CLOCK FUNCTION APPLICATION
It is necessary to request a T2 24V control panel with firmware 02.

By connecting a switch and/or a daily/weekly clock (instead of or in parallel to the open 
button N.O. “COM-OPEN”), you can open and keep the automation open for as long as the 
switch is pressed or the clock remains active. Command functions are inoperative with open 
automation.
Releasing the switch or at the preset time, the automation closes immediately.

CLOSE BUTTON (COM-CLOSE)

Controls the closing movement when the gate is stationary.

REMOTE CONTROL
If DIP 6 OFF =>

   It cyclically performs the commands open-stop-close-stop-open etc.

If DIP 6 ON =>

   Opens the gate when closed. There is no effect if activated while opening. 

If activated when gate is open, the gate closes. If activated while closing, 
the gate reopens.

PEDESTRIAN OPEN BUTTON (COM-PED.BUTT.)

Partial opening and closing control.
During pedestrian opening, pausing or closing, you can control the opening of any command 
linked to the T2 24V board.
With DIP 6 you can choose the operation mode of the pedestrian push button.

If DIP 6 OFF =>

   It cyclically performs the commands open-stop-close-stop-open etc.

If DIP 6 ON =>

   Opens the gate when closed. There is no effect if activated while opening. 

If activated when gate is open, the gate closes. If activated while closing, 
the gate reopens.

 

ELECTRIC LOCK (LOCK)

Set DIP 8 to ON to enable control of the electric lock when opening.

ELECTRIC LOCK PULSE RELEASE IN OPENING

Set DIP 9 to ON to enable the electric lock pulse release when opening (provided DIP 8 is ON).
If a command to open the gate is given when the gate is closed, the closing movement is 
performed for 0.5 seconds and the electric lock is simultaneously activated (followed by a 0.5 
second pause and then the opening of the gate).

ELECTRIC LOCK PULSE ENGAGEMENT

Set DIP 10 to ON to enable the pulse engagement of the electric lock when closing. Upon 
closing, motors are activated for 0.5 seconds at full voltage to ensure lock engagement. 

EASY MOTOR RELEASE

Set DIP 11 to ON to enable easy manual release (provided that DIP 10 is ON), upon closing a 
reverse motion with a fixed time of 0.2 seconds occurs to facilitate manual release.

OPERATION OF SAFETY ACCESSORIES

PHOTOCELL (COM-PHOT)
DIP 4 OFF =>   

if an obstacle is placed in range of the photocells when the gate is closed, 
the gate does not open. During operation, photocells work when opening 
(by starting the opening movement only after the obstacle is removed) 
and closing (by starting the reverse movement only after the obstacle is 
removed).

DIP 4 ON =>   

if an obstacle is placed in range of the photocells when the gate is closed 
and the command to open is given, the gate opens (the photocells do not 
work while opening). Photocells work only during closing (with reverse 
motion restored after a second, even if they are still engaged).

CONTROL OF IMMEDIATE CLOSING AFTER MOVEMENT IN FRONT OF PHOTOCELLS
DIP 16 ON and DIP 4 OFF =>   

if photocells are engaged during opening, the gate stops 
and the gate only closes one second after the photocells 
are disengaged.

DIP 16 ON and DIP 4 ON =>   

if photocells are engaged during opening, the gate 
continues to open. Upon disengagement of the photocells, 
the gate stops and reverses closing motion after a one 
second pause.

 

 If total opening is reached (end of opening time), 
immediate closing is deactivated and automatic 
time closing is activated (if TCA trimmer is activated 
and LED DL6 is on). If during closing there is a rapid 
movement (e.g. pedestrian) the gate will open again 

for two seconds and then close once again.

DIP 12 OFF => 

 

immediate closing after movement in front of the photocells 
is deactivated.

N.B.:

 Please check photocell operation at least every six months.

EDGE (SAFETY STRIP) (COM-EDGE)

If engaged during opening, reverses the motion when closing.
If engaged when closing, reverses the motion when opening.
If it remains engaged again, it performs a further reversal after 2 seconds, then performs an 
additional short reversal and then gives the sensor failure or engaged alarm (N.O. contact).
If the sensor remains engaged (N.O. contact) no movement is allowed. 
If not used, jump the terminals COM-EDGE.

MONITORING OF SAFETY SENSORS (A+ TEST A-)

Sensors can be monitored through the A+ TEST input and DIP 12 ON.
The monitoring consists of a functional test of the sensor run after every full gate opening.
Closing the gate is therefore permitted only if the sensors have passed the functional test 
after each opening.

CAUTION:

 MONITORING OF THE SENSOR INPUT CAN BE ACTIVATED WITH DIP 12 ON OR 

DEACTIVATED WITH DIP 12 OFF. IN FACT, THE FUNCTIONAL TESTING OF SENSORS IS 
‘POSSIBLE ONLY IF THESE DEVICES HAVE THEIR OWN POWER SUPPLY.
A MECHANICAL SENSOR CAN NOT BE MONITORED, SO DIP 12 SHOULD BE SET TO OFF.

SENSOR AUTOTEST ALARM (DIP 12 ON)

If the sensor fails the monitoring test after opening, an alarm is displayed by the blinker 
lighting up. Gate closure is not allowed in this condition. Normal operation can be restored 
only by repairing the sensor and pressing one of the activated controls.

STOP BUTTON (COM-STOP)
The STOP button stops the gate during any operation.

If held when the gate is fully open (or partially when using the pedestrian control) automatic 
closing is temporarily deactivated (if activated by the TCA trimmer and LED DL6 on). It is 
therefore necessary to use a new command to make it close.
The automatic closing function is reactivated on the next cycle (if activated by the TCA 
trimmer and LED DL6 on).

POWER SENSOR ALARM

The T2 24V control panel has automatic sensors that make the movement of the gate 
reverse in case of impact against objects or persons in accordance with the current EN 
standards (always use the right tool to ensure compliance with the values imposed by the 
standard), without special adjustments on the control panel, as it operates using special 
internal software.
If the power sensor is used in opening or closing (only in high-speed) and then again, in the 
opposite direction, the gate stops and then reverses for 1 second.
The alarm status will be displayed by the blinker which will remain active for one minute, 
during which time you can restore gate operation by pressing any command button.

FUNCTIONING IN DEAD MAN MODE WHEN THE SAFETY DEVICES ARE FAILING

If the safety edge fails or remains engaged for more than 5 seconds, or if photocell fails 
or remain engaded for more than 60 seconds,  the open, close, k button and pedestrian 
commands will work only in dead man mode.
The signal that this mode has been activated is given by the blinking of the programming led.
With the blinking of the programming led, the opening and closing operation are allowed 
only with the command button pressed and held. The radio commands and that of automatic 
closing, will be excluded, since their use in this mode, is not allowed by the norms.
Once the failing safety device is repaired,  in automatic after 1 second, all standard 
commands that were selected, such as step by step, automatic mode, radio commands and 
automatic closing start functioning again.

Note 1:

  during this functioning in dead man mode, in case of damage to the safety strips 

(or photocells) the photocells (or safety strips) still work by interrupting the operation 
in progress.

Note 2:

  the stop command is not to be considered a safety command that can be bypassed 

in this mode. Therefore, when pressed or damaged, it will not allow any movement 
of the gate.

The dead-man operation is only an emergency operation which must be activated 
for a very short period and with the complete installation at sight so to have a 
secure and safe control of the system. As soon as possible however, the failing 
safety devices must be repaired and activated.

BLINKER
N.B.:

 This control panel can power ONLY BLINKERS ON A (ACG7061) CIRCUIT with lamps 

G

B

Summary of Contents for AD00709

Page 1: ...erator Torantrieb Operador Alimentazione Alimentation Power Supply Stromspannung Alimentacion Peso max cancello Poids maxi portail Max gate weight Max Torgewicht Peso m x verja Forza max di spinta For...

Page 2: ...cati dalla mancata osservanza nell installazione delle norme di sicurezza e delle leggi attualmente in vigore ATTENTION POUR LA SECURITE DES PERSONNES IL EST IMPORTANT DE SUIVRE TOUTES LES INSTRUCTION...

Page 3: ...es caused by the non observance during the installation of the safety standards and of the laws in force at present ACHTUNG F R DIE SICHERHEIT DER PERSONEN IST ES WICHTIG DASS ALLE ANWEISUNGEN GENAU A...

Page 4: ...normas EN 12453 EN 12445 4 El instalador antes de instalar el motor de desplazamiento tiene que controlar que la cancela est en buenas condiciones mec nicas y que se abra y se cierre en forma adecuad...

Page 5: ...ntenna radio 3 Lampeggiatore 4 Selettore a chiave 5 Fotocellule esterne 1 NERO 1 Collegare a J5 o J6 morsetto NERO 2 Collegare a J5 o J6 morsetto CARATTERISTICHE TECNICHE KING 24V Lunghezza max anta m...

Page 6: ...orze entro i limiti della norma EN12453 Appendice A E Fotocellule es cod ACG8026 Da applicare ogni 60 70cm per tutta l altezza della colonna del cancello fino ad un massimo di 2 5m EN 12445 punto 7 3...

Page 7: ...ANT COL 1 1 80 90 45 100 100 815 90 14 A S3 Y 1 81 2 20 45 110 110 815 90 18 A S3 X 2 21 2 50 70 140 110 815 90 20 A S1 Z 2 51 3 00 90 170 140 815 115 25 B S2 Y 3 01 3 50 115 200 140 815 115 27 B S2...

Page 8: ...ermo A e bloccarlo serrando la vite da 8mA con una chiave fissa n 13 Per ottenere la chiusura desiderata si dovr spostare il fermo B OPZIONALE bloccandolo come descritto per il fermo A MANUTENZIONE Da...

Page 9: ...PASSO COMUNE COMUNE 24Vdc 0 8A 15 per ACCESSORI 24Vdc 0 8A 15 per AUTOTEST COSTE LAMPEGGIATORE 24Vdc 20W LED R 2 2K 1 4W SERRATURA ELETTRICA PEDONALE COSTE ALIMENTAZIONE 230Vac 50Hz TRASFORMATORE M1...

Page 10: ...a NON TOCCARE IL PONTICELLO SE VIENE RIMOSSO L OPERATORE NON FUNZIONA Connettore dedicato alla programmazione in fabbrica solo per modelli CRX NON TOCCARE IL PONTICELLO SE VIENE RIMOSSO L OPERATORE NO...

Page 11: ...so DL6 segnalazione tempo chiusura automatica rosso DL7 contatto fotocellule NC rosso DL8 contatto costa NC rosso DL9 comando pulsante STOP NC rosso DL10 programmazione codici radio verde FUSIBILI Fus...

Page 12: ...a cancello fermo 1 Posizionare il DIP 1 su ON e successivamente il DIP 2 su ON 2 Il led rosso DL1 di programmazione lampeggia con frequenza di 1 sec ON e 1 sec OFF per 10 secondi 3 Premere e mantenere...

Page 13: ...condo anche se le stesse restano impegnate GESTIONE CHIUSURA IMMEDIATA DOPO IL TRANSITO DA FOTOCELLULE DIP 16 ON e DIP 4 OFF Mentre il cancello apre transitando davanti alle fotocellule il cancello si...

Page 14: ...24VDC Potenza Trasformatore 130VA primario 230Vac secondario 18Vac Assorbimento massimo 50 mA Microinterruzioni di rete 100ms Potenza massima spia cancello aperto 24Vdc 3W equivalente a 1 lampadina d...

Page 15: ...CH cod ACG6058 TELECOMANDO SUN DISPOSITIVI Wi Fi NOVA Wi Fi FOTOCELLULE SENZA FILI cod ACG8037 COPPIA COLONNINE NOVA cod ACG8039 VERTIGO Wi Fi FOTOCELLULE SENZA FILI SOSTITUTIVE DELLA COSTA VERTIGO Wi...

Page 16: ...de 50 mm 1 Operateur KING 24V 2 Antenne radio 3 Signal electrique 4 Selecteur 5 Photocellules p protection externe 1 NOIR 1 Connecter J5 ou J6 borne NOIR 2 Connecter J5 ou J6 borne CARACTERISTIQUES TE...

Page 17: ...spositifs de limitation des forces dans les limites de la norme EN12453 appendice A E Cellules photo lectriques code ACG8026 Appliquer chaque 60 70 cm pour toute la taille de la colonne de la porte ju...

Page 18: ...sec ANT COL 1 1 80 90 45 100 100 815 90 14 A S3 Y 1 81 2 20 45 110 110 815 90 18 A S3 X 2 21 2 50 70 140 110 815 90 20 A S1 Z 2 51 3 00 90 170 140 815 115 25 B S2 Y 3 01 3 50 115 200 140 815 115 27 B...

Page 19: ...e il suffit de d placer le collier A et de le bloquer en vissant la vis M8 avec une cl n 13 Pour obtenir la fermeture desir e il est necessarie de deplacer le collier B OPTIONAL et de le bloquer comme...

Page 20: ...PAS COMMUN COMMUN 24Vdc 0 8A 15 pour ACCESSOIRES 24Vdc 0 8A 15 AUTOTEST pour BARRE PALPEUSE FEU CLIGNOTANT 24Vdc 20W LED R 2 2K 1 4W SERRURE LECTRIQUE PIETON BARRE PALPEUSE ALIMENTATION 230Vac 50Hz TR...

Page 21: ...en usine NE PAS TOUCHER AU CAVALIER SANS L OP RATEUR IL NE FONCTIONNE PAS Connecteur d di la programmation en usine seulement pour les mod les CRX NE PAS TOUCHER AU CAVALIER SI LE SYST ME RADIO EST E...

Page 22: ...ement ou partiellement ouverte pi tonne et avec la DEL DL6 allum e le trimmer doit tre r gl dans le sens des aiguilles d une montre Le temps de pause peut varier de 2 secondes 2 minutes selon le r gla...

Page 23: ...A PROGRAMMATION CHOISIE E PROGRAMMATION DES CODES RADIO POUR OUVERTURE TOTALE 62 CODES MAXIMUM UNIQUEMENT POUR LES MODELES CRX La programmation ne peut se faire que lorsque le portail est ferm 1 Posit...

Page 24: ...s ouvrir stopper fermer stopper ouvrir etc Si DIP 6 est sur ON Il effectue l ouverture quand le portail est ferm S il est actionn pendant le mouvement d ouverture cela ne produit aucun effet S il est...

Page 25: ...ommande et la fermeture automatique sont de travail Note 1 Au cours de cette op ration dans le cas de panne de les barres palpeuses ou cellules photo lectriques les cellules photo lectriques ou barres...

Page 26: ...PHOTOCELLULES SANS FIL POUR REMPLACER LA BARRE PALPEUSE VERTIGO Wi Fi 8 code ACG8042 VERTIGO Wi Fi 10 code ACG8043 BLOCK Wi Fi S LECTEUR CL SANS FILS code ACG6098 SPARK Wi Fi FEU CLIGNOTANT SANS FILS...

Page 27: ...stop is used during closing optional the maximum travel is reduced by 50 mm 1 KING 24V operator 2 Tuned aerial 3 Flashing lamp 4 Key selector 5 Photoelectric cells external 1 TECHNICAL DATA KING 24V...

Page 28: ...keep thrust force within the limits of EN12453 regulation Appendix A E Photocells like code ACG8026 To apply every 60 70cm for all the height of the column of the gate up to a maximum of 2 5m EN 12445...

Page 29: ...COL 1 1 80 90 45 100 100 815 90 14 A S3 Y 1 81 2 20 45 110 110 815 90 18 A S3 X 2 21 2 50 70 140 110 815 90 20 A S1 Z 2 51 3 00 90 170 140 815 115 25 B S2 Y 3 01 3 50 115 200 140 815 115 27 B S2 Y L M...

Page 30: ...per A in the needed position by tightening the 8mA screw with a n 13 key To obtain the desired closing limit you must adjust the stopper B OPTIONAL in the needed position and tighten it as for stopper...

Page 31: ...P COMMON COMMON 24Vdc 0 8A 15 for ACCESSORY SUPPLY 24Vdc 0 8A 15 for AUTOTEST SAFETY STRIPS BLINKER 24Vdc 20W LED R 2 2K 1 4W ELECTRIC LOCK PEDESTRIAN SAFETY STRIPS POWER SUPPLY 230Vac 50 Hz TRANSFORM...

Page 32: ...DO NOT REMOVE ANY JUMPER OTHERWISE THE OPERATOR WILL NOT WORK Connector dedicated to the factory programming only CRX control board DO NOT REMOVE ANY JUMPER OTHERWISE THE OPERATOR WILL NOT WORK Built...

Page 33: ...pening M1 green DL5 gate closing M1 red DL6 automatic closing indicator red DL7 photocell contact NC red DL8 sensor contact NC red DL9 STOP button NC red DL10 radio code program green FUSES Fuse 1 T 8...

Page 34: ...ellation is indicated by two flashes of green LED DL10 4 The red LED DL1 remains active and you can add new codes as shown above 5 Reset DIP 1 to OFF and DIP 2 to OFF 6 End of procedure INDICATOR MEMO...

Page 35: ...when closing If engaged when closing reverses the motion when opening If it remains engaged again it performs a further reversal after 2 seconds then performs an additional short reversal and then gi...

Page 36: ...power to the board and is set up to ensure compliance with double or reinforced insulation with regard to dangerous voltage Any external circuits connected to the outputs of the control panel must be...

Page 37: ...TRANSMITTER SUN Wi Fi DEVICES MASTER Wi Fi RECEIVER CARD TO MANAGE WIRELESS SYSTEM with connector 12 30V ac dc code ACG6094 with terminal block 12 30V ac dc code ACG6099 NOVA Wi Fi PHOTOCELLS WITHOUT...

Page 38: ...HE EIGENSCHAFTEN KING 24V Max Torfl gelweite m 4 Max Torgewicht kg 400 Max Hub mm 345 ffnungszeit ca s 14 27 Laufgeschwindigkeit m s 0 0125 Max Schubkraft N 1800 Stromspannung und Frequenz 24V 24V Mot...

Page 39: ...ungen muessen mit den Norm EN12453 uebereinstimmen Anhang A E Photozelle wie Kode ACG8026 Jede 60 70 cm f r die ganze H he der Spalte des Gatters bis zu einem Maximum von 2 5 m anwenden EN 12445 Punkt...

Page 40: ...Max a A max B C D E T sec ANT COL 1 1 80 90 45 100 100 815 90 14 A S3 Y 1 81 2 20 45 110 110 815 90 18 A S3 X 2 21 2 50 70 140 110 815 90 20 A S1 Z 2 51 3 00 90 170 140 815 115 25 B S2 Y 3 01 3 50 115...

Page 41: ...w nschte Offnungsweite einzustellen gen ngt es die Endschalter A zu verstellen und sie mit Hilfe eines Imbusschl els an der Mutterschraube festzuziehen Um die erw nschte Schliessweite einzustellen m s...

Page 42: ...EINSAME ERDUNGSKONTAKTE GEMEINSAME ERDUNGSKONTAKTE 24Vdc 0 8A 15 f r ZUBEH RE 24Vdc 0 8A 15 f r AUTOTEST KONTAKTLEISTE BLINKER 24Vdc 20W LED R 2 2K 1 4W ELEKTROSCHLOSS FUSSG NGER KONTAKLEISTE STROMVER...

Page 43: ...f r die Programmierung in der Fabrik NICHT DIE BERBR CKUNG BER HREN OHNE ANTRIEB NICHT BETRIEBSF HIG Verbinder f r die Programmierung in der Fabrik nur f r die Modelle CRX NICHT DIE BERBR CKUNG BER H...

Page 44: ...g ffnung und eingeschalteter LED Anzeige DL6 Trimmer im Uhrzeigersinn gedreht Die Pause kann von mindestens 2 Sekunden bis maximal 2 Minuten eingestellt werden LED ANZEIGEN DL1 Programmierung aktivier...

Page 45: ...eschlossenem Tor 1 DIP 1 auf ON und anschlie end DIP 2 auf ON stellen 2 Die rote LED AnzeigeDL1 f r die Programmierung blinkt mit einer Frequenz von 1 Sek ON und 1 Sek OFF f r 10 Sekunden 3 Die Fernst...

Page 46: ...enem Tor gedr ckt so wird das Tor geschlossen dr ckt man sie bei geschlossenem Tor f hrt das zur ffnung ELEKTRISCHE VERRIEGELUNG LOCK DIP 8 auf ON stellen um den Befehl f r die elektrische Verriegelun...

