33
6.2
COMFORT CONTROL
2
SYSTEM™
CONTROL BOARD (-)H2V
The (-)H2V series air handler control, Figure 30, has the following features:
• Memory Card – The memory card stores all information needed for unit operation.
Once the system is wired for the
Comfort Control
2
,
this information is shared with the
thermostat and outdoor unit. This
shared
data is available if one of the components in
the system needs to be replaced.
• An automotive-style ATC blade fuse for transformer protection (3 amp).
• An on-board LED to indicate blower CFM.
• An RJ-11 port for use with a diagnostic tool.
• Inputs for field installed supply and return air temperature sensors (available in kit
RXHT-A01)
• DIP switches for airflow adjustments
IMPORTANT:
The DIP switches are NOT used when the air handler is wired for the
Comfort Control
2
. Airflow adjustments are performed via the thermostat or a diagnostic
tool.
Installation Verification
• Term and bias dip switches should be on.
• 24V AC power on R&C must be present at the control for the air handler to operate,
reference Figure 31.
• Line voltage must be present at the control for indoor blower operation.
• The RX Data LED will flash green in normal operation. A flashing green light indicates
24VAC is present and the data wires 1 and 2 are wired properly.
IMPORTANT:
If the RX DATA LED is solid green, data wire 1 and data wire 2 are not
properly connected. Typically, the connections are switched, i.e. data wire 1 is wired to
the data wire 2 connection and data wire 2 is wired to the data wire 1 connection.
Verify wiring and correct the polarity at the two data wires.
IMPORTANT:
Diagnostic port is not a phone jack. Connecting to a telephone or tele-
phone system will result in damage.
IMPORTANT:
Diagnostic port is for diagnostic tool only. Do not attempt to connect
components using a telephone cord. Damage will occur.
6.3 USING THE ON-BOARD LED TO DETERMINE BLOWER CFM (-)H2V
The CFM LED indicates blower output by flashing one (1) flash for every 100 CFM of air-
flow. The LED will pause 1/10 second between each flash. (See Table 1.)
6.4 AIRFLOW ADJUSTMENTS WITH THE
COMFORT CONTROL
2
SYSTEM™
(-)H2V
The RHPN air handler
Comfort Control
2
System™
may operate using the
Comfort
Control
2
or via traditional thermostat wiring. When the air handler is wired for the
Comfort Control
2
using Data wire 1 and Data wire 2, the DIP switches on the
Comfort
Control
2
control have NO affect on the airflow.
IMPORTANT:
When using the
Comfort Control
2
, the DIP switches have no affect on
airflow or on air handler performance.
FIGURE 31
TYPICAL
COMFORT CONTROL
2
SYSTEM™
WIRING DIAGRAM
Indoor Unit
1
2
C
R
WIRING INFORMATION
Line Voltage
–Field Installed - - - - - -
–Factory Standard
1
2
R
C
1
2
R
C
Communicating Thermostat
Outdoor Unit
C
O
N
V
E
N
T
IO
N
A
L
T
H
E
R
M
O
S
T
A
T
W
IR
IN
G
Summary of Contents for RH1V2417STANJA
Page 54: ...54 FIGURE 44 COMFORT CONTROL2 SYSTEM AIR HANDLER WIRING DIAGRAM H2V...
Page 55: ...55...
Page 56: ...56 CM 0115...