29
5.9 ON DEMAND DEHUMIDIFICATION AIRFLOW ADJUSTMENT – ACTIVE
(-)H1V
Use switches 9 & 10 to lower cooling airflow as defined in Figure 29:
IMPORTANT:
Selection A turns off the input of the ODD terminal. DO NOT USE SELEC-
TION A WITH A DEHUMIDIFYING THERMOSTAT OR HUMIDISTAT (refer to Figure 29).
Selection C:
On Demand Dehumidification (See Table 5) – Active
This selection allows On Demand Dehumidification when using a dehumidifying thermo-
stat or humidistat connected to the ODD wire (as shown in Figure 17). Nominal airflow is
reduced by a preprogrammed amount to maximize latent removal.
IMPORTANT:
A humidistat or dehumidifying thermostat MUST be connected to the ODD ter-
minal when using this setting.
NONE
680
1020
1360
1530
OFF
OFF
OFF
ON
24VAC
800
1200
1600
1800
NONE
680
1020
1360
1530
ON
OFF
OFF
ON
24VAC
800
1200
1600
1800
NONE
510
830
1190
1360
OFF
ON
OFF
ON
24VAC
600
1000
1400
1600
NONE
510
830
1190
1360
ON
ON
OFF
ON
24VAC
600
1000
1400
1600
TABLE 5
SELECTION C EXPLANATION: ON DEMAND DEHUMIDIFICATION – ACTIVE (-)H1V
CABINET SIZE/COOLING CAPACITY
SWITCH POSITIONS
FIGURE 29
ON DEMAND DEHUMIDIFICATION AIRFLOW ADJUSTMENT – ACTIVE (-)H1V
O
N
O
N
PASSIVE
9
10
9
10
ACTIVE
SWITCH 9
SWITCH 10
SELECTION
POSITION
POSITION
COOLING AIRFLOW ADJUSTMENT
MAXIMUM LATENT REMOVAL
PASSIVE
OFF
OFF
(WITHOUT ODD INPUT)
ON DEMAND DEHUMIDIFICATION1
ACTIVE
OFF
ON
(WITH ODD INPUT)
TABLE 6
ODD TERMINAL (-)H1V
INDOOR
INPUT TO “ODD”
AMBIENT
TERMINAL
CONDITION
(FROM HUMIDISTAT)
HIGH HUMIDITY
Ø VAC
LOW HUMIDITY
24 VAC
17 / 2.0 & 3.0
21/3.0
Y1 Y2
SWITCH 1
POSITION
SWITCH 2
POSITION
SWITCH 9
POSITION
SWITCH 10
POSITION
ODD
INPUT
17 / 1
1
/
2
& 2.0
Y1 Y2
21 / 3
1
/
2
& 4.0
Y1 Y2
24 / 4.0 & 5.0
Y1 Y2
TABLE 4
SELECTION A EXPLANATION: MAXIMUM LATENT REMOVAL – PASSIVE (-)H1V
SWITCH POSITIONS
SWITCH 1
POSITION
SWITCH 2
POSITION
SWITCH 9
POSITION
SWITCH 10
POSITION
CABINET SIZE/COOLING CAPACITY
CFM
17/
1
1
⁄
2
& 2.0
17/
2.0 & 3.0
21/
3.0
21/
3
1
⁄
2
& 4.0
24/6021S
4.0 & 5.0
OFF
OFF
OFF
OFF
680
1020
1360
1530
ON
OFF
OFF
OFF
680
1020
1360
1530
OFF
ON
OFF
OFF
510
850
1190
1360
ON
ON
OFF
OFF
510
850
1190
1360
6021SR