Page 47: ...rend dieses Vorgangs im fall eines ausfalls der Kontaktleisten oder Fotozellen der Fotozellen oder Kontaktleisten funktionieren noch Unterbrechung des Betriebs im Gange Anmerkung 2 Die Stoppen Taste i...

Page 48: ...G6058 FERNSENDER SUN Wi Fi VORRICHTUNGEN MASTER Wi Fi KARTE F R DEN BETRIEB DES SYSTEMS OHNE KABEL mit Verbinder 12 30V ac dc Kode ACG6094 mit Endblockierung 12 30V ac dc Kode ACG6099 NOVA Wi Fi FOTOZ...

Page 49: ...lo mec nicos Con el seguro mec nico incorporado que interviene durante la abertura Si se utiliza tambi n el seguro mec nico que interviene durante el cierre opcional la carrera m xima de remolque se r...

Page 50: ...Regulacion de la fuerza del motor D Nervaduras como c d ACG3010 y o otros dispositivos que limitan las fuerzas entre limites de las normas EN 12453 Appendix A E Fotoc lulas como c d ACG8026 Da applic...

Page 51: ...D E T sec ANT COL 1 1 80 90 45 100 100 815 90 14 A S3 Y 1 81 2 20 45 110 110 815 90 18 A S3 X 2 21 2 50 70 140 110 815 90 20 A S1 Z 2 51 3 00 90 170 140 815 115 25 B S2 Y 3 01 3 50 115 200 140 815 11...

Page 52: ...y bloquearlo con una llave fija n 13 Para poder obtener el cierre deseado se tendr que mover el seguro B OPCIONAL y bloquearlo con una llave fija n 13 MANTENIMIENTO Estas operaciones deben ser efectu...

Page 53: ...O PASSO COM N COM N 24Vdc 0 8A 15 para ACCESSORIOS 24Vdc 0 8A 15 para AUTOTEST COSTAS INTERMITENTE 24Vdc 20W LED R 2 2K 1 4W CERRADURA EL CTRICA PEATONAL COSTAS ALIMENTACION 230Vac 50Hz TRANSFORMADOR...

Page 54: ...O RESPETAR LAS PRUEBAS DE IMPACTO INDICADAS EN LA NORMATIVA EN12453 EN CASO DE QUE NO SEA NECESARIO OBEDECER LA NORMA ARRIBA DESCRITA BASTA COLOCAR EL DIP 3 EN POSICI N OFF EN ESTE CASO LAS PUERTAS SE...

Page 55: ...LOS TIEMPOS PARA 1 MOTOR M1 CON SENSOR DE CORRIENTE HABILITADO DIP 7 ON ATENCI N PARA GESTIONAR UN SOLO MOTOR EL DIP 13 DEBE ESTAR COLOCADO EN POSICI N ON DURANTE LA PROGRAMACI N EL SENSOR DE CORRIEN...

Page 56: ...os est n programados en el modo de IMPULSO de lo contrario pueden activar el movimiento de la puerta sin tener activos los elementos de seguridad PULSADOR DE MANDO PASO PASO COM K BUTTON Si DIP 6 en O...

Page 57: ...de seguridad se estropea o se queda empe ada por mas de 60 segundos los comandos ABRE CIERRE K BUTTON y el PEATONAL funcionar n solo a hombre presente El signal de activaci n de este funcionamiento se...

Page 58: ...CH c d ACG6058 TELEMANDO SUN DISPOSITIVOS Wi Fi MASTER Wi Fi FICHA DE GESTI N SISTEMA SIN CABLES con enchufe 12 30V ac dc c d ACG6094 con regleta 12 30V ac dc c d ACG6099 NOVA Wi Fi FOTOC LULAS SIN CA...

Page 59: ...2 de la Directive machines 2006 42 CEE et de ses modifications successives Sa mise en service est interdite avant que l installation ait t d clar e conforme aux dispositions pr vues par la Directive T...

Page 60: ...nsatore 35 F 450V x serie 120V 60 CME1166 Adattat motore KING 24V CME1299 Perno per ingranaggio serie KING CME2042 Corona elicoidale sblocco sx CME2041 Corona elicoidale dx serie KING CME8996 Vite s f...

Reviews: