background image

25

25

G

B

R50 INSTALLATION 

P

RE-INSTALLATION CHECKS

The leaf must be fixed firmily on the hinges to the pillars, must not be 
flexible  during  the  movement  and  must  move  without  frictions.  The 
ground on which the R50 wheels run must be solid and compact with 
minimum gradient.

Gate features must be uniformed with the standards and laws in 
force.

 The door/gate can be automated only if it is in a good condition 

and its conditions comply with the EN 12604 norm.
-  The  door/gate  leaf  does  not  have  to  have  a  pedestrian  opening.  In 

the  opposite  case  it  is  necessary  to  take  the  appropriate  steps,  in 
accordance  with  EN  12453  norm  (for  instance;  by  preventing  the 
operation  of  the  motor  when  the  pedestrian  opening  is  opened,  by 
installing a safety microswitch connected with the control panel).

-  No  mechanical  stop  shall  be  on  top  of  the  gate,  since  mechanical 

stops are not safe enough. 

The ground should be compact and without any excessive differences 
in level along the tract destined for wheel run.
Position  the  gate  about  halfway,  secure  the  gearmotor  plate  to  the 
corner  of  the  gate  leaf  and  ensure  that  the  drive  wheels  rest  on  the 
ground.
Drill  four  Ø  6.5  mm  holes  in  the  leaf,  then  tap  them  with  M8  male 
threading.  
Insert four M8 bolts and tighten with a No. 13 wrench.
Remove the elastic pin which prevents the wheels from turning (Fig. 6).
If  the  drive  wheels  slide  on  the  ground  during  operation,  turn  the  set 
screw  on  the  spring  clockwise  to  increase  the  pressure  between  the 

wheels and the ground.
To reduce wheel wear during operation, loosen nuts (D) with a No. 13 
wrench  and  tilt  the  rubber  wheels  so  that  the  axles  coincide  with  the 
center of the gate leaf pivot point.
The wheels may be tilted by 0° to 7.5°.  Retighten the two nuts.
The  R50  is  equipped  with  two  waterproof,  armored  limit  stops  to 
electrically control gate travel. 
The  limit  stops  should  be  positioned  in  accordance  with  installer 
requirements.

R

50 INSTALLATION

COMMAND TYPE 

USE OF THE SHUTTER

 

Skilled persons 

Skilled persons 

Unrestricted use

 

(out of public area*) 

(public area) 

 

with manned operation 

non possibile

with visible impulses 

C or E 

C or E 

C and D, or E

(e.g. sensor) 

with not visible impulses

 

C or E 

C and D, or E 

C and D, or E

(e.g. remote controldevice)

automatic 

C and D, or E 

C and D, or E 

C and D, or E

* a typical example are those shutters which do not have access to any public way

A:  Command button with manned operation (that is, operating as long as activated), 

like code ACG2013

B: Key selector with manned operation, like code ACG1010

C: Adjustable power of the motor

D:  Safety strips and/or other safety devices to keep thrust force within the limits of 

EN12453 regulation - Appendix A.

E:  Photocells, like code ACG8026 (To apply every 60÷70 cm for all the height of the 

column of the gate up to a maximum of 2,5 m - EN 12445 point 7.3.2.1)

Parts to install meeting the EN 12453 standard

3

B min [m]  = (0,205+A) / 0,12 
B [m]  

= 0,9 x L 

Opening time [sec] = 7,85 x L

D

Summary of Contents for R50

Page 1: ...code code R50 230V 50 60Hz AA21580 Peso max cancello Poids maxi portail Max gate weight Max Torgewicht 2000 kg 4460 lbs ITALIANO pag 04 FRANÇAIS pag 14 ENGLISH page 24 DEUTSCH pag 34 OPERATORE PER PORTONI INDUSTRIALI OPERATEUR POUR PORTAILS INDUSTRIELS OPERATOR FOR INDUSTRIAL DOORS TORANTRIEB FÜR INDUSTRIETORE ...

Page 2: ...E SAFETY OF THE PEOPLE IT IS IMPORTANT TO FOLLOW ALL THE INSTRUCTIONS INSTALLATIONSVORSCHRIFTEN BEACHTET WERDEN 1 Wenn nicht bereits an der elektrischen Schaltzentrale vorgesehen muss vor der Schaltzentrale ein thermomagnetischer Schalter installiert werden omnipolar mit einer minimalen Kontaktöffnung von 3 mm der ein von den internationalen Normen anerkanntes Konformitätszeichen besitzt Solch ein...

Page 3: ...pring Measurements in mm TECHNICAL DATA Max leaf length Max leaf weight Average opening time 90 Operating speed EEC Power supply Motor capacity Power absorbed Capacitor EEC Power supply Motor capacity Power absorbed Capacitor 230 50 60 Normative cycles 120 60 Normative cycles Daily cycles suggested Service Consecutive cycles guaranteed Grease Actuator weight Operating temperature Protection grade ...

Page 4: ...lide on the ground during operation turn the set screw on the spring clockwise to increase the pressure between the wheels and the ground To reduce wheel wear during operation loosen nuts D with a No 13 wrench and tilt the rubber wheels so that the axles coincide with the center of the gate leaf pivot point The wheels may be tilted by 0 to 7 5 Retighten the two nuts The R50 is equipped with two wa...

Page 5: ... these appropriate handles are placed so to avoid safety risks for the operator That the physical effort necessary to move the gate leaf should not be higher than 225 N for doors gates for private dwellings and 390N for doors gates for commercial and industrial sites values indicated in 5 3 5 of the EN 12453 norm A Maximum stroke 60 mm during movement holes or uneven ground B Remove the elastic pi...

Page 6: ... surfaces carefully once a week Check wheel ground pressure and condition of motor wheels every six months The motor should be overhauled every two years and the oil replaced ELECTRIC CONNECTIONS T2 code BC07086 T2 CRX code BC07085 AERIAL COAX R 2 2KΩ SIGNAL BUZZER 12Vdc for AUTOTEST EDGE 12Vdc for ACCESSORY SUPPLY PHOTOCELL EDGE K BUTTON PED BUTTON COM CAPACITOR M1 POWER SUPPLY MOTOR 1 MOTOR 2 CA...

Page 7: ...HASE AND CAPACITOR CONNECTIONS MOTOR 1 COMMON CONNECTION MOTOR 1 PHASE AND CAPACITOR CONNECTIONS DO NOT REMOVE ANY JUMPER OTHERWISE THE OPERATOR WILL NOT WORK only CRX control board DO NOT REMOVE ANY JUMPER OTHERWISE THE OPERATOR WILL NOT WORK Not available for R50 Built in radio module model CRX or connector for radio receiver RIB 12 Vdc supply To select 1 motor M1 or 2 motors M1 and M2 Programmi...

Page 8: ...d lock again the operators 2 Turn DIP1 to ON position The red LED DL1 starts blinking 3 Press the PROG button and hold it When GREEN LEDS DL3 and DL5 are on the gate leaves are opening with a phase shift of 2 seconds Check the leaves swinging and the opening mechanical stopper position movement is now performed in man present mode open close open etc If any of the leaf closes instead of opening re...

Page 9: ...e DL2 LED green will flash once 4 The code programming time resets automatically so that you can programme the next remote control 5 To finish programming let 10 seconds pass and then press the PROG button briefly The red DL1 LED will stop flashing 6 Reposition DIP 1 to OFF and DIP 3 to OFF N B IF THE DL1 LED CONTINUES TO FLASH RAPIDLY THIS MEANS THAT DIP 1 IS STILL POSITIONED TO ON AND ANY MANOEU...

Page 10: ...leaves the gate will close automatically after 1 second pause If DIP12 ON and DIP4 ON If the gate is opening and a vehicle crosses the photo beam the gate will continue to open When the vehicle leaves the gate will stop and then closes automatically after 1 second pause If the complete gate open position is reached before the vehicle leaving the DIP12 will be ignored and the automatic closing will...

Page 11: ... out a self check at the beginning of each operation During blackout At the return of the network power supply If the gate is totally closed It will remain closed If the gate is at the opening stage It will continue opening If the gate is totally open with dip 3 OFF It remains open Consequently closing operations of the gate can be controlled If the gate is totally open with dip 3 ON It remains op...

Page 12: ...TTER code ACG8028 for more than 2 photocells couples up to 4 COUPLE OF BUILT IN BOXES FOR THE FIT SYNCRO code ACG8051 CODE LEARNIG SYSTEM RADIORECEIVERS RX91 A quarzata and coupling code ACG5005 RX91 A quarzata and terminal board code ACG5004 RX433 A super eterodyne and coupling code ACG5055 RX433 A super eterodyne and terminal board code ACG5056 RX433 A 2CH super eterodyne 2 channel and coupling ...

Page 13: ...245 Rotore con albero CMO1320 Statore 230V 50 60Hz 1P CCM6302ZZ Cuscinetto 6302ZZ CTC1006 Chiavetta 6x6x20 CTC1069 Molla per R50 CTC1104 Paraolio 50x72x10 CTC1124 Seeger E28 CTC1136 Seeger I 80 CTC1206 Molla a tazza CTC1350 Anello di tenuta Codice Denominazione Particolare CTC1401 Paraolio 50x80x8 CTC1402 Paraolio30x47x7 CVA1029 Manopola MCG 28 85 GIR CVA1380 Copriventola motore CVA1381 Ventola CV...

Reviews: