as follows For the single rate mode when dipswitch SW10 is ON and SW11 is OFF the furnace will operate in the 4...

Page 63: ...alibration Upon proving pressure switches open as noted above the furnace control will energize the inducer at a low starting RPM The furnace control will first verify that the inducer drive is operat...

Page 64: ...et to level 2 High Pressure Switch Cold Calibration Since the 65 heat inducer RPM is determined or the mid calibration sequence has been skipped for reasons stated the inducer speed is then increased...

Page 65: ...s valve and deactivation of the ignition means during a trial for ignition period per ANSI Z21 47 definition section Trial for Ignition Period TFI 8 seconds TFI The pe riod of time between energizing...

Page 66: ...of the 22 second blower on delay period unless the CFM demand of the cir culating airflow is below the threshold specified below Blower Motor Size CFM Cutoff 1 2 HP 500 CFM 3 4 HP 600 CFM Upon provin...

Page 67: ...67 INTEGRATED FURNACE CONTROL FIGURE 47 FURNACE CONTROL BOARD OR IFC INTEGRATED FURNACE CONTROL ST A1194 73 00 Integrated Furnace Control...

Page 68: ...n other communicating components are attached and communicating with the furnace control 6 LINE VOLTAGE CONNECTIONS 120VAC L1 Four spade terminals are provided for internal connections and accessories...

Page 69: ...between the thermostat terminals labeled R and HUM STAT A separate humidistat is not required for this configuration and the humidifier will turn on whenever there is a call for heat and the blower is...

Page 70: ...is included with EcoNet communicating thermostats To wire the furnace for humidification and de humidification control using an EcoNet communicating thermostat refer to the wiring diagram in Figure 4...

Page 71: ...UMIDISTAT 24V CONTACTS OPEN WHEN HUMIDITY IS ABOVE SET POINT ST A1194 80 00 SWITCH S2 8 MUST BE IN ON POSITION NOTE FACTORY POSITION IS OFF TURNING THIS SWITCH OFF WILL DISABLE DEHUMIDIFICATION OPERAT...

Page 72: ...OFF ON 700 CFM 1225 CFM ON ON 525 CFM 1050 CFM LOW COOL SELECTIONS The following CFM s will be used for low stage legacy cooling unless dipswitch SW9 is in the ON position in which case the low cooli...

Page 73: ...PSWITCHES FIGURE 53 DIPSWITCH MAP NOTE The ECM motor used in a modulating furnace is designed to deliver constant CFM regardless of system static pressure Design system static pressure should never ex...

Page 74: ...perating at 100 heat rate due to the timed staging algorithm then the IFC will continue to run at 100 heat rate for the rest of the heat cycle regardless of the PWM signal applied to the V W2 terminal...

Page 75: ...n ter Heat Blower Off Delay SW17 One dipswitch SW17 is to be provided for heat blower off delay selection SW17 Off 90 second SW17 On 120 second Efficiency or Comfort Select SW18 SW 18 will select betw...

Page 76: ...d be 0 A standard operating code with fault level 0 shall be displayed steady on When displaying a fault code it shall be flashed and not be displayed steady on It shall be flashed on for one second t...

Page 77: ...this fault several times consecutively When the control enters lockout the fault codes 59 Water Sensed and 10 soft lock out will be displayed alternately as described above A D 11 When IFC is in soft...

Page 78: ...fault number but has a lower fault level than the new fault then instead of adding the new fault to the buffer the previous fault and level are replaced with the new fault and level The time stamp wil...

Page 79: ...t most seven segment displays one sec ond on and one second off three times after the fault clear command has been recognized Extended Display Mode If the pushbutton is being pressed during the power...

Page 80: ...en the terminals is determined to be out of range to a low resistance and a valid thermistor value was sensed on the same power cycle a fault 82 is to be displayed on the seven segment displays If the...

Page 81: ...le of communicating with a thermostat and condenser to improve cooling and heat pump airflow displaying active faults and active furnace information at the thermostat and improved diagnostics and trou...

Page 82: ...ommunicating connections Fresh copper must be exposed when making the communicating connections or communications may not be properly established A WIRING OF FULLY COMMUNICATING SYSTEMS Figure 56 is t...

Page 83: ...83 FIGURE 56 WIRING DIAGRAM FOR A FULLY COMMUNICATING SYSTEM ST A1217 01 THERMOSTAT WIRING DIAGRAMS COMMUNICATING INTEGRATED FURNACE CONTROL Integrated Furnace Control...

Page 84: ...ON COMMUNICATING THERMOSTAT AND FURNACE WITH NON COMMUNICATING CONDENSER SINGLE STAGE ONLY CONDENSER B WIRING DIAGRAM SPECIAL CONFIGURATION COMMUNICATING THERMOSTAT AND FURNACE WITH NON COMMUNICATING...

Page 85: ...GURE 55 WIRING DIAGRAM FOR A LEGACY SINGLE STAGE THERMOSTAT WITH AUTOSTAGING SINGLE STAGE THERMOSTAT NON COMMUNICATING TWO STAGE MODULATING GAS FURNACE CONTROL CONDENSER UNIT FIGURE 58 WIRING DIAGRAM...

