background image

Adjustments and Calibration

5

3.0

Adjustments and Calibration

3.1

Mechanical Adjustments

To accommodate minor floor unevenness, scale feet can be used to adjust scale height up or down a fraction of an 

inch.   Adjust the feet by hand (lift the scale corner slightly with a pry bar) until all feet are contacting the floor 

equally. Jam nuts are supplied for locking the feet in place.
When height adjustments are complete, recheck level of the deck with a spirit level. The deck must be level 
within 

1

/

4

".

3.2

Corner Correction

All assembled Benchmark

 LP scales are delivered with the summing board corner-trimmed. Corner trimming is 

only necessary after replacing a load cell.
To calibrate the scale, the output from each load cell must be matched by adjusting the signals with 

potentiometers at the summing board—a process known as trimming.  

1. Remove the summing board cover and identify the correct load cell terminal corresponding to each 

corner (labeled CELL 1, CELL 2, and so on). See Figure 4-3 on page 8 for scale deck corner numbering.

2. The indicator must be connected and calibrated approximately, but it need not indicate the exact weight 

value. A test weight will be required. The recommended test weight for all Benchmark

 LP models is 

25% of scale capacity: for example, 25 lbs for 100-lb models, 250 lbs for 1000-lb models.

3. With no weight on the scale, zero the indicator. 
4. Turn all four potentiometers fully clockwise (shaded areas of Figure 3-1) to increase the reading until a 

clicking sound is heard from each potentiometer. This ensures the maximum signal from each load cell.

JP4

JP2

PT4

PT3

JP3

PT1

EXP

PT2

JP1

1

CELL4

1

CELL1

1

CELL3

1

CELL2

IND

-EX

-SI

SHD

+SI

+EX

M

R

N

I

-SI

S2C

I

A

G

+EX

+SI

-SI

SHD

-EX

I

S

G

A

L

T

+SI

M

S

I

N

L

T

R

+EX

-EX

-SI

SHD

+SI

+EX

+SI

-EX

-SI

SHD

-EX

SHD

+SE

-SE

+EX

Potentiometers

Jumper Locations
JP1 and JP2
Shaded

Jumper Locations
JP3 and JP4
Shaded

Potentiometers

Figure 3-1. Trim Potentiometers

5. Zero the indicator and place 25% of scale capacity using calibrated test weights over each load cell in 

turn.

6. Record the value displayed on the indicator after the test weight is placed in turn on each corner (directly 

over the load cell) without allowing the weight to overhang the sides. Allow the scale to return to zero 

each time to check for friction or other mechanical problems. Select the load cell which has the lowest 

value as your reference point. This cell will not be trimmed.

7. Replace the same test load over each cell in turn. Using the corresponding potentiometer, trim each cell 

down to equal the reference load cell. As corner corrections are somewhat interactive, check all cells 

again for repeatability. If necessary, repeat steps 5 and 6.

Summary of Contents for Benchmark LP

Page 1: ...104742 Benchmark LP Low Profile Bench Scale Installation Manual TM ...

Page 2: ......

Page 3: ...roubleshooting Guide 7 4 2 Periodic Maintenance 7 4 3 Load Cell Replacement 7 4 3 1 Load Cell Wiring to Summing Board 8 4 4 Replacement Load Cells 8 Benchmark LP Limited Warranty 9 2008 Rice Lake Weighing Systems All rights reserved Printed in the United States of America Specifications subject to change without notice April 2008 Technical training seminars are available through Rice Lake Weighing...

Page 4: ...ii Benchmark LP Manual ...

Page 5: ...ions Model Designations The model identification label is located on the side of the frame Include both model number and serial number when ordering replacement parts Electrical Grounding For systems where the scale is connected to a 115 VAC circuit the indicator must be directly connected to an earth ground with a ground interface cable of no more than 3Ω resistance throughout its length Load Cel...

Page 6: ...n conduit will be necessary In operation the scale must be level within 1 4 inch Either choose a site where the floor is close to this standard to avoid excessive shimming or modify the floor at the chosen site to meet this standard 2 2 Unpacking and Assembly 1 Remove all packing material and inspect scale for visible damage caused during shipment 2 Remove the four overload stops on the underside ...

Page 7: ...stainless steel platform 2 Remove lid in the center of the platform revealing the summing board coverplate 3 Remove security cables this will void NTEP Certification 4 Remove screws on the summing board coverplate and remove lid Wire Connections Remove the summing board cover and connect the wires to the INDICATOR terminal Figure 2 3 To connect the indicator wires to the appropriate connectors pus...

Page 8: ...to facilitate future lifting of the scale for servicing or cleaning 1 When the interface cable is protected and in its final position complete connections to the indicator See indicator installation manual for wiring information 2 If necessary trim corners as described in Section 3 2 on page 5 3 Check all strain relief for tightness Figure 2 4 Homerun cable wired to summing board and secured with ...

Page 9: ...25 of scale capacity for example 25 lbs for 100 lb models 250 lbs for 1000 lb models 3 With no weight on the scale zero the indicator 4 Turn all four potentiometers fully clockwise shaded areas of Figure 3 1 to increase the reading until a clicking sound is heard from each potentiometer This ensures the maximum signal from each load cell JP4 JP2 PT4 PT3 JP3 PT1 EXP PT2 JP1 1 CELL4 1 CELL1 1 CELL3 ...

Page 10: ...on to be certain that everything is seated 1 Load the scale to near capacity two or three times 2 With no load on the scale place the indicator in its calibration mode and perform a zero calibration 3 Place test weights on the platform not exceeding the scale s full capacity If several weights are used they should be evenly distributed around the platform 4 Perform a span calibration ...

Page 11: ...ance 4 2 Periodic Maintenance The space beneath the platform must be periodically cleaned to prevent debris buildup Caution Do not attempt to use scales with load cells that are not hermetically sealed in washdown applications Water damage is a common cause of failure in non hermetically sealed load cells Use care with high pressure steam washdowns for hermetically sealed load cells The steam may ...

Page 12: ...n is necessary after load cell replacement Follow the instructions in Section 3 2 and Section 3 3 4 3 1 Load Cell Wiring to Summing Board The four load cells are each wired to their respective terminals in the summing board according to the corner numbering system shown in Figure 4 3 and the coloring code in Table 4 1 3 4 1 2 Hole for homerun cable Figure 4 3 Corner numbering top view Table 4 1 Lo...

Page 13: ...ccident misuse neglect alteration improper installation improper repair or improper testing RLWS shall be the sole judge of all alleged non conformities Such equipment has not been modified altered or changed by any person other than RLWS or its duly authorized repair agents RLWS will have a reasonable time to repair or replace the defective equipment Buyer is responsible for shipping charges both...

Reviews: