background image

Manual

63300841

3

0

Troubleshooting / operating errors 

You are able to see errors and operating errors in the status messages of the LED display and then 

correct them accordingly. 

Reset should be carried out in the case that other non-defined conditions arise and the lock does not 

operate faultlessly even though the battery has been replaced. This resets the lock to factory default 

settings and all programming is deleted.  

Replacing the battery 

1.

TG 

Loosen the screw on the side of the cover 

(using a

 T6x60 mm Torx screwdriver

).

2. Open the battery compartment and remove the

battery pack. Disconnect the two-pole plug-in

connector from the battery pack.

3. Connect the new battery pack to the plug-in

connector and insert the battery into the housing.

4. Close the battery compartment and screw down.

Codes are not deleted when a battery is replaced. 

Notice: Please dispose the empty battery pack properly in accordance with the valid 
environmental regulations!

Battery monitoring / battery alarm 

Automatic battery monitoring on the SAFE-O-TRONIC

®

 63300841

3

0

 ensures that with inadequate

 

battery voltage 

he 

can no longer be operated.

There is an advance warning when all the LEDs flash twice. In this case it is 

recommended

 to 

replace the battery. 

An alarm is triggered after a while if the battery is not replaced.  This is indicated when the red and 

green LEDs light up in turn three times. The battery 

must

 now be replaced. In this condition the 

compartment can only be opened but no longer locked. 

The lock must only be operated using batteries approved. The use of non-approved batteries can 

lead to malfunctions and lock damage. 

Maintenance and care 

The SAFE-O-TRONIC

®

 

63300841

3

0

 is maintenance-free. In no case should the lock be oiled or

 

greased with lubricants containing mineral oil.  

Only use non-stick, residue-free cleaning agents and disinfectants for cleaning purposes. Do not use 

any heavy cleaning agents, acids or lyes when caring for the product. Also do not use a pressure 

cleaner. It is also not permitted to spray-wash the locks, for example using a hose. 

16

www.richelieu.com

Summary of Contents for SAFE-O-TRONIC access

Page 1: ...SAFE O TRONIC access Electronic Identification and Locking System Via Pin Codes Item No 6330084130 SAFE O TRONIC access Cabinet Lock Manual 6330084130 english 1 www richelieu com ...

Page 2: ...ease observe this important information Handling instructions These mark a work step during user input Safety and warning notes Please read before initial operation This manual describes the initial operation and operation of lock 6330084130 The equipment must only be used for the purpose intended by the manufacturer Please keep the instruction manual in an easily accessible place Unauthorised ame...

Page 3: ...Code 8 MasterCode1 8 MasterCode2 8 Code overview 8 Operation 9 Function control 9 Initial operation 10 Programming MasterCode2 10 Locking and opening using MasterCode2 11 Locking and opening using the UserCode 11 Further functions 12 Altering MasterCode2 12 Programming MasterCode1 13 Opening using MasterCode1 14 Release using MasterCode2 14 Further information 15 LED display 15 Troubleshooting ope...

Page 4: ...entry Abort key Code entries or programming operations can be rejected by pressing the abort key Keys 1 2 3 4 5 6 7 8 9 0 Number keys for Code entry Exchangeable plate LED display red green Capacity keypad Rotary knob X 1 2 3 4 5 6 7 8 9 0 4 www richelieu com ...

Page 5: ...ever A cropped or hook shaped locking lever can also be used depending on the properties and condition of the cabinet 5 Fastening screw for locking lever 6 Bush for fastening the lock to the door for door thickness from 10 mm to 18 mm 7 Bush for fastening the lock to the door for door thickness from 1 mm to 9 mm 8 Screw for fastening the lock to the door 9 Rotary knob 5 www richelieu com ...

Page 6: ...ten the grommet 3 for setting the rotational direction and the locking lever 4 using the screw 5 5 Test the lock function by means of the TestCode when the door is open 6 Test the function when the door is closed Replacement of the rotary knob as needed 1 Remove the screw 5 2 Using a TG 10 screwdriver item no 358008910 to loosen the fastening screw for the rotary knob by inserting through the thre...

Page 7: ...at is attached to the lock on the inside of the door The opening marked L points downwards 3 Rear side of the lock to which the grommet is attached If the lock is installed in a position where by the rotary knob is not at the top e g horizontal installation the grommet must be turned accordingly If the rotary knob is to be turned to the right for locking the grommet must be attached to the lock in...

Page 8: ...mployees cannot come into question as offenders Notice MasterCode1 cannot be programmed with 0 as the first number MasterCode2 MasterCode2 can be used by the operator of the facility at any time to open and close the compartment or release the lock A 5 to 10 digit code can be programmed as MasterCode2 Notice MasterCode2 cannot be programmed with 0 as the first number Code overview The following ta...

Page 9: ...is disabled for one minute as protection against manipulation The lock is blocked after 100 incorrect entries Blocking can only be released with MasterCode2 Function control All locks in the SAFE O TRONIC 6330084130 series are delivered with the same factory setting The TestCode for locking and opening is activated in the factory setting TestCode The TestCode can be used to carry out a simple SAFE...

Page 10: ...owledge of the programmed MasterCode2 Programming MasterCode2 Press the OK and abort keys simultaneously Enter new MasterCode2 Notice 3 5 1 9 7 is only an example code Press the OK key Enter new MasterCode2 one more time Press the OK key Please note The programming procedure will be terminated automatically if a key is not pressed within approx 3 seconds X 3 1 9 7 5 and 3 1 9 7 5 10 www richelieu ...

Page 11: ...ing MasterCode2 Notice 3 5 1 9 7 is only an example code Then press the OK key Turn the knob Locking and opening using the UserCode The user has the possibility to enter a random 4 digit UserCode and lock or open the compartment Enter the UserCode Notice A four digit code must be entered 9 0 6 0 is only an example code Then press the OK key Turn the knob 3 5 1 9 7 5 9 6 0 0 11 www richelieu com ...

Page 12: ...tive MasterCode2 Notice 3 5 1 9 7 is only an example code Press the OK key Press 2 2 for MasterCode2 Press the OK key Enter new MasterCode2 Notice 4 8 2 7 3 is only an example code Press the OK key Enter new MasterCode2 one more time Press the OK key X 3 1 9 7 5 and 4 2 7 3 8 4 2 7 3 8 2 12 www richelieu com ...

Page 13: ...e2 is not permitted Press the OK and abort keys simultaneously Enter active MasterCode2 Notice 3 5 1 9 7 is only an example code Press the OK key Press 1 1 for MasterCode1 Press the OK key Enter new MasterCode1 Notice 9 0 6 0 9 is only an example code Press the OK key Enter new MasterCode1 one more time Press the OK key X 3 1 9 7 5 and 9 6 0 9 0 9 6 0 9 0 1 13 www richelieu com ...

Page 14: ... that is fitted with a SAFE O TRONIC 6330084130 is opened using MasterCode1 it stays blocked for the entry of a UserCode The SAFE O TRONIC 6330084130 then has to be released again using MasterCode2 Enter active MasterCode2 Notice 3 5 1 9 7 is only an example code Press the OK key The blocked SAFE O TRONIC 6330084130 is now released again for further operation 9 6 0 9 0 3 1 9 7 5 14 www richelieu c...

Page 15: ... error the rotary knob was not operated within the released period Alternate Waiting for rotary knob to be operated 1 second Lock has been locked programming successful 2 seconds Lock has been unlocked second Code accepted 3 seconds Internal malfunction lock may have to be replaced Red LEDs light up first then the green LEDs for a second in each case Blocking triggered by MasterCode 1 cancelled by...

Page 16: ...ental regulations Battery monitoring battery alarm Automatic battery monitoring on the SAFE O TRONIC 6330084130 ensures that with inadequate battery voltage he can no longer be operated There is an advance warning when all the LEDs flash twice In this case it is recommended to replace the battery An alarm is triggered after a while if the battery is not replaced This is indicated when the red and ...

Page 17: ... lockings per day Temperature ranges Function 0 to 60 C Storage 15 to 70 C Relative humidity 10 90 non condensing Protection class according to DIN EN 60529 IP 43 Weight approx 300 g Housing dimensions incl rotary knob H x W x D 151mm x 38mm x 33mm Colour of housing frame Similar to RAL 9006 white aluminium Colour of the control panel Black Door thickness 1 to 18 mm 17 www richelieu com ...

Page 18: ...0084130 Drilling template Notice Depending on the printer there can be dimensional deviations when printing this drilling template Therefore please remeasure the drilling template before use 18 www richelieu com ...

Reviews: