background image

49

• Loosen the bolt holding the wire motor band around the motor shell and pull the

motor from the motor mount. Note the motor position in the mount for re-assembly.

• To re-assemble, insert the motor shaft through the hub in the blower wheel and orient

the motor to original position.

• For proper motor cooling, it is important that the motor be mounted the same as the

original, as far into the blower as practical.

• The dimension from the face of the motor end plate (shaft end) to the first wire on the

motor mount band around the shell should be:

DIMENSION

TONNAGE

CABINET SIZE

1

3

/

32

"

1

1

/

2

& 2

17

1

1

/

2

"

2

1

/

2

& 3

17

2

1

/

2

"

3, 3

1

/

2

& 4

21

2

7

/

8

"

5

24

• With motor held to above position and motor lead plugs oriented to the original posi-

tion (the wire connectors on the motor must point straight to the supply air end of the
unit and away from the return air [filter] end of the unit). Securely tighten the bolt on
the mount band to the motor shell.

• Turn the motor shaft so that the flat on the shaft is located under blower wheel

setscrew, and the blower wheel is centered in the blower housing with the same dis-
tance on each side between the inlet venturi and the outside of the blower wheel.

• Re-assemble the motor wiring (high and low voltage plugs) into the motor.

IMPORTANT: 

DO NOT FORCE POWER PLUG INTO THE MOTOR CONNECTOR

BACKWARDS. The A.C. power plug to the motor has locking tabs. It has been
proven that by applying excessive force to the A.C. cable half of the connector it is
possible to force the connector in backwards. It will not seat and “click” properly but
will make connection. If A.C. power is applied with the connector reversed the motor
will be immediately destroyed. 

13.8 ECM CONTROL MODULE REPLACEMENT

Always take the following steps before replacing the control module on the end of the
ECM indoor blower motor.

1. 

HAVE THE CORRECT REPLACEMENT MODULE.

These controls are factory pro-

grammed for specific operating modes. Even though they look alike, different mod-
ules may have different CFM characteristics.

IMPORTANT: 

Using the wrong control module voids all product warranties and may pro-

duce unexpected results.

2. Turn off power to the equipment. Wait at least 5 minutes after disconnecting AC

power before opening the motor. 

FIGURE 39

INTERNAL MOTOR PLUG AND SOCKET

Summary of Contents for RH1V2417STANJA

Page 1: ...instructions are intended as an aid to qualified licensed service personnel for proper installation adjustment and operation of this unit Read these instructions thoroughly before attempting installa...

Page 2: ...low Performance Data 32 6 2 Copper Wire Size Awg 3 Voltage Drop 33 6 3 Blower Motor Electrical Data H2v 33 6 4 Electric Heat Electrical Data 33 6 5 Cooling Airflow Settings 34 6 6 Cooling Airflow Adju...

Page 3: ...ll joints seams and openings in the equipment and duct must also be sealed to prevent depressurization of the space and possible migration of combustion byproducts including carbon monoxide into the l...

Page 4: ...intained WARNING SEE SECTION 8 0 DUCTWORK Do not under any circumstances connect return ductwork to any other heat pro ducing device such as fireplace insert stove etc Unauthorized use of such devices...

Page 5: ...unconditioned space This can result in property damage NOTICE Improper installation or installation not made in accordance with the Underwriters Laboratory UL certification or these instructions can...

Page 6: ...re field installed items 4 The air handlers do not have an internal filter rack An external filter rack or other means of filtration is required 2 2 MODEL NUMBER EXPLANATION SEE FIGURE 2 AVAILABLE MOD...

Page 7: ...MATCHED TO OUTDOOR UNIT1 ODD ODD Normal Normal 1ST STAGE 2ND STAGE UNIT WITH COIL MAX kW NOMINAL COIL AIRFLOW L s UNIT WEIGHT SHIPPING WEIGHT LBS kg 2421HT 21 533 421 2 1080 191 2 495 ARL ASL 024JEC...

Page 8: ...ants such as dirt dust fumes and odors into the home causing property damage Fumes and odors from toxic volatile or flammable chemicals as well as automobile exhaust and carbon monoxide CO can be draw...

Page 9: ...ice These units may be installed in either ventilated or nonventilated spaces 3 0 APPLICATIONS 3 1 ZONING SYSTEMS The manufacturer does not currently provide or support zoning However zoning systems c...

Page 10: ...and the National Electric Code for horizontal right application the circuit breaker s on field installed electric heater kits must be re installed per procedure below so that the breaker switch on po...

Page 11: ...is loop Rotate unit into the downflow position with the coil compartment on top and the blower com partment on bottom The set of coil rails must be moved for vertical down flow and horizontal right ap...

Page 12: ...can be wrapped with insulation This can be done as long as the unit is completely enclosed in insulation sealed and service access is provided to prevent accumulation of moisture inside the insulation...

Page 13: ...ric Heater is installed units may be equipped with one two or three 60 amp circuit breakers These breaker s protect the internal wiring in the event of a short circuit and serve as a disconnect Circui...

Page 14: ...after installation separation of control wiring and power wiring has been maintained FIELD WIRE SIZE FOR 24 VOLT THERMOSTAT CIRCUITS Thermostat Load Amps 3 0 2 5 2 0 16 16 18 50 14 14 16 100 12 12 14...

Page 15: ...WITH ELECTRIC HEAT AND USING A HUMIDISTAT FOR DEHUMIDIFICATION B W2 G Y W1 B ODD C R Air Handler Y G W2 E Heat PumpThermostat Heat Pump Outdoor Unit Y B Humidistat C R R D C Y2 Field Installed Line V...

Page 16: ...Unit Y2 C R Y2 Field Installed Line Voltage WIRING INFORMATION Factory Standard ODD R Y1 Y2 G W2 R Y1 C L Y Y BL R BR W R DHM L W1 FIGURE 18 2 STAGE CONDENSING UNIT WITH ELECTRIC HEAT USING A TWO STA...

Page 17: ...W1 G BK W BK BL G Y BR R Y2 Y BL FIGURE 21 TYPICAL SINGLE STAGE THERMOSTAT SINGLE STAGE STRAIGHT COOLING WITH ELECTRIC HEAT 2ND STAGE AIR FLOW G W2 C R Single Stage A CThermostat A C Outdoor Unit C Y...

Page 18: ...nit must be permanently grounded Failure to do so can result in electri cal shock causing personal injury or death 4 6 BLOWER MOTOR ELECTRICAL DATA H1V MAXIMUM CIRCUIT PROTECTOR MINIMUM CIRCUIT AMPACI...

Page 19: ...jumpered together to energize all the electric heat when a call for electric heat is received if warmer supply air is desired NOTE When using 24VAC thermostat control wiring the serial communicating c...

Page 20: ...8 1 60 1 4 8 SINGLE 17 3 20 0 4 0 27 30 30 30 RXBH 1724 07J 5 4 7 2 1 60 2 3 6 SINGLE 26 0 30 0 4 0 38 43 40 45 RXBH 1724 10J 7 2 9 6 1 60 2 4 8 SINGLE 34 6 40 0 4 0 49 55 50 60 10 8 14 4 1 60 3 4 8...

Page 21: ...3 2 SINGLE 40 0 46 2 4 4 56 64 60 70 RXBH 24A20C 7 2 9 6 3 60 3 3 2 MULTIPLE CKT 1 20 0 23 1 4 4 31 35 35 35 7 2 9 6 3 60 3 3 2 MULTIPLE CKT 2 20 0 23 1 0 25 29 25 30 RXBH 24A25C 18 0 24 0 3 60 6 4 0...

Page 22: ...0 8 35 4 4 9 45 60 45 51 MULTI CKT 2 208 240 1 60 6 4 8 5 30 8 35 4 0 40 45 39 45 Single 208 240 1 60 14 4 19 2 69 2 80 0 4 9 100 110 93 107 RXBH 24A20J MULTI CKT 1 208 240 1 60 7 2 9 6 34 6 40 0 4 9...

Page 23: ...ng where the breakers apply has been UL approved for short circuit protection Ampacity not breaker size determines supply circuit wire size The ampacity listed on the unit rating plate and the Maximum...

Page 24: ...to 1 0 W C The interface board pro vides the required communications between the thermostat and the ECM blower motor The H1V series of air handlers feature An automotive style ATC blade fuse for trans...

Page 25: ...SEE FIGURE 25 The H1V series of air handlers allow a wide range of airflow settings for cooling and heat pump operation These airflow settings are selected via DIP switches 1 and 2 on the interface b...

Page 26: ...switches 5 and 6 control electric heat air flow levels on H1V air handlers FIGURE 26 COOLING AIRFLOW ADJUSTMENTS H1V COOLING SELECTION SWITCH 3 SWITCH 4 AIRFLOW POSITION POSITION ADJUSTMENT A OFF OFF...

Page 27: ...e and airflow through the duct system TABLE 3 H1V S8 S7 S7 S8 On On Off On Off Ramp Times CFMReduction 5 minutes 18 Less 5 to 12 5 minutes 12 Less after 12 5 minutes 100 Full Operating Sequence Pre pr...

Page 28: ...dehu midification in the cooling mode that is controlled by the user s dehumidifying thermostat or humidistat setting When the humidity exceeds the humidistat setting the airflow is decreased by a pre...

Page 29: ...24VAC 600 1000 1400 1600 TABLE 5 SELECTION C EXPLANATION ON DEMAND DEHUMIDIFICATION ACTIVE H1V CABINET SIZE COOLING CAPACITY SWITCH POSITIONS FIGURE 29 ON DEMAND DEHUMIDIFICATION AIRFLOW ADJUSTMENT A...

Page 30: ...1202 1200 1197 1180 RPM 664 740 805 868 926 982 1031 1087 1138 1196 Watts 163 191 226 239 261 292 322 373 420 472 CFM 1000 1001 1011 1009 1005 1000 996 994 970 967 RPM 593 650 737 801 867 914 980 102...

Page 31: ...s 246 325 369 401 459 495 532 572 509 652 CFM 1794 1808 1808 1808 1807 1807 1807 1800 1786 1772 RPM 676 739 787 840 871 923 950 994 1028 1050 Watts 330 376 416 465 504 554 576 624 662 694 CFM 1756 177...

Page 32: ...mmunicating control will assume the control is being used with a traditional thermostat and will IGNORE ANY COMMUNICATIONS USING DATA WIRE 1 AND DATA WIRE 2 IMPORTANT Class 2 low voltage control wire...

Page 33: ...TANT If the RX DATA LED is solid green data wire 1 and data wire 2 are not properly connected Typically the connections are switched i e data wire 1 is wired to the data wire 2 connection and data wir...

Page 34: ...eration only They are ignored when in heating mode or when electric heat is activated 6 7 ELECTRIC HEAT AIRFLOW H2V The H2V series of air handlers are factory programmed to provide adequate airflow fo...

Page 35: ...to bring the blower up to 50 airflow for 30 seconds before advancing to 100 airflow This minimizes air flow sounds at system startup Profile C Humid Climate Profile The humid profile is configured to...

Page 36: ...e stage condensing units Refer to the Engineering Specifications Sheets to determine the required airflow for your particular combination Refer to Table 5 to determine the air flows available for each...

Page 37: ...AIRFLOW The RHPN series air handlers are shipped with the Low KW airflow feature turned OFF Activate lower airflow feature for lower KW electric heat applications by turning DIP switch 8 ON IMPORTANT...

Page 38: ...for cooling operation only They are ignored when the heat pump is in heating mode or when electric heat is activated 6 16 COOLING DELAY PROFILES H2V Cooling delay profiles are not available when the H...

Page 39: ...1044 289 334 377 417 456 493 529 562 593 623 1050 1050 1075 1075 1050 1025 1025 1025 1025 1000 525 575 625 675 750 800 825 875 925 975 100 125 150 175 225 250 275 300 325 350 1625 1625 1650 1675 1675...

Page 40: ...ce T d8 Old Shared Data System data is obsolete If system will not operate order new memory card to update system information T T T T 68 ECM No Signal The ECM motor is not communicating to the air han...

Page 41: ...MPORTANT Flanges around blower opening for attaching supply duct must be up out of blower discharge even if not used so they do not restrict airflow from blower IMPORTANT If an elbow is included in th...

Page 42: ...om being damaged by torch flames After the refrigerant connections are made seal the gap around the connections with pressure sensitive gasket If necessary cut the gasket into two pieces for a better...

Page 43: ...nsulated where necessary to prevent sweating and damage due to condensate forming on the outside surface of the line Make provisions for disconnecting and cleaning of the primary drain line should it...

Page 44: ...B energizes the reversing valve RV switching it to the heating position remains energized as long as system switch is in heat position Circuit R and Y energizes the contactor CC starting the outdoor f...

Page 45: ...when the fan switch is in the auto position 10 6 ROOM THERMOSTAT ANTICIPATOR SETTING See instructions with outdoor section condensing unit or heat pump for recommended room thermostats On units with...

Page 46: ...ead all WARNINGS listed in these installation instructions PRE START CHECKLIST Is unit properly located level secure and service able Has auxiliary pan been provided under the unit with separate drain...

Page 47: ...able in Section 5 20 NOTE The memory card is attached to the control box with a tether The tether has an identification label that can be used to identify the memory card if replacement is need ed IMP...

Page 48: ...blower deck Make sure blower assembly engages lances in deck properly If assembly hangs up check to make sure top and bottom are lined up in proper locations Slide blower assembly to back of cabinet...

Page 49: ...r wheel is centered in the blower housing with the same dis tance on each side between the inlet venturi and the outside of the blower wheel Re assemble the motor wiring high and low voltage plugs int...

Page 50: ...or and carefully insert the plug that was removed in step 5 BE SURE THE PLUG LATCHES IT SHOULD CLICK INTO PLACE 8 Install the new control module back on the motor Carefully engage the alignment pin in...

Page 51: ...ugh discharge opening in the blower housing Hold blower wrap down into position and replace two screws holding blower wrap to blower sides See motor replacement and blower assembly instructions for re...

Page 52: ...re 42 Model Cabinet Size Filter Size Part Number A B 17 16 x 20 406 x 508 RXHF 17 15 70 17 50 21 20 x 20 508 x 508 RXHF 21 19 20 21 00 24 25 x 20 635 x 508 RXHF 24 22 70 25 50 Accommodate 1 or 2 filte...

Page 53: ...RXBM Coil Model Horizontal Adapter Kit Horizontal Adapter Kit Model Number Single Qty Model Number 10 pak Qty 2414 RXHH A01 RXHH A01x10 2417 RXHH A02 RXHH A02x10 3617 3621 RXHH A03 RXHH A03x10 3821 4...

Page 54: ...54 FIGURE 44 COMFORT CONTROL2 SYSTEM AIR HANDLER WIRING DIAGRAM H2V...

Page 55: ...55...

Page 56: ...56 CM 0115...

Reviews: