 -  SETTINGS

 

DIP 1  (ON)  MOTOR ROTATION DIRECTION CHECK (See Point 

C

)

DIP 2  (ON)

 

PROGRAMMING (See Point D)

DIP 1-2   

STORAGE/DELETION OF RADIO CODES FOR COMPLETE 
OPENING  (DIP  1  ON  followed  by  DIP  2  ON)  (POINT  G) 
ONLY FOR CRX MODELS

DIP 1-3  

STORAGE/DELETION  OF  RADIO  CODES  FOR  PEDESTRIAN  OPENING 
(DIP 1 ON followed by DIP 3 ON) (POINT H) ONLY FOR CRX MODELS

DIP 2-1  PROGRAMMING OF THE PEDESTRIAN OPENING (See Point F)
DIP 3

  ON  - Automatic Closing ENABLED

 

OFF  - Automatic Closing DISABLED

DIP 4

  ON  - Photocells active only in closing 

 

OFF  - Photocells always active 

DIP 5

  ON  - blinker pre-flashing 

 

OFF  - blinker normal-flashing

DIP 6

  OFF  - STEP BY STEP 

 

 

  Single pulse contact (K BUTT) 

 

 

  Pedestrian button (PED BUTT)

 

 

  Radio Receiver command 

 

ON  - AUTOMATIC  

 

 

  Single pulse contact (K BUTT) 

 

 

  Pedestrian button (PED BUTT)

 

 

  Radio Receiver command

DIP 7

  ON  - low speed in approaching ENABLED 

 

OFF  - low speed in approaching DISABLED

DIP 8

  ON  - electric lock command ENABLED 

 

OFF  - electric lock command DISABLED

DIP 9

    ON  -  Hammering on complete close position to ease Manual Release

 

 

-  Hammering before opening to ease electric lock unlocking

 

OFF  - no impulse

DIP 10

  ON  -  Extra  thrust  when  reached  closing  position  to  make  sure  that  the 

mechanical bolt is fixed into the ground

 

OFF  - no impulse

DIP 11

  ON  - black out function ENABLED (See chart 1)

 

OFF  - black out function DISABLED

DIP 12

  ON  -  close command after the transit through the photocell ENABLED

 

OFF  -  close command after the transit through the photocell DISABLED  

DIP 13

  ON  - safety strip self-test ENABLED 

 

OFF  - safety strip self-test DISABLED

DIP 14

 

OFF  OBLIGATORY FOR R50 MOTOR

DIP 15

 

ON  OBLIGATORY FOR R50 MOTOR

DIP 16

 

ON  OBLIGATORY FOR R50 MOTOR

JP   17

  OPEN JUMPER 1 motor (M1) - 1 leaf

 

CLOSE JUMPER 2 motors (M1 and M2) - 2 leaves

JP1 =>

  Pay attention that the jumper is inserted!

JP2 =>

  Pay attention that the jumper is inserted!

JP3 =>

  Pay attention that the jumper is inserted!

TORQUE TR1 Electronic regulator for motor torque 

Adjustment of motor torque is carried out using the TORQUE Trimmer which varies 
the output voltage to the  head/s of the motor/s (turn clockwise to increase torque).
This torque control is activated after 2 seconds form any manoeuvre begging, whereas 
the motor is turned on at full power to guarantee the starting at the manoeuvre begging.

PAY  ATTENTION:  IF  THE  TORQUE  TRIMMER  SETTING  IS  CHANGED,  IT  IS 
PREFERABLE TO REPEAT THE TIME PROGRAMMING.    

     

LOW SPEED  TR2 Electronic regulator for low speed on approach  

Adjustment of low speed is carried out using the LOW SPEED Trimmer which varies 
the output voltage to the  head/s of the motor/s (turn clockwise to increase speed). 
Adjustment is carried out to establish the correct speed at the completion of opening 
and  closing,  depending  on    the  structure  of  the  gate,  or  if  there  is  any  light  friction 
that could compromise the correct working of the system. The low speed is activated 
(DIP7 OFF) when the gate leaf is 0.50-0.60 meters away from the complete close or 
open position.    

ATTENTION: WHEN USING HYDRAULIC OPERATORS
When  using  the  hydraulic  operators  the  deceleration  phase  may  not  operate 
correctly; in that case it is advisable to disable the feature of the deceleration by 
putting DIP 7 in the OFF mode.

LED WARNING

DL1 - programming activated (red)
DL2 - radio code programming (green) (only for CRX)
DL3 - gate opening M2 (green)

DL4 - gate closing M2 (red)
DL5 - gate opening M1 (green)
DL6 - gate closing M1 (red)
DL7 - photocell contact (NC) (red)
DL8 - safety strip contact (NC) (red)

FUSES

F1 T100mA    Accessories protection fuse 
F2 5A            Motor protection fuse     

POINT C

 - MOTOR ROTATION DIRECTION CHECK

1 -  Unlock  the  operators  with  the  Manual  Release  -  swing  open  the  leaves  about 

halfway and lock again the operators.

2 -  Turn DIP1 to ON position. The red LED DL1 starts blinking.
3 -  Press  the  PROG  button  and  hold  it  - When  GREEN  LEDS  DL3  and  DL5  are 

on,  the  gate  leaves  are  opening  (with  a  phase  shift  of  2  seconds). Check  the 
leaves swinging and the opening mechanical stopper position (movement is now 
performed in “man present” mode, open-close-open-etc.).

 

 If any of the leaf closes instead of opening, release PROG button, turn off the main 
power and reverse the two phase wires (V1/2 and W1/2) of the relevant motor/s. 

4 -  Press  the  PROG  button  and  hold  it  to  CLOSE  completely  the  gate. When  RED 

LEDS DL4 and DL6 are on, the gate leaves are closing (with a phase shift of 4 
seconds). Check leaves swinging and the closing mechanical stopper position. 

5 -  After  3  seconds  motor  starting  and  for  the  next  10  seconds  motor  working,  the 

torque  controls  automatically  activated.  Set  the  motor  torque by  the  TORQUE 
Trimmer/s which varies the output voltage to the motor/s (turn clockwise to increase 
the torque).

6 -  After  other  10  seconds  motor  working,  the  low  speed  controls  automatically 

activated  (DIP7  ON).  Set  the  motor  low  speed  by  the  LOW  SPEED  Trimmer  to 
select the gate leaf low speed in approaching.

7 - Close completely the gate.
8 - Turn DIP1 to OFF position, LED DL1 turns off.

During  Point  C  procedure,  safety  devices  (photocells  and  safetystrip)  are  not 
active and the remote control cannot operate.

(#)   In  Point D, Point E and Point F procedures, all the safety devices (photocells and 

safety strip) will be active, so they must be properly installed and connected to the 
control board. Any changing of the safety devices input state, will stop the Point D, 
Point E or Point F procedure that must be repeated from the beginning. 

POINT D

 -  PROGRAMMING FOR 2 MOTORS (#)

1 -  The gate must be fully closed.
2 -  Turn 

DIP2 to ON

 position, LED DL1 starts blinking

3 -  

Press PROG. Button

, motor M1 opens.

4 -  Once reached the open position, let 1 second pass and 

press the PROG button

 to 

cut out motor M1 (time travel of M1 has now been just stored with this operation).

5 - Motor M2 opens, automatically.
6 -  Once reached the open position, let 1 second pass and 

press the PROG button

 to 

cut out motor M2 (time travel of M2 has now been just stored with this operation).
The  gap  of  time  between  now  (stop  of  motor  M2)  and  the  next  pressing  of  the 
PROG. button (see step 7 below) will be then stored as waiting time for Automatic 
Closing feature.

7 -  

Press  PROG.  button

,  M2  closes  and  the  Automatic  Closing  time  is  stored  (see 

DIP3 function to enable or disable the Automatic Closing feature). The gap of time 
between now (close of motor M2) and the next pressing of the PROG. button (see 
step 8 below)  will be stored as time delay between motor M2 and motor M1 closing, 
during normal operations. 

8 -  

Press the PROG. button

, motor M1 closes thus setting the delay time between M2 

and M1, as explained in step 7 above.

9 -  The LED DL1 will turn OFF, signalling exit from the Point D procedure. 
Closing  of the gate will be carried out at normal speed and only on approaching 
total closing at low speed (depending on the adjustment of LOW SPEED trimmer). 
10 -  

Turn  DIP2 to OFF

 position.

During Point D procedure, the safety devices (photocells and safety strip) are active.

POINT E

 -  PROGRAMMING FOR 1 MOTOR (M1) (#)

ATTENTION:  in order to manage one motor only, OPEN JUMPER JP17. 

1 -  The gate must be fully closed.
2 -  Turn 

DIP2 to ON

 position, the LED DL1 starts blinking

3 -  

Press PROG. button

, the motor M1 opens.

4 -  Once reached the open position, let 1 second pass and 

press the PROG button

 to 

cut out motor M1 (time travel of M1 has now been just stored with this operation). 
The  gap  of  time  between  now  (stop  of  motor  M1)  and  the  next  pressing  of  the 
PROG. button (see step 5 below) will be then stored as waiting time for Automatic 
Closing feature.

5 -  

Press  PROG.  button

,  M1  closes  and  the  Automatic  Closing  time  is  stored  (see 

Summary of Contents for R50

Page 1: ...code code R50 230V 50 60Hz AA21580 Peso max cancello Poids maxi portail Max gate weight Max Torgewicht 2000 kg 4460 lbs ITALIANO pag 04 FRANÇAIS pag 14 ENGLISH page 24 DEUTSCH pag 34 OPERATORE PER PORTONI INDUSTRIALI OPERATEUR POUR PORTAILS INDUSTRIELS OPERATOR FOR INDUSTRIAL DOORS TORANTRIEB FÜR INDUSTRIETORE ...

Page 2: ...E SAFETY OF THE PEOPLE IT IS IMPORTANT TO FOLLOW ALL THE INSTRUCTIONS INSTALLATIONSVORSCHRIFTEN BEACHTET WERDEN 1 Wenn nicht bereits an der elektrischen Schaltzentrale vorgesehen muss vor der Schaltzentrale ein thermomagnetischer Schalter installiert werden omnipolar mit einer minimalen Kontaktöffnung von 3 mm der ein von den internationalen Normen anerkanntes Konformitätszeichen besitzt Solch ein...

Page 3: ...pring Measurements in mm TECHNICAL DATA Max leaf length Max leaf weight Average opening time 90 Operating speed EEC Power supply Motor capacity Power absorbed Capacitor EEC Power supply Motor capacity Power absorbed Capacitor 230 50 60 Normative cycles 120 60 Normative cycles Daily cycles suggested Service Consecutive cycles guaranteed Grease Actuator weight Operating temperature Protection grade ...

Page 4: ...lide on the ground during operation turn the set screw on the spring clockwise to increase the pressure between the wheels and the ground To reduce wheel wear during operation loosen nuts D with a No 13 wrench and tilt the rubber wheels so that the axles coincide with the center of the gate leaf pivot point The wheels may be tilted by 0 to 7 5 Retighten the two nuts The R50 is equipped with two wa...

Page 5: ... these appropriate handles are placed so to avoid safety risks for the operator That the physical effort necessary to move the gate leaf should not be higher than 225 N for doors gates for private dwellings and 390N for doors gates for commercial and industrial sites values indicated in 5 3 5 of the EN 12453 norm A Maximum stroke 60 mm during movement holes or uneven ground B Remove the elastic pi...

Page 6: ... surfaces carefully once a week Check wheel ground pressure and condition of motor wheels every six months The motor should be overhauled every two years and the oil replaced ELECTRIC CONNECTIONS T2 code BC07086 T2 CRX code BC07085 AERIAL COAX R 2 2KΩ SIGNAL BUZZER 12Vdc for AUTOTEST EDGE 12Vdc for ACCESSORY SUPPLY PHOTOCELL EDGE K BUTTON PED BUTTON COM CAPACITOR M1 POWER SUPPLY MOTOR 1 MOTOR 2 CA...

Page 7: ...HASE AND CAPACITOR CONNECTIONS MOTOR 1 COMMON CONNECTION MOTOR 1 PHASE AND CAPACITOR CONNECTIONS DO NOT REMOVE ANY JUMPER OTHERWISE THE OPERATOR WILL NOT WORK only CRX control board DO NOT REMOVE ANY JUMPER OTHERWISE THE OPERATOR WILL NOT WORK Not available for R50 Built in radio module model CRX or connector for radio receiver RIB 12 Vdc supply To select 1 motor M1 or 2 motors M1 and M2 Programmi...

Page 8: ...d lock again the operators 2 Turn DIP1 to ON position The red LED DL1 starts blinking 3 Press the PROG button and hold it When GREEN LEDS DL3 and DL5 are on the gate leaves are opening with a phase shift of 2 seconds Check the leaves swinging and the opening mechanical stopper position movement is now performed in man present mode open close open etc If any of the leaf closes instead of opening re...

Page 9: ...e DL2 LED green will flash once 4 The code programming time resets automatically so that you can programme the next remote control 5 To finish programming let 10 seconds pass and then press the PROG button briefly The red DL1 LED will stop flashing 6 Reposition DIP 1 to OFF and DIP 3 to OFF N B IF THE DL1 LED CONTINUES TO FLASH RAPIDLY THIS MEANS THAT DIP 1 IS STILL POSITIONED TO ON AND ANY MANOEU...

Page 10: ...leaves the gate will close automatically after 1 second pause If DIP12 ON and DIP4 ON If the gate is opening and a vehicle crosses the photo beam the gate will continue to open When the vehicle leaves the gate will stop and then closes automatically after 1 second pause If the complete gate open position is reached before the vehicle leaving the DIP12 will be ignored and the automatic closing will...

Page 11: ... out a self check at the beginning of each operation During blackout At the return of the network power supply If the gate is totally closed It will remain closed If the gate is at the opening stage It will continue opening If the gate is totally open with dip 3 OFF It remains open Consequently closing operations of the gate can be controlled If the gate is totally open with dip 3 ON It remains op...

Page 12: ...TTER code ACG8028 for more than 2 photocells couples up to 4 COUPLE OF BUILT IN BOXES FOR THE FIT SYNCRO code ACG8051 CODE LEARNIG SYSTEM RADIORECEIVERS RX91 A quarzata and coupling code ACG5005 RX91 A quarzata and terminal board code ACG5004 RX433 A super eterodyne and coupling code ACG5055 RX433 A super eterodyne and terminal board code ACG5056 RX433 A 2CH super eterodyne 2 channel and coupling ...

Page 13: ...245 Rotore con albero CMO1320 Statore 230V 50 60Hz 1P CCM6302ZZ Cuscinetto 6302ZZ CTC1006 Chiavetta 6x6x20 CTC1069 Molla per R50 CTC1104 Paraolio 50x72x10 CTC1124 Seeger E28 CTC1136 Seeger I 80 CTC1206 Molla a tazza CTC1350 Anello di tenuta Codice Denominazione Particolare CTC1401 Paraolio 50x80x8 CTC1402 Paraolio30x47x7 CVA1029 Manopola MCG 28 85 GIR CVA1380 Copriventola motore CVA1381 Ventola CV...

Reviews: