34
engaged).
IMMEDIATE GATE CLOSURE AFTER TRANSIT ON PHOTOCELLS
DIP 8 ON and DIP 4 OFF = > while the gate opens, passing in front of the photocells, the
gate will stop. Once it is done transiting, after 1 second the
gate closes.
DIP 8 ON and DIP 4 ON = > while the gate opens, passing in front of the photocells, the
gate will continue to open. Once it is done transiting, the gate
will stop and after a pause of 1 second, close.
If during closing you have a rapid transit (e.g. Pedestrian), the gate will reopen for two
seconds and then close again.
8 OFF => immediate gate closure after transit on photocells disabled.
EDGE (COM-EDGE) - Safety function SF1 - PL “b” according to EN13849-1
With the edge enabled, the buzzer emits 2 tones.
If the edge intervenes while the gate is opening
, it will cause the gate to to stop for 2
seconds and then come to a complete stop.
If the edge intervenes while the gate is closing
, it will cause the gate to to open for 2
seconds and then come to a complete stop.
If the edge remains engaged
(contact NO), no automatic movement is allowed.
If the edge not installed
, jumper connect the COM-EDGE terminals.
IMPORTANT: It is recommended to check that the edges are working properly at least
once every 6 months.
ALARM FROM EDGE
After an inversion following intervention of the edge, the gate stops and the control unit
signals the alarm by activating the flasher for 1 minute and the buzzer for 1 minute (with a
2-tone sound signal every 5 seconds).
During or after the alarm minute, you can reset the gate by pressing any control button.
SAFETY EDGE “AUTO-TEST” MONITORING (A+/A- TEST)
Via the A+ TEST input and with DIP 10 set to ON, you can monitor the edge(s) equipped with
its/their own power unit connected to the A+/A- TEST terminals (24Vdc).
The monitoring consists of a functional test of the edge performed at the end of a complete
gate opening.
After every opening, closing of the gate is only allowed if the edge(s) has passed the
functional test.
Caution: Edge entrance monitoring can be enabled with DIP 10 set to ON, or disabled with
DIP 10 set to OFF.
A mechanical edge cannot be monitored, therefore DIP 10 must be set to OFF.
FAILED AUTO-TEST ALARM
If the edge auto-test fails, the buzzer will sound for a minute (with 4 tones every 5 seconds)
to signal the alarm, and will not allow closure of the gate until you have solved the problem.
The alarm is reset with a closing command.
CURRENT SENSOR (DIP 7 - ON) - Safety function SF4 - PL “b” according to EN13849-1
The K 24V control unit features a self-calibrating current sensor which reverses the gate’s
movement if this bumps against things or people (in compliance with the applicable en
standards - always check with the aid of the tool that the values are within the standard
limits).
With sensor enabled, in the event of impact, the buzzer emits 3 tones.
If the sensor intervenes while the gate is opening
, it will invert the gate’s closing
movement for 2 seconds and then come to a complete stop.
If the sensor intervenes while the gate is closing
, it will invert the gate’s opening
movement for 2 seconds and then come to a complete stop.
N.B.: With DIP 7 in OFF mode, the SF4 safety function is disabled. The gate, in case of
an impact with a person, an animal or a thing, will NOT stop!
CURRENT SENSOR ALARM
After an inversion following intervention of the current sensor, the gate stops due to an alarm,
which is signalled by the flasher turning on for 1 minute and the buzzer for 1 minute (with a
3-tone sound signal every 5 seconds).
During or after the alarm minute, you can reset the gate by pressing any control button.
STOP BUTTON (COM-STOP) - Safety function SF3 - PL “b” according to EN13849-1
During the movement, the stop button will stop the gate.
If the STOP button is pressed when the gate is fully open (or partially using the pedestrian
command) the automatic closure will be temporarily excluded (if enabled via trimmer ACT
with led DL3 on). It is therefore necessary to give a new command to close the gate.
Closing the gate will re-enable automatic closing (if enabled via trimmer ACT with led DL3
on).
MODE “WORK ALWAYS” IN CASE OF FAILURE OF ONE OF THE SAFETY DEVICES.
DIP 9 - OFF:
If the edge is faulty or engaged for more than 5 seconds, or if the photocell is
faulty or engaged for more than 60 seconds, the OPEN,CLOSE, K-BUTTON and PEDESTRIAN
controls will work if operator-run.
Led DL1 will flash to signal that the function has been enabled.
With this feature allows opening or closing of the gate only if the control buttons are held
pressed. The radio control and automatic closing are excluded.
When the safety contact is restored, after 1 second, the automatic or step mode are
automatically re-enabled, and therefore also the remote control and automatic closing will
work again.
DIP 9 - ON:
You can control the gate also with the remote control by pressing and holding
the key on the remote control until the power saver system is activated (approximately 8
seconds).
Note 1: during this mode, if the edges (or photocells) experience a fault, they will continue to
work, interrupting the command in progress.
Note 2: the stop button is not considered a safety to be bypassed in this mode, therefore if
it is pressed or broken, it does not allow any command.
The operator-run command is exclusively an emergency that must be run only for short
periods and with the visual safety of the automatism. Repair/replace the faulty safety devices
as soon as possible, in order to restore correct system operation.
HEATER FUNCTION (DIP 5-ON)
Allows the operator to always operate at a temperature suitable for the operation.
This device automatically turns on only when the gate is at a standstill and the opening or
closing limit-switch engaged, at an ambient temperature of the motor of 0° C, detected by
the sensor mounted on the board.
When the motor is in motion, the heater is turned off.
After 10 seconds that the gate remains stationary, the heater is activated (if the motor
ambient temperature is less than or equal to 0° C).
When the motor reaches a temperature of 3° C, the heater shuts down, maintaining the
environmental conditions at a constant temperature.
VISUAL AND SOUND SIGNALS
FLASHER
IMPORTANT: This electronic panel can power only one flasher with flashing circuit (ACG7061)
with a 24V and 20W (maximum) lamp.
If you exceed 20W, the electronic
panel’s logic will be compromised, with the system possibly stopping.
PRE-FLASHING FUNCTION
DIP 11 - OFF
=> the motor and flasher start simultaneously.
DIP 11 - ON
=> the flasher starts 3 seconds before the motor.
GATE OPEN 24Vdc INDICATOR LIGHT (A+ SIGNAL)
The light signals that the gate is open, partly open or not completely closed. Only when the
gate is completely closed does the light turn off.
During programming, this signal is enabled.
IMPORTANT: Max. 10 W. If you pass the limits with the lights, the electronic panel’s
logic will be compromised, with the system possibly stopping.
BUZZER
Signals that the safety devices have triggered an alarm, alarm status and codes saved/
deleted in memory.
G