background image

A-Frame Fault Locator

999-995-095.10_REV. A

11

• If the paved area is relatively small, the

receiver can be used around the periphery
of the area. The receiver can be rotated
side to side, and where the receiver di-
rectional arrows and beeping toggle back
and forth, extend a straight line perpendicu-
lar to the center of the A-Frame Receiver.
Do this in several locations around the
suspected fault area. The straight lines
should all intersect at the same point. This
is the location of the fault. This method of
locating is less exact than placing the re-
ceiver directly over the conductor. 

See

Figure 13.

• An alternate way to locate below paved

surfaces is to improve the conductivity be-
tween the pavement and the receiver with
water. One method is to attach sponges to
the spikes of the receiver. Wet the sponges
with water and keep wet. Conduct the fault
locate normally.

• Another method is to wet the surface of the

pavement with water and conduct the fault
locate normally. Do not do this in the area
of the transmitter – this increases the risk of
electrical shock.

Figure 13 – Locating below paved surfaces

Multiple Faults

If there are multiple faults in the conductor,
the faults will have signals proportional to
the amount of current leaking. The locate is
done the same as for a single fault, but the
signal strength will not be as strong. Typically,
the largest fault (least resistance fault) is
easiest to find. Best practice is to find and re-
pair the first fault and continue the locate
for other faults.

Path Locating

The FT-103 Transmitter can be used with other
commercially available receivers (such as the
RIDGID SeekTech or NaviTrack receivers) to
path locate conductors. The FT-103 transmitter

can be used to apply an active tracing signal to
a conductor in three ways: 

• Direct Connect – The transmitter’s leads

are connected directly to the target conduc-
tor and a suitable ground. This method is
most commonly used when the target util-
ity is accessible. Direct connect should not
be used for energized (live) conductors.

• Inductive Clamp (optional equipment) –

the jaws of the inductive clamp encircle
the target conductor; if the conductor is in-
sulated, there is no metal to metal contact.
This method is commonly used when the
target utility is accessible but direct con-
nect is not possible on an insulated cable.

• Broadcast Inductive Mode – The transmit-

ter generates a field, which in turn induces
a current in the target conductor. There is no
direct connection between the transmitter
and the target conductor. The transmitter is
placed over and inline with the target con-
ductor. The transmitter’s internal antenna in-
duces a signal onto the target conductor.
This method is most commonly used when
the target utility is not accessible.

Disconnect all loads from the conductor to
be tested and all neighboring conductors to
prevent damage from high voltage and false
reading.

Direct Connect Path Locating
Method

1. Insert supplied ground stake into the

earth. Or, if other good grounds are avail-
able in the area, they can be used. 

A good ground results in a stronger tracing

signal. To get a good ground, insert the
ground stake as far as possible into the
earth. Moist earth will give a better ground
than dry earth. Wetting the earth around
the ground stake can improve grounding.
This lowers the resistance of the circuit.
While moist earth around the ground
stake improves the circuit, do not use the
transmitter in areas that are wet, this can
increase the risk of electrical shock.

The far end of the conductor should be

grounded.

2. Make sure that the transmitter is OFF.

3. Connect BLACK test lead to the ground

stake. Always connect to the ground stake
first.

4. Connect the BLACK and RED test leads

to the Transmitter.

Conductor

Fault

Paved Area

www.

GlobalTestSupply

.com

Find Quality Products Online at:

sales@GlobalTestSupply.com

Summary of Contents for A-Frame Fault Locator

Page 1: ...me Fault Locator Model FT 103 Transmitter and Model FR 30 Receiver Français 15 Castellano pág 33 A Frame Operator s Manual www GlobalTestSupply com Find Quality Products Online at sales GlobalTestSupply com ...

Page 2: ...er A Frame 7 Pre Operation Inspection 7 Set Up And Operation Instructions 7 Fault Locating Connecting Transmitter 8 Locating 9 Locating Below Paved Surfaces 10 Multiple Faults 11 Path Locating Direct Connect Path Locating Method 11 Inductive Clamp Path Locating 12 Broadcast Inductive Path Locating 12 Storage 13 Maintenance Cleaning 13 Calibration 13 Service And Repair 13 Optional Equipment 14 Disp...

Page 3: ...etain product serial number which is located on nameplate Serial No WARNING Read this Operator s Manual carefully before using this tool Failure to understand and follow the contents of this manual may result in electri cal shock fire and or serious personal injury www GlobalTestSupply com Find Quality Products Online at sales GlobalTestSupply com ...

Page 4: ... result in serious personal injury Use personal protective equipment Al ways wear eye protection Protective equip ment such as dust mask non skid safety shoes hard hat or hearing protection used for appropriate conditions will reduce per sonal injuries Do not overreach Keep proper footing and balance at all times This enables better control of the power tool in unex pected situations Do not let fa...

Page 5: ...all instructions and warnings may re sult in property damage and or serious in jury rect equipment will do the job better and safer at the rate for which it is designed Do not use equipment if the switch does not turn it ON and OFF Any tool that can not be controlled with the switch is dan gerous and must be repaired Remove the battery pack from the equip ment before making any adjustments changin...

Page 6: ... detects the current flow to ground through the insulation fault The re ceiver provides audio and visual indications of both signal strength and direction to assist in detecting and locating the fault For the A Frame fault detector to work the conductor must be in contact with the earth it will not work with conductors in conduit Additionally the transmitter can be used to apply a signal to the co...

Page 7: ...mitter Set for Fault Finding dFF displayed in Frequency area 1 6 Transmitter Set for Inductive Clamp Use for Path Locating Insert Inductive clamp into Jack 7 Transmitter Set for Direct Connect Use for Fault Finding or Path Locating 8 Transmitter Set for Broadcast Inductive Mode for Path Locating 9 Transmitter Battery Status 5 8 1 3 4 2 6 7 Transmitter Display 9 Figure 3 Transmitter Display Display...

Page 8: ...on the trans mitter or receiver display the bat teries need to be replaced Use the batteries that are of same type Do not mix battery types Do not mix new and used batteries Mixing batteries can cause overheating and battery damage Path locating 128 Hz 1 kHz 8 kHz 33 kHz 93 kHz Direct Connect 128 Hz 1 kHz 8 kHz 33 kHz 93 kHz Inductive Clamp 8 kHz 33 kHz 93 kHz Broadcast Inductive 33 kHz 93 kHz Loa...

Page 9: ...er service com ponents or anything that might be af fected by high voltage De energize any circuits in or around the work area Always attach transmitter test leads be fore turning unit ON and turn unit OFF be fore disconnecting leads This will re duce the risk of electrical shock Never turn transmitter ON the unit when anyone is touching the conductor ground stake or any part of the transmitter Tu...

Page 10: ...establishes a current flow the current leaks to ground through the insulation fault A Frame Fault Locator 999 995 095 10_REV A 8 and back to the ground stake The Model FR 30 Receiver detects the current flow to ground through the insulation fault For the A Frame fault detector to work the conductor must be in contact with the earth it will not work with con ductors in conduit Generally the A Frame...

Page 11: ...C TIONS The target conductor is energized and there is the risk of electrical shock Use high voltage precautions to disconnect 2 When fault locating generally the receiver should be used over the conductor with the front receiver spike towards the ex pected fault and the rear receiver spike to wards the ground stake The receiver spikes should evenly penetrate the earth to make good electrical cont...

Page 12: ...he loca tion and continue down the conductor path looking for a fault signal strength closer to the reference signal Once a fault is located with a signal similar to the reference signal turn the A Frame Locator perpendicular to the path of the conductor Move the receiver back and forth until slight movement causes the di rectional arrows and beeping to toggle back and forth At this point the faul...

Page 13: ...s are connected directly to the target conduc tor and a suitable ground This method is most commonly used when the target util ity is accessible Direct connect should not be used for energized live conductors Inductive Clamp optional equipment the jaws of the inductive clamp encircle the target conductor if the conductor is in sulated there is no metal to metal contact This method is commonly used...

Page 14: ...ct the cable lead from the target conductor first before removing the cable lead from the ground spike to reduce the risk of electrical shock Disconnect the cable lead from the ground spike Inductive Clamp Path Locating 1 This method requires an inductive clamp Optional equipment Read and follow A Frame Fault Locator 999 995 095 10_REV A 12 all instruction for the use of the inductive clamp 2 Inse...

Page 15: ...Figure 16 One way to confirm that you are tracing the target conductor and not the transmitter field is to look for a strong stable proximity signal and a valid depth measurement on the receiver While directly over the ener gized line you can also raise the receiver a set distance off of the ground and verify that the depth reading on the display e quals the distance that you raised the re ceiver ...

Page 16: ...ainst harmful interference in a resi dential installation This equipment generates uses and can ra diate radio frequency energy and if not in stalled and used in accordance with the in structions may cause harmful interference to radio communications However there is no guarantee that interfer ence will not occur in a particular installation If this equipment does cause harmful interfer ence to ra...

Page 17: ...s estados de los EE UU no permiten la exclusión o restricción referente a daños in cidentales o consiguientes Por lo tanto puede que la limitación o restricción mencionada anteriormente no rija para Ud Esta garantía le otorga derechos específicos y puede que además Ud tenga otros derechos los cuales varían de estado a estado provincia a provin cia o país a país No rige ninguna otra garantía expres...

Reviews: