33
B - SETTINGS
DIP 1
(ON) - MOTOR ROTATION DIRECTION CONTROL (POINT C)
DIP 2
(ON) - TIMER (POINT D)
DIP 3
(ON) - ACTIVATES DOOR RELEASE DURING PHASES OF SLOWDOWN AND
TOTAL OPENING AND CLOSING (AS PER THE IMPACT TESTS OF EN12453)
DIP 1-2
MEMORIZATION/CANCELLATION OF RADIO CONTROL CODES FOR TOTAL
OPENING (ONLY MODEL CRX) (POINT E)
DIP 1-3
MEMORIZATION/CANCELLATION OF RADIO CONTROL CODES FOR
PEDESTRIAN OPENING (ONLY MODEL CRX) (POINT F)
DIP 2-1
MICRO-SWITCH CONTROLLER FOR PEDESTRIAN OPENING TIMER
DIP 4
Photocells always active (OFF) - Photocells active only during closing (ON)
DIP 5
Pre-blinking (ON) - Normal blinking (OFF)
DIP 6
Single pulse command (K BUTT) and step-by-step radio receiver (OFF) - automatic
(ON)
DIP 7
Power sensor operation (ON-activated) time operation (OFF-activated).
DIP 8
Electric lock activation (ON-activated)
DIP 9
Electric lock pulse release (ON-activated)
DIP 10
Electric lock pulse engagement (ON-activated)
DIP 11
Easy release activation (ON-activated)
DIP 12
Sensor TEST activation (ON-activated).
DIP 13
Selection of 1 or 2 motor operation (default OFF 2 motors)
DIP 14
KING 24 - ON
DIP 15
KING 24 - OFF
DIP 16
IMMEDIATE CLOSING AFTER PASSING IN FRONT OF PHOTOCELLS
ON ACTIVATED
OFF DEACTIVATED
JP1 =>
Check that the jumper is inserted!
JP2 =>
Check that the jumper is inserted!
JP3 =>
Check that the jumper is inserted!
PROG =>
S3 Programming button
ADJUSTMENTS
ATTENTION: PUT DIP 3 IN THE ON MODE ONLY AFTER HAVING CARRIED OUT ALL THE
PROGRAMMING PROCEDURES.
NOTE: WITH DIP 3 (ON) BRIEF GATE REVERSAL AFTER IMPACT IS ACTIVATED.
THIS BRIEF GATE REVERSAL PERMITS STATIC FORCE TO BE REDUCED TO ZERO
WITHIN 5 SECONDS AS PER STANDARD EN12453 POINT A.2.2 (ACCEPTABLE STATIC
FORCE), THEREBY COMPLYING WITH THE IMPACT TESTS ALSO OUTLINED BY
EN12453).
IF COMPLIANCE WITH THE AFOREMENTIONED STANDARD IS UNNECESSARY, SIMPLY
POSITION DIP 3 TO OFF. IN THIS CASE THE GATES STOP WITHOUT REVERSING.
RUN TRIMMER (TR1) high-speed electronic regulator
This trimmer permits motor speed adjustment (the default setting is maximum speed).
Adjustment of the automation is useful for compliance with European impact standards.
LOW-SPEED TRIMMER (TR2) Electronic slow speed approach control
The slow speed control is performed by adjusting the LOW- SPEED TRIMMER which changes
the voltage output across the motor(s) (turning it clockwise increases the speed). Adjustment
is performed to determine the correct speed at the end of opening and closing according to
the gate or when there is friction that might cause the system to function poorly.
AUTOMATIC CLOSING TRIMMER - TCA (TR3) TOTAL OR PEDESTRIAN default NOT
ACTIVATED and LED DL6 OFF (TRIMMER FULLY ROTATED COUNTERCLOCKWISE)
This trimmer makes it possible to adjust the time for total or pedestrian automatic closing.
Only with gate completely (total) or partially (pedestrian) open and LED DL6 on (trimmer
rotated clockwise).
The pause time can be adjusted from a minimum of two seconds up to a maximum of two
minutes.
LED SIGNALS
DL1 program activated (red)
DL2 gate opening M2 (green)
DL3 gate closing M2 (red)
DL4 gate opening M1 (green)
DL5 gate closing M1 (red)
DL6 automatic closing indicator (red)
DL7 photocell contact (NC) (red)
DL8 sensor contact (NC) (red)
DL9 STOP button (NC) (red)
DL10 radio code program (green)
FUSES
Fuse 1 T 8A
MOTOR PROTECTION FUSE
F1 T 2A
TRANSFORMER PROTECTION FUSE (on the outside of the T2 24V board)
C - MOTOR ROTATIONAL DIRECTION CONTROL
1 - Set DIP 1 to ON => LED DL1 starts flashing.
2 - Press and hold the PROG button. (movement is now manually controlled - open-stop-
close-stop-open - etc.) => GREEN LEDS DL2 and DL4 are lit and the gate panels open
with a fixed lag of 2 sec. If they close instead of open, release the button and reverse the
two wires on the motor used.
3 - After opening release the PROG button and calibrate the mechanical opening stops (on
the operator).
4 - Press and hold the PROG button => RED LEDs DL3 and DL5 turn on and the gate panels
close with a time lag of 2 sec.
5 - Continue to hold the PROG button until the gate is completely closed.
6 - Leave the two doors completely closed to set the timer.
7 - Reset DIP1 to OFF => LED DL1 turns off, signaling exit from control.
N.B.: During this check the stop, the photocells and the sensors are not active.
D - SETTING THE TIMER FOR 2 MOTORS (#) WITH POWER SENSOR
ACTIVATED (DIP 7 ON)
WHILE SETTING THE TIMER THE POWER SENSOR IS CONTINUOUSLY ACTIVATED.
1 - The gate must be completely closed.
2 - Set DIP 2 to ON => LED DL1 will blink rapidly.
3 - Press the PROG button. => M1 opens.
4 - When the mechanical opening stop is reached, the AUTOMATIC POWER SENSOR stops
M1 (memorizing the time and the power) => At the same time M2 is triggered to open.
5 - When the mechanical opening stop is reached, the AUTOMATIC POWER SENSOR stops
M2 (memorizing the time and the power).
6 - Press the PROG button. => M2 closes.
7 - Press the PROG button. => M1 closes and sets the lag time between M2 and M1. At
the same time LED DL1 stops flashing indicating exit from the programming procedure.
Safety and other gate commands now operate normally (inversions, stop, alarms, etc.).
8 - The gate panels will close in high-speed mode (depending on how you set the RUN
trimmer) and near total closure in the slow mode (depending on how you set the LOW-
SPEED trimmer).
9 - Upon closing the power sensors stop the gate.
10 - AFTER PROGRAMMING RESET DIP 2 TO OFF.
D - SETTING THE TIME FOR ONE MOTOR (M1) (#) WITH POWER
SENSOR ACTIVATED (DIP 7 ON)
CAUTION: FOR ONE MOTOR CONTROL DIP 13 MUST BE POSITIONED TO ON; DURING
PROGRAMMING THE POWER SENSOR IS CONTINUOUSLY ACTIVE.
The gate must be completely closed.
1 - Set DIP 2 to ON => LED DL1 will blink rapidly.
2 - Press the PROG button. => M1 opens.
When the mechanical opening stop is reached, the AUTOMATIC POWER SENSOR stops
M1 (memorizing the time and the power).
3 - Press the PROG button. => M1 closes.
At the same time LED DL1 stops flashing indicating exit from programming. Safety and
other gate commands now operate normally (inversions, stop, alarms, etc.).
Upon closing the power sensor stops the gate.
4 -
AFTER PROGRAMMING RESET DIP 2 TO OFF.
(#) DURING PROGRAMMING THE SAFETY DEVICES ARE ACTIVE AND STOP THE
PROGRAMMING PROCEDURE (LED DL1 FROM FLASHING BECOMES CONSTANT).
TO REPEAT PROGRAMMING SET DIP 2 TO OFF, CLOSE THE GATE USING THE
PROCEDURE “MOTOR ROTATIONAL DIRECTION CONTROL” AND REPEAT THE
DESIRED PROGRAMMING PROCEDURE.
G
B