32
B - SETTINGS
DIP 1 (ON) - MOTOR ROTATION DIRECTION CONTROL (POINT C)
DIP 2 (ON) - TIMER (POINT D)
DIP 3
(ON) - ACTIVATES DOOR RELEASE DURING PHASES OF SLOWDOWN AND
TOTAL OPENING AND CLOSING (AS PER THE IMPACT TESTS OF EN12453)
DIP 1-2
MEMORIZATION/CANCELLATION OF RADIO CONTROL CODES FOR TOTAL
OPENING (ONLY MODEL CRX) (POINT E)
DIP 1-3
MEMORIZATION/CANCELLATION OF RADIO CONTROL CODES FOR
PEDESTRIAN OPENING (ONLY MODEL CRX) (POINT F)
DIP 2-1
MICRO-SWITCH CONTROLLER FOR PEDESTRIAN OPENING TIMER
DIP 4
Photocells always active (OFF) - Photocells active only during closing (ON)
DIP 5
Pre-blinking (ON) - Normal blinking (OFF)
DIP 6
Single pulse command (K BUTT) and step-by-step radio receiver (OFF) - automatic
(ON)
DIP 7
Power sensor operation (ON-activated) time operation (OFF-activated).
DIP 8
Electric lock activation (ON-activated)
DIP 9
Electric lock pulse release (ON-activated)
DIP 10
Electric lock pulse engagement (ON-activated)
DIP 11
Easy release activation (ON-activated)
DIP 12
Sensor TEST activation (ON-activated).
DIP 13
Selection of 1 or 2 motor operation (default OFF 2 motors)
DIP 14
DIP 15
IMPACT SENSOR SENSIBILITY (ACTIVE IF DIP 7 ON)
OFF
OFF
HIGH
ON
OFF
MEDIUM HIGH
OFF
ON
MEDIUM LOW
ON
ON
LOW
DIP 16
IMMEDIATE CLOSING AFTER PASSING IN FRONT OF PHOTOCELLS
ON ACTIVATED
OFF DEACTIVATED
JP1 =>
Check that the jumper is inserted!
JP2 =>
Check that the jumper is inserted!
JP3 =>
Check that the jumper is inserted!
PROG =>
S3 Programming button
ADJUSTMENTS
ATTENTION: PUT DIP 3 IN THE ON MODE ONLY AFTER HAVING CARRIED OUT ALL
THE PROGRAMMING PROCEDURES.
NOTE: WITH DIP 3 (ON) BRIEF GATE REVERSAL AFTER IMPACT IS ACTIVATED.
THIS BRIEF GATE REVERSAL PERMITS STATIC FORCE TO BE REDUCED TO ZERO
WITHIN 5 SECONDS AS PER STANDARD EN12453 POINT A.2.2 (ACCEPTABLE
STATIC FORCE), THEREBY COMPLYING WITH THE IMPACT TESTS ALSO OUTLINED
G
B
J1
N F
Power supply 230 Vac 50/60 Hz - external to the control
panel - (120V/60Hz upon request)
J2
COM
Common contact
CLOSE
Closing impulse contact (NA)
OPEN
Opening impulse contact (NA)
STOP
STOP impulse contact (NC)
AERIAL
Radio Antenna
J3
SIGNAL
Gate open state and battery state output indicator (24Vdc 3W
max)
A+TEST
+ 24Vdc safety strip self-test power supply
EDGE N.C.
Safety strip contact (NC)
COM.
Common contact
PHOTO N.C.
Photocells contact (NC)
K BUTT.
Single pulse contact (NO)
PED. BUTT.
Pedestrian opening contact (NA)
A+
+ 24Vdc accessories power supply
A -
- 24Vdc accessories power supply
LOCK
Electric lock connection (MAX 15W 12V)
- 24Vdc blinker (code ACG7061) power supply. Pay attention
to the polarity.
J4
SECONDARY
TRANSFORMER
Connection to secondary coil of transformer 18 Vac
J5
MOTOR 1
MOTOR 1 CONNECTION (without polarity)
J6
MOTOR 2
MOTOR 2 CONNECTION (without polarity)
J7
SW T2 PREMIER
24V
Connector dedicated to the factory programming. DO NOT
REMOVE ANY JUMPER! OTHERWISE THE OPERATOR WILL
NOT WORK!
J8
SW RADIO
Connector dedicated to the factory programming (only CRX
control board) DO NOT REMOVE ANY JUMPER! OTHERWISE
THE OPERATOR WILL NOT WORK!
J9
RADIO
Built-in radio module (model CRX), or connector for radio
receiver RIB, 24 Vdc supply
J10
BATTERY
CHARGER
Connector for charge card of 24Vdc battery (code ACG4648)
TR1
TRIMMER RUN
Trimmer for high speed adjustment operations
TR2
TRIMMER LOW
SPEED
Trimmer for low speed adjustment operations
TR3
TRIMMER TCA
Trimmer for automatic closing time adjustment (DISABLED
DEFAULT AND DL6 LED OFF)
S3
PROG
Programming button
FUSE 1 T 8 A
Motor protection fuse
F1
T 2 A
Transformer protection fuse
A - CONTROL PANEL FEATURES
J3
TR2
TR1
J2
J4
F1
FUSE 1
J5
J6
TR3
J10
J8
J9
J1
J7
S3
TRANSFORMER