6.2 240V AIRFLOW PERFORMANCE DATA – RHAL (PSC MOTOR)
Nominal
Cooling
Capacity
Tons
Manufacturer
Recommended
Air-Flow Range
(Max/Min) CFM
Blower Size/
Motor HP #
of Speeds
Motor
Speed
From
Factory
Motor
Speed
PSC Motor
CFM wet coil with filter & heaters
External Static Pressure-Inches W.C.
0.10
0.20
0.30
0.40
0.50
0.60
0.70
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
850
807
763
723
644
568
538
948
970
989
1003
1021
1037
1046
269
262
252
245
238
226
221
642
606
575
521
450
—
—
766
798
817
864
912
—
—
175
170
168
158
149
—
—
1016
966
927
885
834
780
718
1083
1090
1096
1101
1109
1114
1121
380
365
360
349
338
328
311
830
805
772
735
690
—
—
932
950
974
994
1014
—
—
270
262
253
244
235
—
—
1190
1116
1058
997
927
851
762
900
927
950
974
997
1018
1038
374
361
346
331
320
307
290
1034
983
931
868
808
—
—
836
860
892
921
944
—
—
300
291
281
269
260
—
—
1330
1262
1184
1066
968
871
—
1029
1047
1060
1082
1095
1104
—
478
456
437
403
376
355
—
1189
1135
1054
976
—
—
—
958
984
1012
1037
—
—
—
402
385
362
341
—
—
—
1.5
850/450
8 kW max
10X6 1/5 hp
2 speed
dual voltage
High
High
Low
2
1016/690
10 kW max
10X6 1/5 hp
2 speed
dual voltage
High
2.5
1190/808
10 kW max
10X8T 1/4 hp
2 speed
dual voltage
High
High
Low
High
Low
3
1330/976
10 kW max
10X8T 1/3 hp
2 speed
dual voltage
High
High
Low
NOTE:
• All 208/240V PSC motors have voltage taps for 208 and 240 volts.
• All 208/240V PSC motors have shipped on high speed and 240 volts.
• If the application external static is less than 0.5” WC, adjust the motor speed to the low static speed as described below.
– Unplug the black motor wire off the relay on the control board and plug in the red motor wire.
– Replace the cap on the black motor wire.
• Voltage change (208/240V motors):
– Move the orange lead to transformer 208V tap. Replace the wire cap on 240V tap.
– Unplug the purple motor wire off the transformer and plug in the yellow motor wire.
– Replace the cap on the purple motor wire.
• The above airflow table lists the airflow information for air handlers with maximum heater allowed for each mode.
17