Page 86: ...AGRAM FOR A LEGACY TWO STAGE THERMOSTAT TWO STAGE THERMOSTAT NON COMMUNICATING TWO STAGE MODULATING GAS FURNACE CONTROL CONDENSER UNIT FIGURE 59 WIRING DIAGRAM FOR A LEGACY TWO STAGE THERMOSTAT ST A11...

Page 87: ...ONLY EcoNet COMMUNICATING THERMOSTAT CONTROL CENTER NON COMMUNICATING OUTDOOR UNIT E1 E2 R C D Y1 B R C Y2 SA1 SA2 OAT1 OAT2 S1 S2 S3 HUM HUM EAC L1 NEUTRAL 1 2 R C HUM STAT W1 W2 G Y1 Y2 B O SA1 SA2...

Page 88: ...QUIRED GURE 58 ING DIAGRAM FOR A LEGACY SINGLE STAGE THERMOSTAT WITH AUTOSTAGING SINGLE STAGE THERMOSTAT NON COMMUNICATING TWO STAGE MODULATING GAS FURNACE CONTROL OUTDOOR UNIT FIGURE 61 WIRING DIAGRA...

Page 89: ...AC and Ground or Common A fault code 30 is displayed at the furnace control when the fuse has been opened ST A1194 93 01 D 1 2 R C HUM STAT W1 W2 G Y1 Y2 B FIGURE 59 WIRING DIAGRAM FOR A LEGACY 2 STAG...

Page 90: ...ING DIAGRAM Below are timing diagram for calibration Table 16 and normal heat sequence Table 16 These diagrams assume no faults are present during the heat call TABLE 16 TIMING DIAGRAM FOR A CALIBRATI...

Page 91: ...91 TIMING DIAGRAM TABLE 17 TIMING DIAGRAM FOR NON CALIBRATION GAS HEAT SEQUENCE Timing Diagram...

Page 92: ...through it to keep from overheating CAUTION DO NOT OPERATE THE SYSTEM FOR EXTENDED PE RIODS WITHOUT FILTERS A PORTION OF THE DUST ENTRAINED IN THE AIR MAY TEMPORARILY LODGE IN THE AIR DUCT RUNS AND A...

Page 93: ...ches IMPORTANT It is recommended that at the beginning of the heating season the condensate neutralizer if used be replaced by a qualified installer service agency or the gas supplier IMPORTANT It is...

Page 94: ...This code indicates that there is a both cooling and dehumidication demand present at the same time When de humidification is active the cooling airflow will be reduced in order to allow water to accu...

Page 95: ...esent or the SOLUTION Remove the model data card and replace with the original memory card from the furnace or the correct replace CAUSE Typically the model data card will be missing from the furnace...

Page 96: ...e This fault will not be displayed to the homeowner on communicating systems unless it occurs at least three times within a single heat call It will not be displayed to the homeowner after the first o...

Page 97: ...purge After both the post purge and blower off delay are complete the fault code 13 is removed and a new attempt at ignition is made Often the new ignition attempt will fail and operation will proceed...

Page 98: ...98 Diagnostics TABLE 19 continued R97V FAULT CODES WITH DESCRIPTIONS AND SOLUTIONS...

Page 99: ...that all gaskets between the inducer and center panel heat exchanger are properly installed and sealed 3 Unstable flame pattern CAUSE 2 Loose or faulty wiring SOLUTION 1 Replace low pressure control s...

Page 100: ...l board inducer relay 5 Loose or faulty wiring 6 Disconnected blocked split or cut pressure switch hoses 45 EXPECTED OPERATION 1 DISPLAYED BEFORE HEAT IS ESTABLISHED The IBM Indoor Blower Motor will n...

Page 101: ...of P4 at the IFC or at the water sensors is not properly made 7 Replace hoses as necessary 8 Insure proper termination and determine if high altitude kit may be necessary see item 4 2 Check the speci...

Page 102: ...f operation should operate as normal CAUSE 1 A blocked condensate drain or the drain trap has become blocked and cannot allow condensate water to flow properly 2 Wiring to the sensors has been damaged...

Page 103: ...ecause the static pressure is too high SOLUTION 1 The static pressure is too high because the ductwork is improperly designed or is restricted for some other reason or the filter needs cleaning or rep...

Page 104: ...is fault is cleared However this fault may also indicate an internal microprocessor failure This may mean that the heat call will not end as expected and that all outputs will be de energized and gas...

Page 105: ...con tacts welded relay and will not clear by cycling the in ducer Fault code 93 is set and displayed This lockout condition cannot be reset by cycling the heat call 3 The furnace control will declare...

Page 106: ...at 75 of capacity If the motor is operating at a good speed it is likely not the motor that is the problem If the motor is not operating verify that the control wiring between the motor and furnace co...

Page 107: ...ate the motor again If the motor continues to fail it may be perma nently damaged and may need to be replaced B Is the motor overheating If so it may report an overheat condition to the furnace contro...

Page 108: ...108 FIGURE 65 MODULATING ECM FURNACE WIRING DIAGRAM Troubleshooting CM 0716...

Reviews: