TURN OFF ELECTRIC POWER AT
THE FUSE BOX OR SERVICE PANEL
BEFORE MAKING ANY
ELECTRICAL CONNECTIONS.

ALSO, THE GROUND CONNECTION
MUST BE COMPLETED BEFORE
MAKING LINE VOLTAGE
CONNECTIONS. FAILURE TO DO
SO CAN RESULT IN ELECTRICAL
SHOCK, SEVERE PERSONAL
INJURY OR DEATH.

IMPORTANT: 

The furnace must be

installed so that the electrical
components are protected from water
due to improper flue installation or
evaporator condensate drain run-off,
etc.

ELECTRICAL CONNECTIONS

THE CABINET MUST BE
PERMANENTLY GROUNDED. A
GROUND SCREW IS PROVIDED IN
THE JUNCTION BOX FOR THIS
PURPOSE. FAILURE TO DO SO CAN
RESULT IN FIRE, ELECTRICAL
SHOCK, PERSONAL INJURY OR
DEATH.

The electrical supply requirements are

listed on the furnace rating plate.
Use a separate fused branch electrical

circuit containing a properly sized fuse

or circuit breaker. Run this circuit

directly from the main switch box to an

electrical disconnect which must be

readily accessible and located within

sight of the furnace. Connect from the

disconnect to the junction box on the

left side of the furnace, inside the

control compartment. See appropriate

wiring diagram.

NOTE: 

The electrical junction box

inside the furnace control compartment

may be relocated to the right side if

necessary. A knockout is provided.

NOTE:

L1 (hot) and neutral polarity

must be observed when making field

connections to the furnace. The

ignition control on electric ignition

models will not sense flame if L1 and

neutral are reversed.
Installation of the electric supply line

should be in accordance with the

National Electric Code ANSI/NFPA No.

70, latest edition, or Canadian

Electrical Code Part 1 - CSA Standard

C22.1 and local building codes.
This can be obtained from:

National Fire Protection Association

Batterymarch Park

Quincy, MA 02269
Canadian Standards Association

178 Rexdale Blvd.

Etobicoke (Toronto), Ontario

Canada  M9W, 1R3

WARNING

!

WARNING

!

ELECTRICAL WIRING

drafts, concealed hot or cold water

pipes, lighting fixtures, radiation from

fireplace, rays of sun, lamps, television,

radios or air streams from registers.

Refer to the instructions packed with

the thermostat for best anticipator

adjustment or selection or see below.

HEAT ANTICIPATOR SETTINGS

For adjusting the thermostat heat

anticipator setting; (a) add the current

draw of the various components in the

system or (b) using jumper wire,

measure the current flow between the

R and W thermostat circuits. Set the

thermostat heat anticipator according

to the current flow measured.

The room thermostat must be

compatible with the integrated furnace

control on the furnace. Generally, all

thermostats that are not of the “current

robbing” type are compatible with the

integrated furnace control used.

NOTE:

An isolation relay (part number

42-25104-01) may assist with “current

robbing” type thermostat compatibility

problems. Use a single-pole, single-

throw relay with a 24-volt AC coil. The

contacts should be rated for .5 amps

minimum at 24 volts. See Figure 17.
Install the room thermostat in

accordance with the instruction sheet

in the box with the thermostat. Run the

thermostat lead wires inside the control

compartment. Connect the thermostat

as shown on the wiring diagram. Never

install the thermostat on an outside

wall or where it will be influenced by

THERMOSTAT

FIGURE 17

ISOLATION RELAY

ST-A0804-01

TABLE 5
FIELD WIRE SIZE FOR 24 VOLT CONTROL CIRCUITS

SOLID COPPER WIRE - AWG

3.0

16

14

12

2.5

16

14

12

2.0

18

16

14

50

100

150

LENGTH OF RUN - FEET 

Wire length equals twice the run distance

NOTE: 

Do not use 24 volt control wiring smaller than No. 18.

T

H

E

R

M

O

S

T

A

T

L

O

A

D

 -

 A

M

P

S

Summary of Contents for GLT series

Page 1: ...92 24161 96 01 SUPERSEDES 92 24161 96 00 INSTALLATION INSTRUCTIONS FOR UPFLOW HORIZONTAL DOWNFLOW INDUCED DRAFT GAS FURNACES WITH ECM X 13 MOTORS GPT UPFLOW HORIZONTAL SERIES GLT DOWNFLOW SERIES...

Page 2: ...el DC microamp A flame signal hot surface ignition units Correct control voltage Measure and set heat anticipator amperage Air conditioning low voltage wires connected to terminals Y C not with wire n...

Page 3: ...cause cancer or birth defects such as fiberglass insulation lead in brass and combustion products from natural gas All new equipment shipped for sale in California will have labels stating that the pr...

Page 4: ...ING THE FURNACE THE RETURN AIR SHALL ALSO BE HANDLED BY DUCT S SEALED TO THE FURNACE CASING AND TERMINATING OUTSIDE THE SPACE CONTAINING THE FURNACE WHEN THIS FURNACE IS INSTALLED IN A RESIDENTIAL GAR...

Page 5: ...ERS OR BOILERS ALL JOINTS SEAMS AND OPENINGS IN THE EQUIPMENT AND DUCT MUST ALSO BE SEALED TO PREVENT DEPRESSURIZATION OF THE SPACE AND POSSIBLE MIGRATION OF COMBUSTION BYPRODUCTS INCLUDING CARBON MON...

Page 6: ...nology and venting requirements are changing awareness of local state and federal codes and industry changes is imperative NOTE Always perform a proper heat loss calculation before specifying the furn...

Page 7: ...OMMENDED THAT AN AUXILIARY DRAIN PAN BE INSTALLED UNDER ALL EVAPORATOR COILS OR UNITS CONTAINING EVAPORATOR COILS THAT ARE LOCATED IN ANY AREA OF A STRUCTURE WHERE DAMAGE TO THE BUILDING OR BUILDING C...

Page 8: ...IGURE 3 UPFLOW HORIZONTAL DIMENSIONS IMPORTANT This furnace is not approved or recommended for installation on its back with access doors facing upwards REDUCED CLEARANCE IN Model A B C D E F Left Rig...

Page 9: ...15 5 8 23 5 8 0 0 0 1 3 6 140 lbs 15 24 1 2 23 11 32 15 5 8 23 5 8 0 0 0 1 3 6 150 lbs TOP BOTTOM 24 1 2 19 3 4 C A B D LOW VOLTAGE GAS CONNECTION ELECTRIC CONNECTION E S A R A 26 5 8 26 13 16 6 3 16...

Page 10: ...filter NOTE DO NOT take return air from bathrooms kitchens furnace rooms garages utility or laundry rooms or cold areas IMPORTANT When using outside air design and adjust the system to maintain a ret...

Page 11: ...indoor coil on the supply air side of the furnace Insure that no air can bypass this coil 3 Connect the supply air plenum to the furnace plenum opening DOWNFLOW UNITS THE DOWNFLOW FURNACE DESIGN IS CE...

Page 12: ...uded from warranty coverage The following types of installation may require OUTDOOR AIR for combustion due to chemical exposures Commercial buildings Buildings with indoor pools Furnaces installed in...

Page 13: ...ined space any space smaller than shown above as unconfined must have openings into the space which are located in accordance with the requirements set forth in the following subsections A and B Size...

Page 14: ...ating for all equipment in the enclosure Here are typical duct sizes B Method 2 One permanent opening located within 12 inches of the top of the enclosure shall be permitted where the equipment has cl...

Page 15: ...at the furnace must be protected from accidental blockage Install a 90 elbow pointing horizontally at the top of inlet air pipe See Figure 11 maximum of 2 45 or 90 elbows allowed NOTE Maximum length o...

Page 16: ...al Fuel Gas Code ANSI Z223 1 and or the Natural Gas Installation Code CSA B149 1 2 for proper installation practices NOTE Follow combustion air instructions as outlined in this manual Single wall vent...

Page 17: ...height above the highest connected equipment draft hood or flue collar 3 Must rise 1 4 per foot away from the furnace on horizontal runs and be supported with straps or hangers so it has no sags or d...

Page 18: ...xhausts so they will operate at maximum speed Do not operate a summer exhaust fan Close fireplace dampers 3 Follow the lighting instructions Place the appliance being inspected into operation Adjust t...

Page 19: ...e Refer to Table 2 for the recom mended pipe size for natural gas and Table 3 for LP gas pipe sizes IMPORTANT It is permissible to run flexible gas connector inside the unit to a piece of black pipe I...

Page 20: ...s pressure of 13 w c ELEVATIONS ABOVE 2000 FT REQUIRE THAT THE FURNACE INPUT RATING BE ADJUSTED AND THAT THE SIZE OF THE BURNER ORIFICES BE RE CALCULATED BASED ON ELEVATION AND GAS HEATING VALUE THE B...

Page 21: ...re at the regulator See Table 3 NOTE Depending on the amount of LP vapor and the outdoor ambient temperature the LP storage tank may require supplemental heat to maintain proper pressure levels Ensure...

Page 22: ...t ratings apply For high altitudes elevations 8 000 and over and for any necessary major changes in the gas flow rate the orifice spud must be changed TO CHANGE ORIFICE SPUDS 1 Shut off the manual mai...

Page 23: ...is can be obtained from National Fire Protection Association Batterymarch Park Quincy MA 02269 Canadian Standards Association 178 Rexdale Blvd Etobicoke Toronto Ontario Canada M9W 1R3 WARNING WARNING...

Page 24: ...DS IMPORTANT ONLY BOTTOM RETURNS CAN BE USED NO MORE THAN TWO FURNACES CAN SHARE THE SAME SUPPLY AND RETURN FURNACES MUST HAVE SAME HEATING AND BLOWER CAPACITY TWINNING FURNACES MUST OPERATE OFF THE S...

Page 25: ...25 FIGURE 19 UT Electronic Controls 1028 930R2 CONTROL BOARD TWINNING CONNECTION SINGLE STAGE OPERATION a099201...

Page 26: ...26 FIGURE 20 UTEC 1028 930R2 CONTROL BOARD TWINNING CONNECTION TWO STAGE OPERATION a099301...

Page 27: ...per thousand ft 47 LP GAS TABLE 7 NOTE Keep any parts removed during LP conversion procedure stored with the product literature for future use LP Gas is a manufactured gas that has consistent heating...

Page 28: ...must be measured onsite with manifold pressure adjustment to ensure that an actual 10 reduction in input rate is achieved Once this field adjustment has been made the label shown in Figure 21 must be...

Page 29: ...8 48 25 000 24 000 23 000 22 000 21 000 20 000 19 000 18 000 17 000 16 000 All calculations are performed by using the first three columns of information only Before beginning any calculations determi...

Page 30: ...h es close the spark igniter energizes The induced draft blower operates for the complete heating cycle 4 After the spark igniter energizes the gas valve opens for a 8 second trial for ignition 5 The...

Page 31: ...is wired for blower speeds required for normal operation as shown If additional blower speed taps are available leads connected to M1 M2 and M3 on the electronic control speeds may be changed if neces...

Page 32: ...asured temperature rise to the approved temperature rise range listed on the furnace name plate See Figure 25 If the measured temperature rise is above the approved range either the air flow is too lo...

Page 33: ...2 1611 760 1572 741 1474 695 1433 676 1319 622 LOW RED 1 840 396 717 338 634 299 545 257 495 233 400 188 MED LO YELLOW 2 992 468 945 446 909 429 831 392 783 369 702 331 MED PURPLE 3 1214 573 1176 555...

Page 34: ...ll out condition the switch will shut the furnace down Switches for the GPT furnaces are located on either side of the burner cover plate and just above the burners on the blower divider panel The GLT...

Page 35: ...1 241 2 125 150 223 4 X 25 153 4 X 25 1 FILTER ROD 45 24095 01 IMPORTANT Do not operate the system for extended periods without filters A portion of the dust entrained in the air may temporarily lodg...

Page 36: ...AE 60520 01 FILTER SUPPORT ANGLE SEE ANGLE DETAIL AE 61883 01 FILTER ROD SUPPORT ANGLE AE 60520 01 FILTER SUPPORT ANGLE AE 61883 01 CUT OUT AND DRILL DETAIL FILTER AND ROD ASSEMBLY ROD FILTER SUPPORT...

Page 37: ...XCHANGER CAN CAUSE TOXIC FUMES TO ENTER THE HOME RESULTING IN CARBON MONOXIDE POISONING OR DEATH THE VENT PIPE OR HEAT EXCHANGER MUST BE REPLACED IF THEY LEAK IMPORTANT It is recommended that at the b...

Page 38: ...Did a limit open during ignition trial If yes go to D Check voltage between HEAT and COMMON on IFC Check wires connections and continuity between IFC and IBM Check IBM capacitor Check IBM CHECK groun...

Page 39: ...39 FIGURE 31 FOR MODELS WITH UT ELECTRONIC CONTROLS 1028 928 INTEGRATED FURNACE CONTROL AND DIRECT SPARK IGNITION...

Page 40: ...CM 0510 40...

Reviews: